Heat-N-Glo CFX-ZC Installer'S Manual Download Page 14

14

Step 5.   Gas Pressure Requirements

Pressure requirements for these gas appliances are shown
in the table below.

Pressure

Natural Gas

Propane

Minimum

5.0 inches

11.0 inches

Inlet Pressure

w.c.

w.c.

Maximum Inlet

14.0 inches

14.0 inches

Gas Pressure

w.c.

w.c.

Manifold

3.5 inches

10.0 inches

Pressure

w.c.

w.c.

A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is
provided on the inlet and outlet side of the gas control for a
test gauge connection to measure the manifold pressure.
Use a small flat blade screwdriver to crack open the screw
in the center of the tap.  Position a rubber hose over the tap
to obtain the pressure reading.

The fireplace and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing of the system at test pressures in
excess of one-half (1/2) psig (3.5 kPa).

The fireplace must be isolated from the gas supply piping
system by closing its individual shut-off valve during any
pressure testing of the gas supply piping system at test
pressures equal to or less than one-half (1/2) psig (3.5 kPa).

Step 6.  Wiring the Fireplace

NOTE: Electrical wiring must be installed by a licensed
electrician.

CAUTION: DISCONNECT REMOTE CONTROLS IF AB-
SENT FOR EXTENDED TIME PERIODS TO PREVENT
ACCIDENTAL APPLIANCE OPERATION.

For Standing Pilot Ignition Wiring
Appliance Requirements

• 

This appliance 

DOES NOT 

require 110-120 VAC to operate.

WARNING:  DO NOT CONNECT 110-120 VAC
TO THE GAS CONTROL VALVE OR THE AP-
PLIANCE WILL MALFUNCTION AND THE
VALVE WILL BE DESTROYED

.

Wall Switch

Position the wall switch in the desired position on a wall.
Run a maximum of 25 feet (7.8 m) or less length of 18
A.W.G. minimum wire and connect it to the fireplace valve
pigtails.

WARNING: DO NOT CONNECT 110-120 VAC
TO THE WALL SWITCH OR THE CONTROL
VALVE WILL BE DESTROYED.

CAUTION: LABEL ALL WIRES PRIOR TO DISCONNEC-
TION WHEN SERVICING CONTROLS. WIRING ERRORS
CAN CAUSE IMPROPER AND DANGEROUS OPERATION.
VERIFY PROPER OPERATION  AFTER SERVICING.

!

!

Figure 8.

Standing Pilot Ignition Wiring Diagram

THERMOCOUPLE

GAS

VALVE

OPTIONAL WALL SWITCH

THERMOSTAT OR REMOTE

ON

OFF

ROCKER

SWITCH

THERMOPILE

WHITE T2

RED T1

Summary of Contents for CFX-ZC

Page 1: ...EFERENCE Please contact your Heat N Glo dealer for any questions or concerns For the number of your nearest Heat N Glo dealer please call 1 888 427 3973 Printed in U S A Copyright 2003 Heat N Glo a di...

Page 2: ...DERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the firs...

Page 3: ...16 After the Installation 16 Section 4 Maintaining and Servicing Your Appliance 17 u u Contains updated information TABLE OF CONTENTS Safety and Warning Information 2 Service Parts List 4 Section 1 A...

Page 4: ...ros de pi ce se trouve la page suivante 6 1 10 2 10 4 8 3 7 9 5 Log Set Assembly 11 12 13 14 15 17 17 16 NG LP Exploded Parts Diagram GN PL Vue clat e des pi ces Service Parts CFX ZC Beginning Manufa...

Page 5: ...leuse GN 571 517 Pilot Orifice LP Orifice de veilleuse PL 571 516 Thermopile Thermopile 060 512 Thermocouple Thermocouple 571 511 ON OFF Rocker Switch Interrupteur bascule marche arr t 060 525A Pilot...

Page 6: ...ce of local codes with the National Electric Code ANSI NFPA No 70 in the United States or to the CSA C22 1 Canadian Electric Code in Canada These models may be installed in a bedroom or bed sitting ro...

Page 7: ...for recessed in stallations into solid fuel Masonry or Factory Built Non Combustible fireplaces that have been installed in ac cordance with the National Provincial State and local building codes 2 Mi...

Page 8: ...6 1 4 413mm NOTE If exhaust collar on insert and fireplace damper do not line up add 4 inches 102mm to minimum fireplace height for bends in vent pipe 11 279mm 5 1 2 139mm 16 1 8 410mm 16 406mm 4 5 8...

Page 9: ...t to the end of the last section of vent pipe See dimension V in Figure 3 Vent System Approvals A vertical vent termination system installed on this model will include one 1 length of 3 inch flexible...

Page 10: ...tion cap and to the top of the flexible vent pipe and set the cap in place at the top of the chimney See Figures 3 4 and 5 CAUTION TO AVOID DOWNDRAFTS AND OR COLD AIR PROBLEMS IT IS RECOMMENDED TO SEA...

Page 11: ...ECTED TO THE INLET AIR COLLAR OF THE UNIT AND EITHER ATTACHED TO THE INLETAIRCOLLAROFTHETERMINATIONCAP OR TERMINATED IN THE CHIMNEY This option shows both exhaust and inlet air vent pipes attached to...

Page 12: ...XHAUST COLLAR GASKET TO INSURE POSITIVE EXHAUST SEAL SIDE VIEW TERMINATION CAP EXHAUST COLLAR ADAPTOR INLET AIR COLLAR STAINLESS STEEL FLEXIBLE PIPE PROVIDED 3 INCH COLLAR EXHAUST STARTING COLLAR WITH...

Page 13: ...ation must be performed by a licensed plumber or gas fitter NOTE Before the first firing of the fireplace the gas supply line should be purged of any trapped air NOTE Consult local building codes to p...

Page 14: ...ing of the gas supply piping system at test pressures equal to or less than one half 1 2 psig 3 5 kPa Step 6 Wiring the Fireplace NOTE Electrical wiring must be installed by a licensed electrician CAU...

Page 15: ...tch Place a dime size piece of glowing ember material near port holes in burner top sides and front see Figure 10 Figure 10 Placement of the Ember Material Space ember pieces about a 1 2 inch apart Ne...

Page 16: ...rs on the initial start up Turn it off and let it cool completely Remove and clean the glass Replace the glass and run the fireplace for an additional 8 hours This will help to cure the chemicals used...

Page 17: ...ompartment fireplace logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a visual check of your...

Reviews: