Roof Pitch

       H (min.) ft.

flat to 6/12

1.0

6/12 to 7/12

1.25

over 7/12 to 8/12

1.5

over 8/12 to 9/12

2.0

over 9/12 to 10/12

2.5

over 10/12 to 11/12

3.25

over 11/12 to 12/12

4.0

over 12/12 to 14/12

5.0

over 14/12 to 16/12

6.0

over 16/12 to 18/12

7.0

over 18/12 to 20/12

7.5

over 20/12 to 21/12

8.0

Figure 2.   Minimum Height from Roof to Lowest
                 Discharge Opening

HORIZONTAL OVERHANG

VERTICAL WALL

TERMINATION CAP

12

X

ROOF PITCH IS  X/ 12

LOWEST 
DISCHARGE 
OPENING

H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING

2 FT.

MIN.

2 FT. MIN.

WARNING: DO NOT FORCE
COLLAR ATTACHMENT INTO

PLACE. THE FIREPLACE IS MADE
OF A FRAGILE MATERIAL, AND
MAY BREAK. READJUST FLEXI-
BLE VENT PIPES IF NECESSARY.

Attach the pipe-to-cap adaptor to the
termination cap and to the top of the
flexible vent pipe and set the cap in place
at the top of the chimney. See Figures 3,
4 and 5.

CAUTION: TO AVOID DOWNDRAFTS
AND/OR COLD AIR PROBLEMS, IT IS
RECOMMENDED TO SEAL OFF THE
AREA BETWEEN THE TERMINATION
CAP AND THE TOP OF THE SOLID-
FUEL CHIMNEY OPENING INTO
WHICH THE VENT CAP HAS BEEN IN-
STALLED.

WHEN USING THE LINK-DV4-3O VENT
SYSTEM, IT IS REQUIRED TO SEAL
AROUND THE FLEXIBLE VENT PIPES
IN THE DAMPER AREA. SEE FIGURE
3. USE FIBERGLASS INSULATION OR
OTHER SUITABLE NON-COMBUSTI-
BLE MATERIAL.

WARNING: MAJOR U.S.
BUILDING CODES SPECIFY

MINIMUM CHIMNEY AND/OR VENT
HEIGHT ABOVE THE ROOF TOP.
THESE MINIMUM HEIGHTS ARE
NECESSARY IN THE INTEREST OF
SAFETY. SEE THE FOLLOWING
DIAGRAM FOR MINIMUM HEIGHTS,
PROVIDED THE TERMINATION CAP
IS AT LEAST 2-FEET FROM A VER-
TICAL WALL AND 2-FEET BELOW
A HORIZONTAL OVERHANG.

NOTE:

 This also pertains to vertical vent

systems installed on the outside of the
building.

Summary of Contents for CFX-ZC

Page 1: ...EFERENCE Please contact your Heat N Glo dealer for any questions or concerns For the number of your nearest Heat N Glo dealer please call 1 888 427 3973 Printed in U S A Copyright 2003 Heat N Glo a di...

Page 2: ...DERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the firs...

Page 3: ...16 After the Installation 16 Section 4 Maintaining and Servicing Your Appliance 17 u u Contains updated information TABLE OF CONTENTS Safety and Warning Information 2 Service Parts List 4 Section 1 A...

Page 4: ...ros de pi ce se trouve la page suivante 6 1 10 2 10 4 8 3 7 9 5 Log Set Assembly 11 12 13 14 15 17 17 16 NG LP Exploded Parts Diagram GN PL Vue clat e des pi ces Service Parts CFX ZC Beginning Manufa...

Page 5: ...leuse GN 571 517 Pilot Orifice LP Orifice de veilleuse PL 571 516 Thermopile Thermopile 060 512 Thermocouple Thermocouple 571 511 ON OFF Rocker Switch Interrupteur bascule marche arr t 060 525A Pilot...

Page 6: ...ce of local codes with the National Electric Code ANSI NFPA No 70 in the United States or to the CSA C22 1 Canadian Electric Code in Canada These models may be installed in a bedroom or bed sitting ro...

Page 7: ...for recessed in stallations into solid fuel Masonry or Factory Built Non Combustible fireplaces that have been installed in ac cordance with the National Provincial State and local building codes 2 Mi...

Page 8: ...6 1 4 413mm NOTE If exhaust collar on insert and fireplace damper do not line up add 4 inches 102mm to minimum fireplace height for bends in vent pipe 11 279mm 5 1 2 139mm 16 1 8 410mm 16 406mm 4 5 8...

Page 9: ...t to the end of the last section of vent pipe See dimension V in Figure 3 Vent System Approvals A vertical vent termination system installed on this model will include one 1 length of 3 inch flexible...

Page 10: ...tion cap and to the top of the flexible vent pipe and set the cap in place at the top of the chimney See Figures 3 4 and 5 CAUTION TO AVOID DOWNDRAFTS AND OR COLD AIR PROBLEMS IT IS RECOMMENDED TO SEA...

Page 11: ...ECTED TO THE INLET AIR COLLAR OF THE UNIT AND EITHER ATTACHED TO THE INLETAIRCOLLAROFTHETERMINATIONCAP OR TERMINATED IN THE CHIMNEY This option shows both exhaust and inlet air vent pipes attached to...

Page 12: ...XHAUST COLLAR GASKET TO INSURE POSITIVE EXHAUST SEAL SIDE VIEW TERMINATION CAP EXHAUST COLLAR ADAPTOR INLET AIR COLLAR STAINLESS STEEL FLEXIBLE PIPE PROVIDED 3 INCH COLLAR EXHAUST STARTING COLLAR WITH...

Page 13: ...ation must be performed by a licensed plumber or gas fitter NOTE Before the first firing of the fireplace the gas supply line should be purged of any trapped air NOTE Consult local building codes to p...

Page 14: ...ing of the gas supply piping system at test pressures equal to or less than one half 1 2 psig 3 5 kPa Step 6 Wiring the Fireplace NOTE Electrical wiring must be installed by a licensed electrician CAU...

Page 15: ...tch Place a dime size piece of glowing ember material near port holes in burner top sides and front see Figure 10 Figure 10 Placement of the Ember Material Space ember pieces about a 1 2 inch apart Ne...

Page 16: ...rs on the initial start up Turn it off and let it cool completely Remove and clean the glass Replace the glass and run the fireplace for an additional 8 hours This will help to cure the chemicals used...

Page 17: ...ompartment fireplace logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a visual check of your...

Reviews: