HeatLink
®
Mixing Valve Reset Control Stk# 31360
®
Link
Heat
www.heatlinkgroup.com
H
e
a
tL
in
k
20
Adjust Menu
35ß to 100ßF
(2ß to 38ßC)
Range
ADJUST
MIX MIN
6,
10
Room Occupied
The desired room air temperature during
an occupied (Day) period.
(OUTDR DSGN › OFF)
Room Unoccupied
The desired room air temperature
during an unoccupied (Night) period.
(OUTDR DSGN › OFF)
Mix Target
Mixing setpoint temperature.
(OUTDR DSGN = OFF)
Outdoor Design
The design outdoor air temperature used
in the heatloss calculation for the heating system. For
setpoint operation, set the
OUTDR DSGN
to
OFF.
Terminal Unit
The type of terminal units that are being
used in the heating system.
(OUTDR DSGN › OFF, European version only)
Display
Description
Page #
Installer
Advanced
ADJUST
Terminal Unit
ADJUST
DSGN
OUTDR
ß
F
ADJUST
TARGET
MIX
ß
F
ADJUST
ROOM
ß
F
OCC
UN
ADJUST
ROOM
ß
F
OCC
ADJUST
INDR
MIX
ß
F
ADJUST
DSGN
MIX
ß
F
ADJUST
MIX
ß
F
MAX
Motor Speed
ADJUST
ADJUST
BOIL
ß
F
MIN
Actual
Setting
6,
9
6,
9
7,
8
6,
8
9
10
6,
10
5
7,
10
11,
12
Indoor Design
The design indoor air temperature used in
the heatloss calculation for the heating system.
(OUTDR DSGN › OFF, European version only)
Mix Design
The design supply water temperature used in
the heatloss calculation for the heating system.
(OUTDR DSGN › OFF)
Mix Maximum
The maximum supply temperature for the
mixing system.
(OUTDR DSGN › OFF)
Motor Speed
The time that the actuating motor requires to
operate from fully closed to fully open.
Mix Minimum
The minimum supply temperature for the
mixing system.
(OUTDR DSGN › OFF)
Boil Minimum
The minimum temperature allowed for the
boiler target temperature.
(Boiler sensor is present)
35ß to 100ßF
(2ß to 38ßC)
35ß to 100ßF
(2ß to 38ßC)
60ß to 200ßF
(16ß to 93ßC)
-60ß to 32ßF, OFF
(-51ß to 0ßC, OFF)
1 (High Mass Radiant),
2 (Low MassRadiant),
3 (Fancoil),
4 (Fin-tube Convector),
5 (Radiator),
6 (Baseboard)
70ßF to 220ßF
(21ß to 104ßC)
80ß to 210ßF
(27ß to 99ßC)
30 to 230 seconds
(1 sec. increments)
OFF, 35ß to 150ßF
(OFF, 2ß to 65ßC)
OFF, 80ß to 180ßF
(OFF, 27ß to 82ßC)
ADJUST
DIFF
BOIL
12
Ad, 2ß to 42ßF
(Ad, -17ß to 6ßC)
Boil Differential
The differential that the control is to use
when it is operating the boiler.
(Boiler Sensor DIP switch = Supply AND Boiler
sensor is present, European version only)
Adjust Menu
North American and European Versions
(differences where noted)
“Installer” and “Advanced” levels on European version only.