background image

HeatLink

®

 Mixing Valve Reset Control Stk# 31360

H

e

a

tL

in

k

®

Link

Heat

27

www.heatlinkgroup.com

ELECT 5.2

Indoor/Outdoor controller c/w Optional Standard Thermostats

Application:

  StatLink

® 

controls  activating    individual  manifold  module  zone  motors  and  automatic  mixing 

valve reset controller which in turn activates boiler plus primary (P-2) and system (P-1) pumps. 

 

DHW  tank  aquastat  opens  DHW  valve  and  activates  boiler  plus  primary  (P-2)  and  system  (P-3) 
pumps.

Note:

•  Drawings are for HeatLink

®

 suggested

 electrical schematics only!  User must determine if electrical schematic will work for their particular application.  

User must also confirm all HeatLink

®

 schematics with manufacturer schematics of each particular control chosen.

•  In all cases manufacturer equipment schematics will take precedence over HeatLink

®

 electrical schematics.

•  All wiring as per applicable electrical codes!

4

4

4

6

2

2

2

Indoor/Outdoor

Controller

31360

Boiler

Primary Pump

 P-2

IF Aquastat

IFHWH

Relay

R-1

P-3

Outdoor

Sensor

Optional Boiler

Return Sensor

System Pump P-1

Class II

Transformer

Supply Sensor

Relay

SLR-2

46151

Zone Thermostats

Class II

Transformer

Class II

Transformer

SL1

SL2

4

46643

Timer

6 5 4

3

7 8 1 2

6 5 4

3

7 8 1 2

31360

 Mixing Valve Reset Control

Do not apply

power here

12 13 14 15 16 17

11

10

9

8

7

6

5

4

3

2

1

Uno

Sw

Boil

Out

Com

Mix

Com

C

Cls

Mix

Opn

Mix

Boiler

N

Sys

Pump

Pwr

N

Pwr

L

Mixing

Demand

10 A

10 A

P-1

P-3

Boiler

Contacts

Mix Supply

Sensor

Boiler

Sensor

Optional

Unoccupied

Switch

Outdoor

Sensor

R-1

DHW

Aquastat

(SPST)

24V

24 Vac Class II

Transformer

R1 & R2 = 

45012

 (24 Vac / 2pole)

Max. Pump 1/4 HP @ 110Vac

Max. Pump 1/3 HP @ 220Vac

110 V

or

220 V

N

blu

e

brow

n

black

R

C

N

L

P-2

Power

Supply

StatLink 

40226

SL2

C R

Power

Supply

StatLink 

40226

SL1

C

R

To 24 Vac Class II

Transformer

C

R

To 24 Vac Class II

Transformer

R-2

11

10

9

Opn

Pwr

Mix

N

Note: European version (31360e)

requires power to the mixing valve

motor and has an 18th terminal for

an optional indoor sensor.

Cls

blue

brow

n

black

R

C

18

Indr

Summary of Contents for 31360

Page 1: ...n R Cls 11 C Powered Output 7 8 L N Sys Pmp N 1 Mixing Demand 2 3 4 5 6 Power 12 13 14 15 16 17 Do not apply power UnO Sw Com Boil Mix Com Out Item Motor Speed Open Close Mixing Demand Input Timer Opt...

Page 2: ...4 StatLink Controls Activating Circuits plus SnowMelt Controller Pg 34 35 TECH 5 5 4 Circuit Mod Fl Ht plus Fan Coil IFHWH Secondary Ht Exchanger Pg 36 ELECT 5 5 StatLink Activating Low Temp plus Inde...

Page 3: ...then show the word ADJUST in the top right corner Then select the desired item using the Item button Finally use the Up and or Down button to make the adjustment To exit the ADJUST menu either select...

Page 4: ...unt of heat lost by a building changes depending on the outdoor air temperature The amount of heat supplied by the heating system must be equal to the amount of heat being lost in the building If the...

Page 5: ...owever the control does not operate the heating system to satisfy this demand If the control is in setpoint mode the WWSD feature is not functional 12 13 Timer Switch UnO Sw Com Floating Action A 24V...

Page 6: ...oints to establish the rate at which the mix supply water temperature is to be increased for every degree that the outdoor air temperature falls The starting point of the reset ratio is fixed at 70 F...

Page 7: ...he MIN segment will be displayed in the LCD when either the MIX TARGET or MIX temperature is being viewed Mix Target Temperature MIX TARGET When used as a mixing reset control the MIX TARGET temperatu...

Page 8: ...whenever there is a mixing demand and the Stk 31360 is not in WWSD The system pump segment is displayed in the LCD After the mixing demand has been satisfied the Stk 31360 continues to operate the sys...

Page 9: ...tant velocity by the fan or either a fan or blower Air is forced across the coil at a constant velocity by the fan or blower and is then delivered into the building space Default values MIX DSGN 190 F...

Page 10: ...ual to the original MIX TARGET This minimizes overheating of the zone while the control is operating at the MIX MIN temperature Warm Weather Shut Down WWSD OCC UNOCC When the outdoor air temperature r...

Page 11: ...le contact allows the boiler to ignite and operate at the boiler s operator setting The control closes the Boiler Enable contact when the position of the mixing valve exceeds 30 The Boiler Enable cont...

Page 12: ...Note The boiler pump should not be operated by the boiler s aquastat as this may lead to improper cycling of the boiler because of inconsistent flow past the boiler return sensor Boiler return sensor...

Page 13: ...k Boiler Universal Sensor Stk 30071 and HeatLink Mixing Universal Sensor Stk 30071 according to the instructions in the 10K Sensors L630070 and run the wiring back to the control If an HeatLink Indoor...

Page 14: ...of the actuating motor and R Cls 10 is connected to the close terminal of the actuating motor C 11 is then connected to the common terminal of the actuating motor 3 4 Power Sys Pmp 5 6 N 120 V ac L N...

Page 15: ...Boil 14 15 Mix Test The Power Supply Make sure exposed wires and bare terminals are not in contact with other wires or grounded surfaces Turn on the power and measure the voltage between the Power L...

Page 16: ...s The terminal blocks should snap firmly into place Install the supplied safety dividers between the unpowered sensor inputs and the powered 120 V ac or 24 V ac wiring chambers Apply power to the cont...

Page 17: ...oor design temperature The OUTDR DSGN setting is set to the typical coldest temperature of the year ADJUST ROOM F OCC The ROOM OCC adjustment is the first item displayed Use the Up or Down button to s...

Page 18: ...Up or Down button to set the scale to F or C ADJUST TARGET MIX F Press and release the Item button to advance to the MIX TARGET adjustment Use the Up or Down button to select the desired temperature...

Page 19: ...t European version only Mix Current mixed supply water temperature as measured by the mixing sensor Mix Target Target mixed supply is the temperature the control is currently trying to maintain at the...

Page 20: ...lation for the heating system OUTDR DSGN OFF European version only Mix Design The design supply water temperature used in the heatloss calculation for the heating system OUTDR DSGN OFF Mix Maximum The...

Page 21: ...pressed the test light is turned on The individual outputs and relays are tested in the following test sequence T est not testing testing testing paused off red red Test Sequence Each step in the test...

Page 22: ...overlooked however it can often save hours of time in troubleshooting a system Note flow directions in the system paying close attention to the location of pumps check valves pressure bypass valves an...

Page 23: ...upply sensor due to a short circuit In this case the control will operate the mixing valve at a fixed output as long as there is a mixing demand Locate and repair the problem as described in 10K Senso...

Page 24: ...ependently on its own operating controls or 2 By activation through a relay of the indoor outdoor controls APPLICATION TO USE OPTION ____ Primary pump P 2 to be wired through a relay in series with th...

Page 25: ...s of each particular control chosen In all cases manufacturer equipment schematics will take precedence over HeatLink electrical schematics All wiring as per applicable electrical codes 2 4 2 2 2 2 2...

Page 26: ...ry pump P 2 to be wired in series with water heater aquastat 24v wiring and zone valve see elect 5 2 For schematic Aquastat to be set at a maximum of 130 f to prevent scalding Pumps P 1 P 2 to be wire...

Page 27: ...er 31360 Boiler Primary Pump P 2 IF Aquastat IFHWH Relay R 1 P 3 Outdoor Sensor Optional Boiler Return Sensor System Pump P 1 Class II Transformer Supply Sensor Relay SLR 2 46151 Zone Thermostats Clas...

Page 28: ...tly on its own operating controls or 2 By activation through a relay of the indoor outdoor controls APPLICATION TO USE OPTION ____ Primary pump P 2 to be wired through a relay in series with the therm...

Page 29: ...This page is intentionally blank...

Page 30: ...and the primary P 2 and system P 3 pump Note DrawingsareforHeatLink suggestedelectricalschematicsonly Usermustdetermineifelectricalschematicwillworkfortheirparticularapplication User must also confirm...

Page 31: ...P 3 Boiler Contacts Mix Supply Sensor Boiler Sensor Optional Unoccupied Switch Outdoor Sensor R 1 DHW Aquastat SPST 24V 24 Vac Class II Transformer R1 R2 45012 24 Vac 2pole Max Pump 1 4 HP 110Vac Max...

Page 32: ...own operating controls or 2 By activation through a relay of the controllers APPLICATION TO USE OPTION ____ Primary pumps P 4 P 5 to be wired through a relay in series with the thermostats or aquastat...

Page 33: ...This page is intentionally blank...

Page 34: ...rmineifelectricalschematicwillworkfortheirparticularapplication User must also confirm all HeatLink schematics with manufacturer schematics of each particular control chosen In all cases manufacturer...

Page 35: ...Power N L 22 Sys P1 4 Red 5 Blk Com 6 Blu 7 Yel 8 Brn Slab 9 Boil 10 Com 11 tN2 12 Mix Ret 13 Mix Sup 14 Com 15 Out Do not apply power Boiler Contacts Outdoor Sensor P 2 Snow Ice Detector Wiring as s...

Page 36: ...y pump P 3 to be wired through a relay in series with the thermostats of the fan coil as well as the indoor outdoor controller Some boilers may have an internal relay which can be used to bring on pri...

Page 37: ...This page is intentionally blank...

Page 38: ...from DHW tank is controlled by StatLink which activates system pump P 4 no tie in to boiler required Note DrawingsareforHeatLink suggestedelectricalschematicsonly Usermustdetermineifelectricalschemat...

Page 39: ...6 17 11 10 9 8 7 6 5 4 3 2 1 Uno Sw Boil Out Com Mix Com C Cls Mix Opn Mix Boiler N Sys Pump Pwr N Pwr L Mixing Demand 10 A 10 A DHW Boiler Contacts see SL2 Boiler Contacts 24V 24 Vac Class II Transfo...

Page 40: ...is provided by the indoor outdoor control unit See ELECT 1 2 1 3 For rough in wiring instructions using StatLink controls see ELECT 1 8 1 9 Boilertofireeither 1 Independentlyonitsownoperatingcontrols...

Page 41: ...er equipment schematics will take precedence over HeatLink electrical schematics All wiring as per applicable electrical codes 4 4 Boiler Primary Pump P 2 Outdoor Sensor Indoor Outdoor Controller 3136...

Page 42: ...HeatLink Mixing Valve Reset Control Stk 31360 Link Heat www heatlinkgroup com HeatLink 42 User Notes...

Page 43: ...HeatLink Mixing Valve Reset Control Stk 31360 HeatLink Link Heat 43 www heatlinkgroup com User Notes...

Page 44: ...proved meets ICES FCC regulations for EMI FI Ambient conditions Indoor use only 32 to 102 F 0 to 39 C 90 RH noncondensing Altitude 2000 m Installation Category II Pollution Category II Power supply 23...

Reviews: