Step 2.  Positioning, Leveling, and
               Securing the Insert

• Place the insert into position.

• Level the insert from side to side and from front to back.

Use the leveling legs included with the manual
bag if necessary. Screw the legs into the nuts installed
in the bottom rear of the insert.  Turn legs in until insert
is level.

!

!

Step 3. The Gas Control System

WARNING: THIS UNIT IS NOT FOR USE WITH
SOLID FUEL.

This model uses a standing pilot ignition type of gas control
system.

Standing Pilot Ignition System

This system includes millivolt control valve, standing pilot,
thermopile/thermocouple flame sensor, and piezo ignitor.

WARNING: 110-120 VAC MUST NEVER BE
CONNECTED TO A CONTROL  VALVE IN A
MILLIVOLT SYSTEM.

STANDING PILOT

Figure 6.  Gas Controls System

Step 4.  The Gas Supply Line

NOTE: Have the gas supply line installed in accordance
with  local  building codes by a qualified installer
approved and/or licensed as required by the locality.
(In the state of Massachusetts installation must be
performed by a licensed plumber or gas fitter).

NOTE: Before the first firing of the fireplace, the gas
supply line should be purged of any trapped air.

NOTE: Consult local building codes to properly size
the gas supply line leading to the 1/2 inch (13 mm)
hook-up at the unit.

This gas fireplace is designed to accept a 1/2 inch
(13 mm) gas supply line. To install the gas supply line:

• A listed (and State of Massachusetts approved) 1/2 inch

(13mm) tee-handle manual shut-off valve and a listed
flexible gas connector are connected to the 1/2 inch
(13mm) inlet of the control valve. 

NOTE:

 If substituting

for these components, please consult local codes for
compliance.

• Locate the gas line access hole in the outer casing of

the fireplace.

• Open the lower grille, insert the gas supply line through

the gas line hole, and connect it to the shut-off valve.

• When attaching the pipe, support the control so that the

lines are not bent or torn.

• After the gas line installation is complete, use a soap

solution to carefully check all gas connections for leaks.

WARNING: DO NOT USE AN OPEN FLAME
TO CHECK FOR GAS LEAKS

.

!

Figure 7.   Gas Supply Line

GAS VALVE

MANUAL SHUT OFF

FLEX CONNECTOR

Summary of Contents for CFX-ZC

Page 1: ...EFERENCE Please contact your Heat N Glo dealer for any questions or concerns For the number of your nearest Heat N Glo dealer please call 1 888 427 3973 Printed in U S A Copyright 2003 Heat N Glo a di...

Page 2: ...DERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the firs...

Page 3: ...16 After the Installation 16 Section 4 Maintaining and Servicing Your Appliance 17 u u Contains updated information TABLE OF CONTENTS Safety and Warning Information 2 Service Parts List 4 Section 1 A...

Page 4: ...ros de pi ce se trouve la page suivante 6 1 10 2 10 4 8 3 7 9 5 Log Set Assembly 11 12 13 14 15 17 17 16 NG LP Exploded Parts Diagram GN PL Vue clat e des pi ces Service Parts CFX ZC Beginning Manufa...

Page 5: ...leuse GN 571 517 Pilot Orifice LP Orifice de veilleuse PL 571 516 Thermopile Thermopile 060 512 Thermocouple Thermocouple 571 511 ON OFF Rocker Switch Interrupteur bascule marche arr t 060 525A Pilot...

Page 6: ...ce of local codes with the National Electric Code ANSI NFPA No 70 in the United States or to the CSA C22 1 Canadian Electric Code in Canada These models may be installed in a bedroom or bed sitting ro...

Page 7: ...for recessed in stallations into solid fuel Masonry or Factory Built Non Combustible fireplaces that have been installed in ac cordance with the National Provincial State and local building codes 2 Mi...

Page 8: ...6 1 4 413mm NOTE If exhaust collar on insert and fireplace damper do not line up add 4 inches 102mm to minimum fireplace height for bends in vent pipe 11 279mm 5 1 2 139mm 16 1 8 410mm 16 406mm 4 5 8...

Page 9: ...t to the end of the last section of vent pipe See dimension V in Figure 3 Vent System Approvals A vertical vent termination system installed on this model will include one 1 length of 3 inch flexible...

Page 10: ...tion cap and to the top of the flexible vent pipe and set the cap in place at the top of the chimney See Figures 3 4 and 5 CAUTION TO AVOID DOWNDRAFTS AND OR COLD AIR PROBLEMS IT IS RECOMMENDED TO SEA...

Page 11: ...ECTED TO THE INLET AIR COLLAR OF THE UNIT AND EITHER ATTACHED TO THE INLETAIRCOLLAROFTHETERMINATIONCAP OR TERMINATED IN THE CHIMNEY This option shows both exhaust and inlet air vent pipes attached to...

Page 12: ...XHAUST COLLAR GASKET TO INSURE POSITIVE EXHAUST SEAL SIDE VIEW TERMINATION CAP EXHAUST COLLAR ADAPTOR INLET AIR COLLAR STAINLESS STEEL FLEXIBLE PIPE PROVIDED 3 INCH COLLAR EXHAUST STARTING COLLAR WITH...

Page 13: ...ation must be performed by a licensed plumber or gas fitter NOTE Before the first firing of the fireplace the gas supply line should be purged of any trapped air NOTE Consult local building codes to p...

Page 14: ...ing of the gas supply piping system at test pressures equal to or less than one half 1 2 psig 3 5 kPa Step 6 Wiring the Fireplace NOTE Electrical wiring must be installed by a licensed electrician CAU...

Page 15: ...tch Place a dime size piece of glowing ember material near port holes in burner top sides and front see Figure 10 Figure 10 Placement of the Ember Material Space ember pieces about a 1 2 inch apart Ne...

Page 16: ...rs on the initial start up Turn it off and let it cool completely Remove and clean the glass Replace the glass and run the fireplace for an additional 8 hours This will help to cure the chemicals used...

Page 17: ...ompartment fireplace logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a visual check of your...

Reviews: