background image

28467 Rev I

10

02-02

NOVUS TOP DV GAS APPLIANCE INSTALLATION INSTRUCTIONS

e. Termination

Vent termination must not be recessed in the wall or siding. Siding may be brought to the edge of the cap

base.
Install the cap as shown in Figure 12. Cap pipe sections should overlap the vent pipe by 1½ inches. Caulk

outside edges of cap.
Local codes may require the installation of a shield which prevents the cap from accidentally touching

anything or anyone.
Figure 13 illustrates cap locations prescribed by current ANSI Z273.1 and CAN/CGA-B149 Installation

Codes.

Figure 13 - Termination Cap Locations

Dimension Descriptions

A

Clearance  above  the  ground,  a  veranda,  porch,  deck  or

balcony - 12 inches (30 cm) minimum. *

B

Clearance to window or door that may be opened –  10,000

BTUs  or  less,  6  inches  (15  cm)  minimum;  10,000-50,000

BTUs,  9  inches  (23  cm)  minimum;  over  50,000  BTUs,  12

inches (30 cm) minimum. *

C

Clearance  to  permanently  closed  window  –  12 inches  (30

cm)  minimum  -  recommended  to  prevent  condensation  on

window.

D

Vertical  clearance  to  ventilated  soffit  located  above  the

termination  within  a  horizontal  distance  of  2  feet  (60  cm)

from  the  centerline  of  the  termination  –  18 inches  (46  cm)

minimum. **

E

Vertical clearance to unventilated soffit - 12 inches (30 cm)

minimum. **

F

Clearance to outside corner - 6 inches (15 cm) minimum.

G

Clearance to inside corner - 6 inches (15 cm) minimum.

H

Not to be installed above a meter/regulator assembly within

3 feet (90 cm) horizontally* from the center line of the regulator

I

Clearance  to  service  regulator  vent  outlet  -  6  feet  (1.8m)

minimum. *

J

Clearance to non-mechanical air supply inlet into building or

the combustion air inlet to any other appliance - 12 inches

(30 cm) minimum. *

K

Clearance  to  mechanical  air  supply  inlet  -  6    feet  (1.8  m)

minimum. *

L

Clearance  above  a  paved  sidewalk  or  paved  driveway

located on public property - 7 feet (2.1 m) minimum.

A vent may not terminate directly above a sidewalk or paved

driveway  which  is  located  between  two  single  family

dwellings  and  serves  both  dwellings.

M

Clearance under veranda, porch, deck or balcony - 12 inches

(30  cm)  minimum.  *  Recommended  30  inches  (76  cm)  for

vinyl or plastic.
Only  permitted  if  veranda,  porch,  deck  or  balcony  is  fully

open on a minimum of 2 sides beneath the floor. *

N

Vertical clearance between two horizontal termination caps

– 12 inches (30 cm) minimum.

O

Horizontal  clearance  between  two  horizontal  termination

caps – 12 inches (30 cm) minimum.

*

As specified in CGA B149 Installation Codes

Note:  Local  codes  or  regulations  may  require  different

clearances.

**

Clearance  required  to  vinyl  soffit  material  –  30 inches  (76

cm) minimum. With a vinyl soffit shield – 18 inches (46 cm)

minimum.

WARNING!

In  the  U.S.:

  Vent  system  termination  is  NOT  permitted  in

screened  porches.  You  must  follow  side  wall,  overhang

and ground clearances as stated in the instructions.

In  Canada:

  Vent  system  termination  is  NOT  permitted  in

screened porches. Vent system termination is permitted in

porch areas with two or more sides open. You must follow

all side wall, overhang and ground clearances as stated in

the  instructions.
Hearth Technologies Inc. assumes no responsibility for the

improper  performance  of  the  appliance  when  the  venting

system does not meet these requirements.

All manuals and user guides at all-guides.com

Summary of Contents for GNDC30

Page 1: ...y phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation a...

Page 2: ...nting must not be connected to chimney flue servicing a solid fuel burning appliance or a gas fuel burning appliance 7 NEVER use gasoline gasoline type lantern fuel kerosene charcoal lighter fluid or...

Page 3: ...atest edition in the U S A and the CAN CGA B149 Installation Codes in Canada This Novus Series gas appliance has been tested and listed for use in manufactured housing mobile homes These installation...

Page 4: ...de Number B Black Firebox GNDC36LEB EXAMPLE Gas NOVUS Direct Vent Heat Circulating 36 Propane Gas Electronic Ignition appliance with Black Firebox Components Description CS Cap Shield VP TV Vertical T...

Page 5: ...gure 2 Appliance Clearances to Combustible Materials A hearth extension is not required for this appliance L E D O M A B C D E 0 3 C D N G 9 2 3 4 4 3 7 8 85 8 3 3 4 3 1 2 3 3 C D N G 2 3 3 4 7 3 7 8...

Page 6: ...3 H D N G 8 7 1 4 4 3 6 3 This appliance may be placed on a smooth combustible or noncombustible continuous flat surface When the appliance is installed directly on carpeting tile or other combustibl...

Page 7: ...as fuel burning appliance WARNING RISK OF FIRE If you have chosen horizontal termination be sure there are no future obstructions from trees bushes snow drifts etc CAUTION Provisions shall be made to...

Page 8: ...n Never allow the vent to run downward This could cause high temperatures and may present a fire hazard Figure 8 Vent Lengths with Two Elbows Figure 9 Vent Lengths with Three Elbows Note Horizontal ru...

Page 9: ...national codes and not be easily blocked or obstructed If the hole being penetrated is of noncombustible materials a 9 diameter hole is acceptable Note Exterior wall thickness must be a minimum of 4 t...

Page 10: ...6 feet 1 8m minimum J Clearance to non mechanical air supply inlet into building or the combustion air inlet to any other appliance 12 inches 30 cm minimum K Clearance to mechanical air supply inlet...

Page 11: ...aterial WARNING The horizontal run of vent must have a rise for every 1 ft of run towards the termination Never allow the vent to run downward This could cause high temperatures and may present a fire...

Page 12: ...ter vent Figure 17 Installing the Firestop Spacer e Chase Termination Installation Figure 18 and 19 and Table 1 specify minimum chimney heights for various pitched roofs These chimney heights are nece...

Page 13: ...into the outer flue of section B See Figure 20 Once both inner and outer flues are started press section A into section B firmly until all lances have snapped into place Tug slightly on section A to...

Page 14: ...utoff valve The incoming gas line should be piped into the valve compartment and connected to the 1 2 FIP connection provided on the manual shutoff valve All connections must be tightened and checked...

Page 15: ...C D N G 0 3 H D N G 0 3 C D N G m m 6 5 2 n i 1 0 1 m m 3 4 2 n i 6 9 0 e z i S e c i f i r O s a G e n a p o r P m m 0 5 1 n i 9 5 0 n m u l o C r e t a W s e h c n i s e t a c i d n i Table 2 Gas In...

Page 16: ...o a thermostat If connecting a 24V thermostat not supplied disconnect the black wire from the transformer at the ignition control Connect the thermostat wires between the ignition control and the blac...

Page 17: ...will withstand high temperatures General Electric RTV103 Black or equivalent Rutland Inc Appliance Mortar 63 or equivalent A high temperature sealant 1 8 inch wide minimum must be used to close off g...

Page 18: ...but does not cover the holes in the burner pan This will provide the glowing embers look See Figure 37 Figure 36 Placing the Vermiculite and Lava Rock top logs removed for clarity Figure 37 Placing th...

Page 19: ...P Read the safety information above on this label 2 Turn wall switch to the OFF position 3 This appliance is equipped with an ignition device which automatically lights the burner Do not try to light...

Page 20: ...ANCE 1 Turn wall switch to the OFF position or set thermostat to lowest setting 2 Open the control access panel 3 Turn manual shutoff valve to CLOSED Wait five minutes to clear out any gas Then smell...

Page 21: ...decide to shut down the appliance for a long period of time a Turn all wall switches to OFF b Turn pilot knob on valve to OFF c Turn the gas line to CLOSED Lighting the Appliance During Regular Use Tu...

Page 22: ...l B 2 o t n i g e b l l i w s e m a l f e h t d n a n o i t a r e p o l a m r o n f o t l u s e r a s i s i h T n r u b o t d e w o l l a s i e c n a i l p p a e h t s a w o l l e y 3 e c n a i l p p...

Page 23: ...re cleaning 2 CHECKING THE FLAME PATTERNS Visually check the flame of the burner periodically making sure the flames are steady not lifting or floating The flame color should be blue with yellow tips...

Page 24: ...THE GLASS See Figure 44 Never operate this appliance without the glass properly secured in place or if the glass if broken or chipped In the event of glass breakage carefully remove the glass frame Th...

Page 25: ...ote Control Standing Pilot RCT MLT HTL Multi Function Remote Control SMART STAT HTL Remote Control with Thermostat Control SMART BATT HTL Battery operated Remote Control with Thermostat Control GP30 C...

Page 26: ...1 1 1 3 4 0 8 6 2 3 0 8 6 2 2 0 8 6 2 6 3 y l b m e s s A n e e r c S 3 3 y l b m e s s A n e e r c S 0 3 y l b m e s s A n e e r c S 1 1 1 4 2 1 7 2 2 1 1 7 2 2 0 1 7 2 2 6 3 e m a r F w s s a l G c...

Page 27: ...s 14 Minimum Installation MI Sections 13 Slip Sections Assembly 14 Through the Wall 9 Vermiculite 18 Vertical Installation 3 Vertical Termination Chimney Height 12 Clearances 11 Multiple Terminations...

Page 28: ...afting caused by tight sealing construction of the structure air handling devices such as exhaust fans or forced air furnaces or other causes 5 use of fuels other than those specified in the Operating...

Reviews: