NOTE: IF THE SYSTEM GOES INTO LOCKOUT, WAIT
30 SECONDS AND RESET THE SYSTEM.
• CHECK FLAME SENSOR POSITION AND CONDITION
• CLEAN FLAME SENSOR WITH STEEL WOOL
• CHECK FLAME SENSOR WIRES AND CONNECTIONS
• CHECK FOR 208-230 VAC ACROSS BLOWER
MOTOR TERMINALS ON CONTROL BOARD
• CHECK CAPACITOR
YES
YES
NO
MAIN BURNER FLAME SUSTAINED
YES
NO
INDOOR BLOWER MOTOR STARTS
AFTER 30 SECONDS
REPLACE SENSOR
NO
REPLACE INTEGRATED
CONTROL BOARD (IFC)
NO
REPLACE INTEGRATED
CONTROL BOARD (IFC)
NO
REPLACE IGNITION CON-
TROL
YES
YES
REPLACE BLOWER
MOTOR
• CHECK FOR OPEN LIMIT
• CHECK FOR OPEN ROLL-OUT CONTROL
• CHECK FOR PROPER THERMOSTAT OPERATION
• REMOVE VALVE LEAD AT GAS VALVE
IF VALVE CLOSES, RECHECK THE THERMOSTAT
AND WIRING. IF OK, THEN REPLACE VALVE
• CHECK FOR OPEN LIMIT OR ROLL-OUT CONTROL
YES
NO
SYSTEM RUNS UNTIL
CALL FOR HEAT ENDS
• CHECK FOR EXHAUST OR INTAKE BLOCKAGE.
CLEAR BLOCKAGE AND RESET CONTROL
• CHECK FOR DIRTY FILTERS
• CHECK FOR RESTRICTED AIRFLOW
TROUBLESHOOTING ENDS
REPEAT PROCEDURE UNTIL TROUBLE FREE
OPERATION IS OBTAINED.
YES
NO
TURN THERMOSTAT OFF
VALVE SHUTS OFF
FLAME SHUTS OFF
YES
NO
INDUCED DRAFT MOTOR STOPS
AFTER 5 SECOND POSTPURGE
YES
YES
• CHECK FOR DIRTY FILTERS
• CHECK FOR RESTRICTED
AIR-FLOW
CHECK FOR EXHAUST,
INTAKE OR HEAT EXCHANG-
ER BLOCKAGE
CLEAR BLOCKAGE AND
RESET CONTROL
YES
NO
INDOOR BLOWER MOTOR STOPS
AFTER 90 SECONDS
Summary of Contents for TGC Series
Page 24: ...24 FIGURE 20 FIGURE 21 INTEGRATED FURNACE CONTROL SPEED TAP BLOCK FIGURE 22...
Page 25: ...25 FIGURE 22 Continued...
Page 37: ...37 FIGURE 23 WIRING DIAGRAM...
Page 38: ...38 FIGURE 24 WIRING DIAGRAM...
Page 39: ...39 FIGURE 25 WIRING DIAGRAM...
Page 40: ...40 FIGURE 26 WIRING DIAGRAM...
Page 41: ...41 FIGURE 27 WIRING DIAGRAM...
Page 42: ...42 FIGURE 28 WIRING DIAGRAM...
Page 43: ...43 FIGURE 29 SYSTEM CHARGE CHARTS 3 TON COOLING 13 SEER...
Page 44: ...44 FIGURE 30 SYSTEM CHARGE CHARTS 3 5 TON COOLING 13 SEER...
Page 45: ...45 FIGURE 31 SYSTEM CHARGE CHARTS 4 TON COOLING 13 SEER...
Page 46: ...46 FIGURE 32 SYSTEM CHARGE CHARTS 5 TON COOLING 13 SEER...
Page 50: ...50...
Page 51: ...51...
Page 52: ...52 CM 1206...