14
Heatilator • Birmingham BIR50-B Installation Manual • 4059-701 • Rev G • 06/29/15
3 ft min. from
top of uppermost
chimney section
to air inlet.
G. Outside Air Kit
Outside air kits must be used for combustion and to pro-
vide cooling air to prevent overheating. Hearth & Home
Technologies recommends you utilize the shortest duct
run to optimize the performance of the outside air kit. The
outside air inlet hoods should be positioned in a manner
that will not allow snow, leaves, etc. to block the inlet. In
some installations the air duct may need to be run verti-
cally. In such an installation, a 3 ft (914 mm) height differ-
ence must be maintained from the top of the uppermost
chimney section to the outside combustion air inlet hood.
Refer to Figures 3.8 and 3.9 when placing the outside air
inlet hood.
WARNING! Risk of Fire!
The outside air kits are installed
on the both sides of the fireplace to prevent overheating
and fire.
• Cut a 6 in. (152 mm) hole in outside wall to accommodate
air piping.
• Use 6 in. (152 mm)flex (not supplied) to directly connect
outside air to fireplace intake. Insulate the pipe to prevent
frost condensation.
• Use the supplied outside air inlet hoods.
• Seal between the wall and the pipe with silicone to
prevent moisture penetration and air leaks.
• Seal between the outside air inlet hoods and the house
with silicone to prevent air infiltration.
CAUTION! Risk of Cuts/Abrasions.
Wear protective
gloves and safety glasses during installation. Sheet metal
edges are sharp.
CAUTION!
Risk of Fire or Asphyxiation!
DO NOT
draw
outside combustion air from wall, floor or ceiling cavity, or
enclosed spaces such as an attic or garage.
•
DO NOT
place outside air inlet hood close to exhaust
vents or chimneys. Fumes or odor could be drawn into
the room through the fireplace.
• Locate outside air inlet hood to prevent blockage from
leaves, snow/ice, or other debris. Blockages could cause
combustion air starvation.
Figure 3.8 Outside Air Inlet Locations
Outlet placed
higher than 3 ft
below the
termination cap
Attic space
Garage or
combustible
liquids storage
Outlet blocked by
snow, leaves, etc.
Clear area
outside
house or in
ventilated
crawl space
YES
NO
NO
NO
NO
Factory-built
fireplace
• Use UL181 Class 0 or Class 1 rigid or flexible ducting.
• Install with short run or mainly straight duct, except small
dip for cold air trap which will help prevent flow of cold air.
• Secure flex duct with screws or wire ties.
Figure 3.9 Outside Air Installation
Outside air in-
stalled on both
sides (right side
not shown)
NOTICE:
The fireplace provides some outside air for
combustion. Other methods may be necessary if more air
is required.