26
VENTING
EXHAUST
INTAKE
LEFT SIDE VIEW
EXTERIOR WALL
SUPPORT BRACKETS
MUST BE USED ON
ALL HORIZONTAL
AND VERTICAL PIPING
MIN.
1"
MIN.
12"
SIDEWALL VENTING WITH TEE (INTAKE) AND
COUPLING (EXHAUST)
INTAKE
INTAKE LEG MUST BE FACING UP
AND VERTICAL PIPING
ALL HORIZONTAL
EXHAUST
IMPORTANT:
CONCENTRIC VENT KIT
EXTERIOR WALL
LEFT SIDE VIEW
SIDEWALL VENTING WITH
MUST BE USED ON
SUPPORT BRACKETS
MIN.
1"
CONCENTRIC VENT KIT
PART# KGAVT0501CVT - 2"
KGAVT0601CVT - 3"
EXHAUST
LEFT SIDE VIEW
EXTERIOR WALL
SUPPORT BRACKETS
MUST BE USED ON
ALL HORIZONTAL
AND VERTICAL PIPING
VENT KIT
PART# V500 - 2"
V1000 - 3"
V2000 - 4"
10'-0" MIN.
WHICHEVER IS GREATER
12" OVER MAXIMUM
SNOW LEVEL OR 24"
AND COUPLING (EXHAUST)
INTAKE
ROOF VENT WITH TEE (INTAKE)
EXHAUST
SUPPORT BRACKETS
MUST BE USED ON
ALL HORIZONTAL
AND VERTICAL PIPING
LEFT SIDE VIEW
24" MIN.
10'-0" MIN.
GREATER
12" OVER MAXIMUM
SNOW LEVEL OR 24"
WHICHEVER IS
NOTE: EXTENDED VENT RUNS WHEN
TRANSITIONING TO A LARGER DIAMETER
MUST ALWAYS TAKE PLACE IN A VERTICAL
POSITION TO PREVENT CONDENSATE
BLOCKAGE.
ROOF VENT WITH
LEFT SIDE VIEW
AND VERTICAL PIPING
MUST BE USED ON
ALL HORIZONTAL
CONCENTRIC VENT KIT
SUPPORT BRACKETS
CONCENTRIC VENT KIT
PART# KGAVT0501CVT - 2"
KGAVT0601CVT - 3"
NOTE: When placing support brackets on vent
piping, the first bracket must be within 1 foot
of the appliance and the balance at 4 foot
invervals on the vent pipe.
I. DIAGRAMS FOR VENTING
SIDEWALL VENTING WITH KIT
Summary of Contents for Phoenix
Page 1: ... Installation Operation Maintenance 2007 Heat Transfer Products Inc ...
Page 31: ...30 WIRING F INTERNAL WIRING PART 6 START UP PROCEDURE CONTINUED Phoenix Connector Diagram ...
Page 41: ...40 MAINTENANCE NOTES ...
Page 42: ...41 MAINTENANCE NOTES ...
Page 43: ...42 MAINTENANCE NOTES ...
Page 44: ... 2008 2007 Heat Transfer Products Inc www htproducts com LP 179 REV 4 5 08 ...
Page 68: ...23 ...
Page 69: ...24 ...
Page 73: ...28 MAINTENANCE NOTES ...
Page 74: ...29 MAINTENANCE NOTES ...
Page 75: ...30 MAINTENANCE NOTES ...