25

Pressure

Natural Gas

Propane

Minimum

5.0 inches

11.0 inches

Inlet Pressure

w.c.

w.c.

Maximum Inlet

14.0 inches

14.0 inches

Gas Pressure

w.c.

w.c.

Manifold

3.5 inches

10.0 inches

Pressure

w.c.

w.c.

A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is
provided on the inlet and outlet side of the gas control for a
test gauge connection to measure the manifold pressure.

The fireplace and its individual shut-off valve

MUST

 be

disconnected from the gas supply piping system during
any pressure testing of the system at test pressures in
excess of one-half (1/2) psig (3.5 kPa). The fireplace

MUST

be isolated from the gas supply piping system by closing
its individual shut-off valve during any pressure testing of
the gas supply piping system at test pressures equal to or
less than one-half (1/2) psig (3.5 kPa).

Installing the Fireplace

(continued)

At the gas line access hole, use insulation to re-pack
the space around the gas pipe.

Insert insulation from the outside of the fireplace and
pack the insulation tightly to totally seal between the
pipe and the outer casing.

Figure 11. Gas Supply Line

Step 8
Gas Pressure Requirements

Pression

Gaz naturel

Propane

Pression minimale

127 mm

279 mm

d’approvisionnement

CE

CE

Pression maximale

356 mm

356 mm

d’approvisionnement

CE

CE

Pression du

89 mm

254 mm

collecteur

CE

CE

Une dérivation de visite NPT de 3 mm est prévue sur le
côté d’admission et sur le côté de sortie de la commande
de gaz, afin d’y brancher un manomètre pour mesurer la
pression du collecteur.

Le foyer et son robinet individuel 

DOIVENT

être isolés de

la tuyauterie d’alimentation en gaz pendant les contrôles
de pression du système à des pressions d’essai supérieures
à 3,5 kPa. Le foyer

DOIT

 être isolé de la tuyauterie

d’alimentation en gaz en fermant son robinet individuel
pendant les contrôles de pression de la tuyauterie
d’alimentation en gaz à des pressions d’essai inférieures
ou égales à 3,5 kPa.

Figure 11. Conduit à gaz

Étape 8
Spécifications de la pression du gaz

Installation du foyer

(suite)

Au niveau de l’orifice d’accès du conduit à gaz, utilisez
de l’isolant afin de regarnir l’espace autour du conduit à
gaz.

Insérez l’isolant par l’extérieur du foyer et tassez-le bien
afin de boucher hermétiquement l’espace entre le tuyau
et la paroi extérieure.

USE A WRENCH ON 

SHUT-OFF VALVE WHEN 

TIGHTENING GAS LINE. /

ROBINET MANUEL

GAS VALVE /

FLEX CONNECTOR /

MANUAL SHUT-OFF VALVE /

TUYAU FLEXIBLE

VALVE DE COMMANDE

 DE GAZ

UTILISEZ UNE CLÉ SUR 

LE ROBINET DE GAZ LORS 

DU SERRAGE DU 

CONDUIT À GAZ.

GLASS ASSEMBLY /

  GAS CONTROLS /
  COMMANDES DE GAZ

TOP STANDOFFS /

ACCÈS DU
CONDUIT
À GAZ

GAS LINE
ACCESS /

PORTE EN VERRE

ENTRETOISES
SUPÉRIEURES

COLLETS DE 

RACCORD

VENT COLLARS /

Summary of Contents for SL-550TV-C

Page 1: ...ezlapi ce leb timentoulazone Appelez imm diatement votre fournisseur de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service...

Page 2: ...mencer l installation Si ces instructions d installation ne sont pas suivies un risque d incendie pourrait en r sulter et la garantie sera annul e Avant l allumage initial LISEZ la section du Guide de...

Page 3: ...des syst mes d vacuation d crits dans la section intitul e Installation du foyer dans le Guide d installation AUCUN AUTRE syst me ou l ment d vacuation NE PEUT TRE UTILIS Cet appareil gaz et ce syst m...

Page 4: ...es de s curit et mises en garde 2 Liste des pi ces de rechange 5 Section 1 Homologations et codes 11 Homologations et codes 11 Homologation de l appareil 11 Codes d installation 11 Installation haute...

Page 5: ...d les de foyer Heat N Glo dont il est question dans ce Guide d installation ont t test s conform ment aux normes d homologation et ont t approuv s par les laboratoires comp tents NORME D HOMOLOGATION...

Page 6: ...fice qui convient consultez le service local de distribution de gaz Si cet appareil est install une altitude sup rieure 1 370 m tres au Canada consultez les autorit s locales Homologations et codes su...

Page 7: ...tation des foyers gaz Heat N Glo Les foyers gaz syst me d vacuation de type B Heat N Glo sont con us pour expulser tous les gaz de combustion en dehors de l difice Les informations contenues dans ce G...

Page 8: ...lectrique Les d tails d encadrement et de finition Si vous d sirez installer des accessoires facultatifs dispositifs tels qu un ventilateur un interrupteur mural ou une commande distance Si le foyer d...

Page 9: ...4 402 30 3 4 780 15 3 8 390 8 1 8 206 2 1 4 55 37 3 4 960 34 1 2 878 20 1 2 526 3 1 2 90 5 127 B VENT B VENT HOOD GAS CONTROLS GAS LINE ACCESS VENT COLLARS TOP STANDOFFS ACC S DU FILAGE LECTRIQUE RATI...

Page 10: ...DE AIR ENTRETOISES SUP RIEURES COLLETS DE RACCORD DU SYST ME D VACUATION HOTTE AIR EXT RIEUR ELECTRICAL ACCESS CACHE DE LA GRILLE INF RIEURE PLAQUES SIGNAL TIQUES ET TIQUETTES COMMANDES DE GAZ ACC S D...

Page 11: ...e Sides 1 2 13 C t s Top SL 550TV C 1 1 2 38 Dessus SL 550TV C SL 750TV C 3 1 4 83 SL 750TV C SL 950TV C 3 1 4 83 SL 950TV C Ceiling 31 787 Plafond Inches mm Figure 4 Dimensionsetsp cifications de d g...

Page 12: ...carbon monoxide situation in the house tape 3 Air de compensation en cas de pression n gative dans la pi ce Avertissement en cas de pression n gative dans la pi ce En cas de pression n gative un foyer...

Page 13: ...tative Cet appareil est con u de fa on pouvoir accepter une prise d air ext rieur Gr ce l air de com pensation ext rieur la quantit d air de la pi ce utilis e pour la combustion est r duite Il est con...

Page 14: ...v s pour raccordement un conduit d vacuation de type B de 127 mm de diam tre Le mod le SL 950TV C est approuv pour raccordement un conduit d vacuation de type B de 152 mm de diam tre Un conduit d vacu...

Page 15: ...d vacuation L apparence des flammes et des braises peut varier selon le type de combustible br l et la configuration du syt me d vacuation B l ments du syst me Configuration du syst me d vacuation PRO...

Page 16: ...DE S CURIT LA FIGURE 8 ET LE TABLEAU INDIQUENT LES HAUTEURS MINIMALES RESPECTER LORSQUE LA TERMINAISON DU SYST ME D VACUATION EST LOIGN E D AU MOINS 244 CM D UN MUR VERTICAL Installing the Fireplace c...

Page 17: ...Level the fireplace from side to side and from front to back 3 Shim the fireplace with non combustible material such as sheet metal as necessary 4 Secure the fireplace to the framing by nailing or scr...

Page 18: ...mande de gaz tape 7 Conduit gaz REMARQUE Le conduit d alimentation en gaz doit tre install conform ment aux codes de construc tion locaux par un installateur qualifi approuv et ou agr selon les sp cif...

Page 19: ...ale 356 mm 356 mm d approvisionnement CE CE Pression du 89 mm 254 mm collecteur CE CE Une d rivation de visite NPT de 3 mm est pr vue sur le c t d admission et sur le c t de sortie de la commande de g...

Page 20: ...riodes prolong es De cette fa on le foyer ne pourra pas s allumer accidentellement Filage de l allumage par veilleuse Sp cifications de l appareil Le fonctionnement de cet appareil NE n cessite PAS d...

Page 21: ...TISSEMENT NE BRANCHEZ PAS DE COURANT DE 110 120 VCA L INTERRUP TEUR MURAL DE COMMANDE CELA D TRUIRAIT LAVALVE DE COMMANDE ATTENTION TIQUETEZ TOUS LES FILS AVANT DE LES D BRANCHER POUR LE SERVICE DES C...

Page 22: ...IPI Wiring Diagram RED ROUGE BLK NOIR IGNITION MODULE 3 VAC MODULE D ALLUMAGE 3V BROWN BRUN GREEN VERT ORG VALVE OPTIONAL REMOTE A DISTANCE EN OPTION REM REM FAN VENT ORG WHITE BLANC I S INTERMITTENT...

Page 23: ...on Le sch ma suivant indique le d gagement vertical minimal et les dimensions horizontales maximales correspondantes des habillages de foyer et autres saillies combustibles au dessus du bord sup rieur...

Page 24: ...SCELLAGE POUVANT R SISTER 149 C MINIMUM DOIT TRE UTILIS IL N EST PAS N CESSAIRE DE SCELLER CES JOINTS SEULS DES MAT RIAUX NON COMBUSTIBLES UTILISANT UN ADH SIF POUVANT R SISTER 149 C MINIMUM SIN CESS...

Page 25: ...installation instructions that accompany the logs or the instructions in manual bag assembly Save the log instructions with this manual If sooting occurs the logs might need to be repositioned slightl...

Page 26: ...n place des braises EMBER MATERIALS BRAISES Place dime size pieces of ember material about 1 2 inch apart near port holes in burner top Do NOT press em bers into burner ports Cover the top of the burn...

Page 27: ...ue le support soutenant la grille a t enlev reportez vous la page 31 Assurez vous que la grille repose directement sur le r fractaire V rifiez qu il n y ait pas d l ments d fectueux Tout l ment d fect...

Page 28: ...yer Bien que la fr quence de l entretien et des services de votre foyer d pende de son utilisation et du type d installation il est conseill de demander un technicien de service qualifi d inspecter l...

Page 29: ...e produit est prot g par un our plusieurs des brevets suivants tats Unis 4 112 913 4 408 594 4 422 426 4 424 792 4 520 791 4 793 322 4 852 548 4 875 464 5 000 162 5 016 609 5 076 254 5 191 877 5 218 9...

Reviews: