background image

Heatilator  •  ADI-ZC-FB  •  2032-900  Rev. E  •  8/05

20

Troubleshooting

With proper installation, operation, and maintenance your gas fireplace will
provide years of trouble-free service.  If you do experience a problem, this
troubleshooting guide will assist a qualified service person in the diagnosis
of a problem and the corrective action to be taken. This troubleshooting
guide can only be used by a qualified service technician.

Symptom

Possible Cause

Corrective Action

1.

 After repeated

triggering of the red

or black piezo button,

the spark ignitor will

not light the pilot.

a. Defective ignitor.

Check the spark at the electrode and pilot. If no spark and electrode wire is

properly connected, replace the ignitor.

b. Defective pilot or
misaligned electrode

(spark at electrode).

Using match, light the pilot. If the pilot lights, turn off the pilot and trigger the red or
black piezo button again. If the pilot lights, an improper gas/air mixture caused the
bad lighting and a longer purge period is recommended. If the pilot will not light,

ensure the the gap at the electrode and pilot is one-eighth (1/8) inch to have a
strong spark. If the gap is OK, replace the pilot.

c. No gas or low gas

pressure.

Check the remote shut-off valvess from the fireplace. Usually, there is a valve near

the gas main. There can be more than one (1) valve between the fireplace and the

main.

d. No LP in tank.

Check the LP (propane) tank. You may be out of fuel.

2.

  The pilot will not

stay lit after carefully

following the lighting

instructions.

a. Defective

thermocouple.

Check that the pilot flame impinges on the thermocouple. Clean and/or adjust the

pilot for maximum flame impingement.

Ensure that the thermocouple connection at the gas valve is fully inserted and tight

(hand tighten plus 1/4 turn).

Disconnect the thermocouple from the valve, place one millivolt meter lead wire on

the tip of the thermcouple and the other meter lead wire on the thermocouple

copper lead. Start the pilot and hold the valve knob in. If the millivolt reading is less

than 15mV, replace the thermocouple.

b. Defective valve.

If the thermocouple is producing more than 15 millivolts, replace faulty valve.

3.

 The pilot is

burning, there is no

gas burner, the valve

knob is in the ON
position, and the

ON/OFF switch is in

the ON position.

a. ON/OFF switch or
wires defective.

Check the ON/OFF switch and wires for proper connections. Place the jumper
wires across the terminals at the switch. If the burner comes on, replace the
defective switch. If the switch is OK, place the jumper wires across the switch wires
at the gas valve. If the burner comes on, the wires are faulty or connections are

bad.

b. Thermopile may
not be generating

sufficient millivoltage.

If the pilot flame is not close enough physically to the thermopile, adjust the pilot

flame.

Be sure the wire connections from the thermopile at the gas valve terminals are

tight and that the thermopile is fully inserted into the pilot bracket.

Check the thermopile with a millvolt meter. Take the reading at TH-TP&TP

terminals of the gas valve. The meter should read 325 millivolts minimum, while

holding the valve knob depressed in the pilot position, with the pilot lit, and the

ON/OFF switch in the OFF position. Replace the faulty thermopile if the reading is

below the specified minimum.

With the pilot in the ON position, disconnect the thermopile leads from the valve.
Take a reading at the thermopile leads. The reading should be 325 millivolts

minimum. Replace the thermopile if the reading is below the minimum.

c. Defective valve.

Turn the valve knob to the ON position. Place the ON/OFF switch in the ON

position. Check the millivolt meter a the thermopile terminals. The millivolt meter

should read greater than 125mV. If the reading is acceptable, and if the burner
does not come on, replace the gas valve.

d. Plugged burner
orifice.

Check the burner orifice for stoppage. Remove stoppage.

e. Wall switch or
wires are defective.

Follow the corrective action in Symptom and Possible Cause 1.a above. Check

the switch and wiring. Replace where defective.

5

Summary of Contents for ADI-ZC-FB

Page 1: ...H APPLIANCE FOR FUTURE REFERENCE 1 This appliance may be installed in an af termarket permanentlylocated manufac tured mobile home wherenotprohibited by local codes 2 This appliance is only for use wi...

Page 2: ...ce front READ and UNDERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warran...

Page 3: ...System 9 Step 2 Positioning Leveling and Securing the Insert 13 Step 3 The Gas Control Systems 13 Step 4 The Gas Supply Line 13 Step 5 Gas Pressure Requirements 14 Step 6 Wiring the Appliance 14 Wiri...

Page 4: ...ed in accordance with local codes or in the absence of local codes with the National Electric Code ANSI NFPA No 70 in the United States or to the CSAC22 1 Canadian Electric Code in Canada These models...

Page 5: ...EXTEN SION IF PRESENT MUST COMPLY WITH EI THER OF THE FOLLOWING 1 THE SOLID FUEL BURNING FIREPLACE MANUFACTURER S SPECIFICATION OR 2 LOCAL BUILDING CODES REQUIRED BY AUTHORITY HAVING JURISDICTION WAR...

Page 6: ...R EXHAUST STARTING COLLAR ON OFF SWITCH OPTIONAL 3 SIDED ADI ZC FB MINIMUM FIREPLACE SIZE LOCATION Inches Millimeters A Front Width 30 7 8 784 B Rear Width 25 5 8 651 C Depth 15 381 Height 19 1 2 495...

Page 7: ...the maximum vertical rise is 50 feet These dimensions are measured from the starting collars of the unit to the end of the last section of vent pipe See dimension V in Figure 3 Vent System Approvals...

Page 8: ...E THE ROOF TOP THESE MINIMUM HEIGHTS ARENECESSARYINTHEINTEREST OF SAFETY SEE THE FOLLOWING DIAGRAM FOR MINIMUM HEIGHTS PROVIDED THE TERMINATION CAP IS AT LEAST 2 FEET FROM A VER TICAL WALL AND 2 FEET...

Page 9: ...THE INLET AIR COLLAR OF THE UNIT AND EITHER ATTACHED TO THE INLETAIRCOLLAROFTHETERMINATIONCAP OR TERMINATED IN THE CHIMNEY This option shows both exhaust and inlet air vent pipes attached to the adapt...

Page 10: ...KING HANDLE SLIDING PLATE STAINLESS STEEL ADAPTER FOR EXHAUST MUST BE INSTALLED INLET AIR VENT PIPE 3 INCH COLLAR OPTIONAL LINK ZC ADPB For Flashing Class A Pipe TERMINATION CAP SQUARE FLASHING REMOVE...

Page 11: ...building codes to properly size the gas supply line leading to the 1 2 inch 13 mm hook up at the unit This gas fireplace is designed to accept a 1 2 inch 13 mm gas supply line To install the gas supp...

Page 12: ...ECT REMOTE CONTROLS IF AB SENT FOR EXTENDED TIME PERIODS THIS WILL PRE VENT ACCIDENTAL APPLIANCE OPERATION For Standing Pilot Ignition Wiring Appliance Requirements This appliance DOES NOT require 110...

Page 13: ...glass doors JUNCTION BOX VARIABLE SPEED CONTROL TEMPERATURE SENSOR SWITCH WHT GRN BLK BLK 110 120 VAC BLOWER BLOWER RECEPTACLE BLK BLK BLK BLK WHT GROUND WHT BLK BLK BLK REMOTE RECEPTACLE SPEED CONTRO...

Page 14: ...oles in burner top see Figure 12 Space dime size ember pieces about a 1 2 inch apart Never press embers into burner ports DO NOT cover burner ports Place dime size pieces around front and sides of bur...

Page 15: ...ew minutes for the lines to purge themselves of this air Once the purging is complete the appliance will light and will operate normally Subsequent lightings of the fireplace will not require this pur...

Page 16: ...ILOT position turn the control knob counter clockwise to the PILOT position 6 To light the pilot press the control knob and then press the red or black piezo button once every second The piezo makes a...

Page 17: ...vacuum the control compartment fireplace logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a...

Page 18: ...copper lead Start the pilot and hold the valve knob in If the millivolt reading is less than 15mV replace the thermocouple b Defective valve If the thermocouple is producing more than 15 millivolts re...

Page 19: ...necessary e Improper vent cap installation Check for proper installation and freedom from debris or blockage 6 Glass soots a Flame impingement Adjust the log set so that the flame does not excessivel...

Page 20: ...itions inadequate ventilation or drafting caused by tight sealing construction of the structure air handling devices such as exhaust fans or forced air furnaces or other causes 5 use of fuels other th...

Reviews: