background image

19

Heatilator • Birmingham BIR50-B Installation Manual • 4059-701 • Rev G • 06/29/15

Elbow Strap

30° or 15°

Elbow

Figure 4.6

Elbow Strap

1 per

Section

Figure 4.7

I.  Offset Elbow Installation

A 30° Elbow (measured from the vertical) is the largest 

that can be used in an offset. A 30° Elbow may not be 

combined with another Elbow to make a steeper offset 

(e.g. two 30° Elbows are not allowed to be put together to 

form a 60° elbow.). Avoid Elbows if possible. A totally ver-

tical chimney is more efficient. When Elbows are neces-

sary to avoid obstructions such as rafters, ridgepoles, or 

joists, you are only allowed to use 2 pair of Elbows in any 

one chimney system. Horizontal runs of chimney violate 

building code and are not allowed.
•  Attach elbows

  Attach  elbow  to  chimney  section  or  other  elbow  by 

mating the male and female ends with each other and 

using  four  sheet  metal  screws  provided. Attach  one 

elbow to the chimney section below, and align it for the 

offset. Determine the required offset length and attach 

an appropriate length (or lengths) of chimney section(s) 

above the elbow. Attach the second elbow above the 

chimney section to complete the offset (Figure 4.6).

•  Secure offset

  Use  an  elbow  strap  to  secure  the  offset.  Secure  the 

elbow strap’s band to chimney around the upper portion 

of the top elbow, then tighten the nut and bolt until the 

clamp is firm. Wrap the elbow strap end over an adjacent 

joist or rafter and secure it with at least two 8-penny nails 

or two #8, 1-1/2” screws. Add additional elbow straps 

for each section of chimney in the offset (Figure 4.7). 

Every chimney section in the offset must be supported. 

Do not add more chimney sections until the elbows and 

offset are supported. Be sure that the chimney remains 

vertical.

Chase

Frame

Stabilizer

Plumbers

Tape

Install supplementary

support if height exceeds

50 ft or if required by 

fireplace manufacturer

Each supplementary

support holds up to

25 ft. of chimney

Maintain 2 in. clearance

from chimney to framing

Figure 4.8

Figure 4.9

J.  Supplementary Support & Stabilizer

Install a supplementary support if total chimney height 

is greater than 50-feet, or if the fireplace manufacturer 

requires it. If additional support is needed, install one or 

more supplementary supports which can each support 25-

feet of chimney (Fig. 4.8). 
•  Clamp the supplementary support band around the pipe 

using the nut and bolt provided, and anchor the support 

to nearby building framing.

•  Always maintain the 2” clearance to combustibles from 

the  chimney  pipe. A  stabilizer  is  available  and  may 

be  required  by  some  fireplace  manufacturers  to  keep 

the  chimney  vertical  and  help  maintain  clearances  to 

combustibles within a chase.

•  Clamp the stabilizer to the pipe using the nut and bolt 

provided,  and  secure  legs  to  nearby  framing  using 

plumber’s tape or guy-wires (Fig. 4.9).

Note: 

The  stabilizer  does  not  support  the  weight  of  the 

chimney, it is only used to keep chimney centered within 

a chase.

Summary of Contents for BIR50-B

Page 1: ...r flammable materials Keep clothing furniture draperies and other flammable materials away INSTALLER Leave this manual with party responsible for use and operation OWNER Retain this manual for future...

Page 2: ...r Kit 14 4 Chimney and Termination Installation A Chimney Requirements 15 B Clearances 17 C Installation Notes 17 D Frame Openings 17 E Cut Roof Opening 17 F Install Firestop 17 G Assemble Chimney Sec...

Page 3: ...ated to party responsible Combustible materials not installed in non combustible areas Verified all clearances meet installation manual requirements Mantels and wall projections comply with installati...

Page 4: ...ass Plasters Materials reported as passing ASTM E 136 Standard Test Method for Behavior of Metals in a Vertical Tube Furnace at 750 C C Combustible Materials Materials made of or surfaced with any of...

Page 5: ...Framing headed off in ceiling joists Enclosed space above and around fireplace Mantel and surround Decorative facing and trim Hearth extension Factory built fireplace Protective metal hearth strip s...

Page 6: ...on Framing and Clearances Section 3 NOTICE A minimum 1 1 2 in air clearance at the back and sides of the fireplace assembly must be main tained Chimney sections at any level require a 2 in mini mum ai...

Page 7: ...peak Location NOT recommended Not the highest point of the roof Wind loading possible Multi level Roofs Windward Leeward Recommended Location Above peak Recommended Insulated exterior chase in cooler...

Page 8: ...dry Remove fireplace and components from packaging and inspect for damage Vent system components and doors are shipped in separate packages Report to your dealer any parts damaged in shipment Read al...

Page 9: ...in 282 mm 6 7 8 in 175 mm 5 in 129 mm 50 in 1270 mm 60 7 8 in 1546 mm 3 3 4 in 97 mm 38 in 965 mm 54 in 1372 mm 74 1 8 in 1883 mm 70 3 4 in 1797 mm 16 1 8 in 408 mm 11 1 8 in 282 mm 6 7 8 in 175 mm 5...

Page 10: ...n to floor 2 in 51 mm min Shaded areas represent 2 in 51 mm min air space clearance required around pipe Combustible Object 48 in 1219 mm 1 in B Clearances Warning Risk of Fire You must comply with al...

Page 11: ...on Storm Collar Figure 3 3 Chase Assembly 1 2 3 All outside walls should be insulated Figure 3 4 Chase Constructions 1 Fireplace and chimney enclosed in an exterior chase 2 Chimney offset through exte...

Page 12: ...2 74 1 2 12 21 mm 1572 724 1892 305 533 Model Adjust header height for raised floor under fireplace RUTH50 B If interior of chase will be drywalled add the thickness to this measurement The header can...

Page 13: ...ing approximately 26 in x 4 in 660 mm x 102 mm included with this fireplace Slide each metal strip 2 in 51 mm under front edge of fireplace Overlap strips in the middle of fireplace opening by 1 in 25...

Page 14: ...ne to prevent moisture penetration and air leaks Seal between the outside air inlet hoods and the house with silicone to prevent air infiltration Caution Risk of Cuts Abrasions Wear protective gloves...

Page 15: ...ht 50 15 24 Maximum chimney length between an offset and return 20 6 10 Maximum distance between chimney stabilizers 25 7 62 Maximum unsupported chimney length between the offset and return 6 1 83 Max...

Page 16: ...on of the bottom of the termination cap Subtract the effective height of the fireplace assembly see Figure 4 1 from the total vertical height to determine the overall height of the chimney installatio...

Page 17: ...n Dura Vent directly D Frame Openings From the ceiling drop a plumb bob to the center of the fireplace s flue outlet and mark this center point on the ceiling Mark appropriate cutting lines around the...

Page 18: ...himney section s Warning Risk of Fire Do not use offset returns greater than 30 ft Chimney draft will be restricted and could cause overheating and fire Measure the shift required to avoid the overhea...

Page 19: ...ow strap end over an adjacent joist or rafter and secure it with at least two 8 penny nails or two 8 1 1 2 screws Add additional elbow straps for each section of chimney in the offset Figure 4 7 Every...

Page 20: ...members Note Roof radiation shields do not allow for a reduced clearance to combustibles Clearance to combustibles must be a minimum of 2 away from the chimney pipe Install roof radiation shields at e...

Page 21: ...needed provided the air ventilation requirements are maintained See Figure 4 15 Spacing clips can be field fabricated as needed out of 24 GA sheet metal or other suitable non combustible material refe...

Page 22: ...lant Be sure chimney and offsets are properly supported Apply a non hardening waterproof sealant around the chimney at the point where the storm collar will meet the chimney just above the flashing Fi...

Page 23: ...6 m above any portion of the roof or adjacent structures within 10 ft 3 m of the chimney Chimney must extend 3 ft 9 m above the roof Chimney must extend 2 ft 6 m above any portion of the roof or adja...

Page 24: ...ted but they must meet the requirements as specified in these instructions Shrouds must be constructed of a minimum 24 ga 024 in stainless steel aluminized steel galvanized steel or copper Other mater...

Page 25: ...ud used The three basic shroud styles are 1 House 2 Arch or Mailbox and 3 Pyramid Most factory fabricated shrouds will fall under one of these basic style categories B House Style Shroud The house sty...

Page 26: ...n Total Open Area in mm in mm in mm in mm in mm sq in sq in 14 355 6 154 3911 6 24 609 6 32 812 8 32 812 8 520 1040 D Pyramid Style Shroud The pyramid style shroud is roughly square or rectangular wit...

Page 27: ...hearth may be the same height Finished combustible wall Combustible material Non combustible decorative facing Tile stone or other non combustible material Hearth Refractory 2 x 4 header flush with f...

Page 28: ...8 in 1270 mm x 965 mm to allow for door installation If Mortar is applied it should be applied after finishing material is installed Mortar will be applied between finishing materials and molded brick...

Page 29: ...non combustible sealant Tile stone or other non combustible material Floor constructed of wood or other combustible material 1 in Micore and 1 2 in Durock or equivalent insulation see Table Fireplace...

Page 30: ...n Finishing Figure 6 6 Raised Platform Hearth Extension Detail 2 Raised Hearth Extension and Raised Fire place Non combustible flooring a minimum of 20 in 508 mm in front of and 12 in 305 mm to each s...

Page 31: ...creating the platform allow for the thickness of the non combustible finishing materials Seal gaps between the hearth extension and the front of the fireplace with a bead of non combustible sealant o...

Page 32: ...pening 12 in 305 mm 1 1 2 in 38 mm maximum Mantel 22 in 559 mm minimum Combustible Decorative Facing Seal joint with non combustible sealant 6 in 152 mm minimum 12 in 305 mm minimum Grid represents 1...

Page 33: ...ll two refractory clips in the mortar lines across the top Tighten these and all previously installed brackets C Install Side Molded Brick Panel If a gas line is to be installed remove the knockouts i...

Page 34: ...ip Rod Screen Clip Inside Firebox Top of Fireplace E Install Mortar Optional The brick panels have been designed for installation without the use of mortar being necessary If the look of mortar is pre...

Page 35: ...e Gas Appliances for Installation in Vented Fireplaces Must be installed in accordance with the National Fuel Gas Code ANSI Z223 1 A gas log set must incorporate a gas shutoff Gas log set requires the...

Page 36: ...4 DCA E15 15 degree Elbow 14DCA E30 30 dectree Elbow 14DCA ES Elbow Strap 14DCA SS Supplementary Support 14DCA ST Stabilizer 14DCA FS Firestop 14DCA IS Insulation Shield 14DCA RRS Roof Radiation Shiel...

Reviews: