2
8
GENERAL DATA - TGC MODELS
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Model RKNA- Series
Cooling Performance
1
Gross Cooling Capacity Btu [kW]
EER/SEER
2
Nominal CFM/ARI Rated CFM [L/s]
ARI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
Heating Performance (Package Gas/Electric)
3
Heating Input Btu [kW]
Heating Output Btu [kW]
Temperature Rise Range ºF [ºC]
AFUE %
Steady State Efficiency (%)
No. Burners
No. Stages
Gas Connection Pipe Size in. [mm]
Compressor
No./Type
Outdoor Sound Rating (dB)
Outdoor Coil - Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Indoor Coil - Fin Type
Tube Type
Tube Size in. [mm]
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
CFM [L/s]
No. Motors/HP
Motor RPM
Indoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter - Type
Furnished
(NO.) Size Recommended in. [mm x mm x mm]
Refrigerant Charge Oz. [g]
Weights
Net Weight lbs. [kg]
Ship Weight lbs. [kg]
A048JK13E
49,000 [14.36]
11.4/13.1
1600/1550 [755/731]
47,000 [13.77]
33,600 [9.84]
13,400 [3.93]
4.15
135,000 [39.56]
106,500 [31.2]
50-80 [27.8/44.4]
80
81
6
1
0.5 [12.7]
1/Copeland Scroll
78
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
Corrugated
Rifled
0.375 [9.5]
5.17 [0.48]
3 / 15 [6]
TX Valves
1/0.75 [19.05]
Propeller
1/24 [609.6]
Direct/1
3680 [1737]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Direct/3
1
1/2
1075
48
Disposable
Yes
(1)1x16x25 [25x406x635]
(1)1x16x25 [25x406x635]
167 [4734]
585 [265]
592 [269]
Model TGC-
S
eries
TGC-04
8
C-1K-1
3
0
A060CK13E
60,000 [17.58]
11.6/13
2000/1900 [897/897]
58,000 [16.99]
42,000 [12.31]
16,000 [4.69]
5
135,000 [39.56]
109,400 [32.05]
40-70 [22.2/38.9]
80
81
6
1
0.5 [12.7]
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
Corrugated
Rifled
0.375 [9.5]
5.17 [0.48]
3 / 15 [6]
TX Valves
1/0.75 [19.05]
Propeller
1/24 [609.6]
Direct/1
3930 [1855]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Direct/3
1
Disposable
Yes
(1)1x16x25 [25x406x635]
(1)1x16x25 [25x406x635]
160 [4536]
597 [271]
604 [274]
1
1075
48
TGC-060C-
3
K-1
3
0
A060DL13E
Continued ->
60,000 [17.58]
11.6/13
2000/1900 [897/897]
58,000 [16.99]
42,000 [12.31]
16,000 [4.69]
5
135,000 [39.56]
109,400 [32.05]
40-70 [22.2/38.9]
80
81
6
1
0.5 [12.7]
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
Corrugated
Rifled
0.375 [9.5]
5.17 [0.48]
3 / 15 [6]
TX Valves
1/0.75 [19.05]
Propeller
1/24 [609.6]
Direct/1
3930 [1855]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
3/4
1725
56
Disposable
Yes
(1)1x16x25 [25x406x635]
(1)1x16x25 [25x406x635]
160 [4536]
597 [271]
604 [274]
TGC-060C-4K-1
3
0
A060JK13E
60,000 [17.58]
11.6/13
2000/1900 [897/897]
58,000 [16.99]
42,000 [12.31]
16,000 [4.69]
5
135,000 [39.56]
106,500 [31.2]
40-70 [22.2/38.9]
80
81
6
1
0.5 [12.7]
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
Corrugated
Rifled
0.375 [9.5]
5.17 [0.48]
3 / 15 [6]
TX Valves
1/0.75 [19.05]
Propeller
1/24 [609.6]
Direct/1
3930 [1855]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Direct/3
1
1075
48
Disposable
Yes
(1)1x16x25 [25x406x635]
(1)1x16x25 [25x406x635]
160 [4536]
597 [271]
604 [274]
1
NOTES:
1. Cooling Perform
a
nce is r
a
ted
a
t 95° F
a
mbient,
8
0° F entering dry bulb, 67° F entering wet bulb. Gross c
a
p
a
city does not include the effect of f
a
n motor he
a
t. ARI c
a
p
a
city
is net
a
nd includes the effect of f
a
n motor he
a
t. Units
a
re suit
a
ble for oper
a
tion to ±20% of nomin
a
l cfm. Units
a
re certified in
a
ccord
a
nce with the Unit
a
ry Air Conditioner
Equipment certific
a
tion progr
a
m, which is b
a
sed on ARI
S
t
a
nd
a
rd 210/240 or
3
60.
2. EER
a
nd/or
S
EER
a
re r
a
ted
a
t ARI conditions
a
nd in
a
ccord
a
nce with DOE test procedures.
3
. He
a
ting Perform
a
nce limit settings
a
nd r
a
ting d
a
t
a
were est
a
blished
a
nd
a
pproved under l
a
bor
a
tory test conditions using Americ
a
n N
a
tion
a
l
S
t
a
nd
a
rd Institute st
a
nd
a
rds.
R
a
tings shown
a
re for elev
a
tions up to 2000 feet. For elev
a
tions
a
bove 2000 feet, r
a
tings should be reduced
a
t the r
a
te of 4% for e
a
ch 1000 feet
a
bove se
a
level.
TGC-060C-1K-1
3
0
Summary of Contents for TGC Series
Page 24: ...24 FIGURE 20 FIGURE 21 INTEGRATED FURNACE CONTROL SPEED TAP BLOCK FIGURE 22...
Page 25: ...25 FIGURE 22 Continued...
Page 37: ...37 FIGURE 23 WIRING DIAGRAM...
Page 38: ...38 FIGURE 24 WIRING DIAGRAM...
Page 39: ...39 FIGURE 25 WIRING DIAGRAM...
Page 40: ...40 FIGURE 26 WIRING DIAGRAM...
Page 41: ...41 FIGURE 27 WIRING DIAGRAM...
Page 42: ...42 FIGURE 28 WIRING DIAGRAM...
Page 43: ...43 FIGURE 29 SYSTEM CHARGE CHARTS 3 TON COOLING 13 SEER...
Page 44: ...44 FIGURE 30 SYSTEM CHARGE CHARTS 3 5 TON COOLING 13 SEER...
Page 45: ...45 FIGURE 31 SYSTEM CHARGE CHARTS 4 TON COOLING 13 SEER...
Page 46: ...46 FIGURE 32 SYSTEM CHARGE CHARTS 5 TON COOLING 13 SEER...
Page 50: ...50...
Page 51: ...51...
Page 52: ...52 CM 1206...