![Heat & Glo TRUE-36C Owner'S Manual Download Page 34](http://html.mh-extra.com/html/heat-and-glo/true-36c/true-36c_owners-manual_2115513034.webp)
34
Heat & Glo •
TRUE-36, TRUE-42, TRUE-50 • 2282-900 Rev. i •
4/13
A*
B
10 in.
12 in.
DO NOT PACK WITH
INSULATION OR OTHER
MATERIAL
A. Pipe Clearances to Combustibles
WARNING! Risk of Fire!
Maintain air space clearance to
vent.
DO NOT
pack insulation or other combustibles:
• Between ceiling
fi
restops
• Between wall shield
fi
restops
• Around vent system
Failure to keep insulation or other material away from
vent pipe may cause overheating and
fi
re.
88
Vent Clearances and Framing
Figure 8.2 Wall Penetration
* Shows center of vent framing hole with minimum vertical for top venting. The
center of the hole is one (1) in. (25.4 mm) above the center of the horizontal
vent pipe.
Figure 8.1 Horizontal Venting Clearances To Combustible
Materials
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).
DVP heat shield
- designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184
mm) thick
.
,
f wall thickness is less than 4 in. the e
[
isting heat shields must be field trimmed.
,
f
wall thickness is greater than 7-1/4 in. a DVP-HSM-B will be required.
,
f wall thickness is less than 4-3/8 the e
[
isting heat shields must be field trimmed.
,
f wall thickness is greater than 7-
/8 in. a DVP-HSM-B will be required.
(DVP Pipe Shown)
3 in. (76 mm)
top clearance *
1 in. (2
mm)
clearance
bottom & sides
Heat
Shield
Wall
Shield
Firestop
Heat
Shield
WALL
3 in. (76 mm)
top clearance
1 in. (2
mm)
clearance around
vertical sections
B. Wall Penetration Framing
Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must
frame a hole for the wall shield
fi
restop(s). The wall shield
fi
restop maintains minimum clearances and prevents cold
air in
fi
ltration.
• The opening must be framed on all four sides using the
same size framing materials as those used in the wall
construction.
• DVP pipe - A wall shield
fi
restop is required on one side
only on interior walls. If your local inspector requires a
wall shield
fi
restop on both sides, then both wall shield
fi
restops must have a heat shield (refer to Section
16.B.) attached to them.
• See Section 10.H. for information for regarding the in-
stallation of a horizontal termination cap.
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by non-com-
bustible materials such as concrete, a hole with diameter
one inch greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall
shield
fi
restop is only required on one side and no heat
shield is necessary.
MODEL
A*
B
TRUE-36 NG/LP
74-3/16 in.
73-3/16 in.
TRUE-42 NG
79-3/16 in.
78-3/16 in.
TRUE-42 LP
91-3/16 in.
90-3/16 in.
TRUE-50 NG/LP
83-3/16 in.
82-3/16 in.