background image

23

Heat & Glo  •  SL-5F-IFT, SL-7F-IFT Installation Manual  •  2638-980 Rev. H  •  6/22

Figure 4.14

Top Vent - Horizontal Termination  - (continued)

H

2

H

1

V

2

V

1

Note

: Use SLP Series 

components only.

Fire Risk.   
•  When  using  SLP-HRC-SS  termination  cap 

on top vented fireplaces, a one foot minimum 

vertical vent section is required before installing 

first elbow.   

WARNING *

V

1

 Minimum

H

Maximum**

H

+ H

2

 Maximum**

V

2

V

1

 + V

2

 Minimum

90 Elbow Only*

1-1/2 ft. 457 mm

2 ft.

610 mm

*

*

1/2 ft.* 152 mm 1-1/2 ft. 457 mm

4 ft.

1.2 m

*

*

1-1/2 ft. 457 mm

3 ft.

914 mm

6 ft.

1.8 m

*

*

2-1/2 ft. 762 mm

5 ft.

1.5 m

10 ft.

3.0 m

*

*

3-1/2 ft.

1.1 m

7 ft.

2.1 m

14 ft.

4.3 m

*

*

4-1/2 ft.

1.4 m

14 ft.

4.3 m

14 ft.

4.3 m

*

*

H

1

 + H

2

 MAX. =14 ft. (4.3 m)

V

1

 + V

2

 + H

1

 + H

2

 MAX. = 40 ft. (12.2 m)

No specific restrictions on this value EXCEPT V

1

 + V

2

 + H

1

 + H

2

 CANNOT exceed 40 ft. (12.2 m).

* See Warning Below.

Three Elbows

**

Note

: When using 

SLP-FLEX (6-5/8 in.)

 venting, there 

MUST be a 25% reduction in total H when using flex vent.

See Figure 4.8. 

Summary of Contents for SL-5F-IFT

Page 1: ...cy or the gas supplier WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Models SL 5F IFT SL 7F IFT This appliance may...

Page 2: ...4 4 Termination Location and Vent Information A Approved Pipe 15 B Vent Termination Minimum Clearances 15 C Vent Terminal Clearances 17 D Use of Elbows 18 E Use of Flex Vent SLP FLEX Series 6 5 8 Inch...

Page 3: ..._________________ Was a conversion performed ___________________________ Leak check performed and inlet pressure verified ___________________________ Verified proper air shutter setting for installati...

Page 4: ...ADA Input ratings are certified without a reduction of input rate for elevations up to 4500 feet 1370 m above sea level Please consult provincial and or local authorities having jurisdiction for insta...

Page 5: ...tered or unplastered shall be considered combustible materials G Electrical Codes NOTICE This appliance must be electrically wired and grounded in accordance with local codes or in the absence of loca...

Page 6: ...gas fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local...

Page 7: ...aming square Voltmeter Electric drill and bits 1 4 in Plumb line Safety glasses Gloves Wrenches Reciprocating saw 1 4 in nut driver Non corrosive leak check solution 1 2 3 4 in length 6 or 8 Self dril...

Page 8: ...remove the appliance and components from the packaging The vent system components and decorative barrier fronts may be shipped in separate packages If packaged separately the log set and appliance gra...

Page 9: ...D 18 1 16 459 21 1 2 546 E 34 1 16 865 37 5 8 956 F 3 9 16 90 3 9 16 90 G 6 7 8 175 6 7 8 175 H 23 3 8 594 26 7 8 683 I 34 3 8 873 37 7 8 962 J 36 7 16 926 39 15 16 1014 K 8 203 8 203 L 8 13 16 224 8...

Page 10: ...arrier removed If decorative barrier front is not present contact dealer Note See Section 10 for hearth mantel and finishing requirements Figure 3 2 Decorative Barrier Front Dimensions Firescreen C B...

Page 11: ...the barrier removed Optional Clean Face Decorative Barrier Kit must be ordered at time of fireplace purchase If decorative barrier front is not present contact dealer Note See Section 10 for hearth m...

Page 12: ...s diagrams are not drawn to scale Actual installation may vary due to individual design preference Figure 3 4 Appliance Locations K C A L F I B G E D J J G A F C A H M N Refer to Section 10 for mantel...

Page 13: ...level For installations with vinyl flooring see Section 3 D MINIMUM FRAMING DIMENSIONS Models A B C D E F G H I J DVP Pipe SLP Pipe Rough Opening Height DVP Pipe SLP Pipe Rough Opening Width Clearance...

Page 14: ...m of 300 F continu ous exposure rating or stuffed with unfaced insulation If the appliance is being installed on a cement surface a layer of plywood may be placed underneath to prevent conducting cold...

Page 15: ...nt clearance to combustibles as specified DO NOT pack air space with insulation or other materials Failure to keep insulation or other materials away from vent pipe could cause overheating and fire WA...

Page 16: ...ity to doors traffic areas or where people may pass or gather sidewalk deck patio etc Listed cap shields available Contact your dealer Local codes or regulations may require different clearances Heart...

Page 17: ...rance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance termination mechanical or non mechanical 9 in min 229 mm min 12 in min 305 mm min I clearance to...

Page 18: ...T I V E L E N G T H Y X X X DVP Pipe Effective Length Rise Run Inches Millimeters Inches Millimeters DVP4 4 102 2 3 4 70 DVP6 6 152 4 1 4 108 DVP12 12 305 8 1 2 216 DVP24 24 610 17 432 DVP36 36 914 25...

Page 19: ...ort is required at each change in venting direction and in any location where it is necessary to maintain the necessary clearance to combustibles A simple up and out installation Figure 4 8 requires o...

Page 20: ...lled When penetrating a combustible ceiling a ceiling firestop must be installed Horizontal runs of vent do not require vertical rise horizontal runs may be level Horizontal termination cap should hav...

Page 21: ...ot minimum vertical vent section is required before installing first elbow WARNING V1 Minimum H1 Maximum 90 Elbow Only 2 ft 610 mm 1 2 ft 152 mm 2 ft 610 mm 1 1 2 ft 457 mm 3 ft 914 mm 2 1 2 ft 762 mm...

Page 22: ...tion is required before installing first elbow WARNING Figure 4 13 V1 Minimum H1 H2 Maximum 90 Elbow Only 1 2 ft 152 mm 1 2 ft 152 mm 1 ft 305 mm 1 1 2 ft 457 mm 2 ft 610 mm 2 1 2 ft 762 mm 4 ft 1 2 m...

Page 23: ...um H1 H2 Maximum V2 V1 V2 Minimum 90 Elbow Only 1 1 2 ft 457 mm 2 ft 610 mm 1 2 ft 152 mm 1 1 2 ft 457 mm 4 ft 1 2 m 1 1 2 ft 457 mm 3 ft 914 mm 6 ft 1 8 m 2 1 2 ft 762 mm 5 ft 1 5 m 10 ft 3 0 m 3 1 2...

Page 24: ...t restrictor installation Exhaust restrictor Instructions Exhaust restrictors are recommended for these verti cally terminated products which have excessive draft Exhaust restrictors will compensate f...

Page 25: ...imum 90 Elbow Only 1 1 2 ft 457 mm 1 2 ft 152 mm 2 ft 610 mm 1 1 2 ft 457 mm 3 ft 914 mm 2 1 2 ft 762 mm 5 ft 1 5 m 3 1 2 ft 1 1 m 7 ft 2 1 m 4 1 2 ft 1 4 m 15 ft 4 6 m H1 MAX 15 ft 4 6 m V1 V2 H1 MAX...

Page 26: ...V2 V1 V2 Minimum 90 Elbow Only 1 2 ft 152 mm 1 2 ft 152 mm 1 ft 305 mm 1 1 2 ft 457 mm 2 ft 610 mm 2 1 2 ft 762 mm 4 ft 1 2 m 3 1 2 ft 1 1 m 6 ft 1 8 m 4 1 2 ft 1 4 m 14 ft 4 3 m H1 H2 MAX 14 ft 4 3 m...

Page 27: ...y Figure 4 19 Top Vent Vertical Termination continued V1 H1 V2 V3 H2 V1 MIN H1 MAX V2 MIN H2 MAX V3 MIN 1 1 2 ft 457 mm 4 ft 1 2 m 4 ft 1 2 m 4 ft 1 2 m 3 1 2 ft 1 1 m V1 V2 V3 H1 H2 Maximum 40 ft 12...

Page 28: ...8 980 Rev H 6 22 28 Rear Vent Horizontal Termination No Elbow Figure 4 20 Note Use DVP Series components only Figure 4 21 H1 H1 9 in 229 mm Maximum Rear Vent Horizontal Termination One 45 Elbow Note U...

Page 29: ...1 2 ft 762 mm 3 ft 914 mm 1 ft 305 mm 3 ft 914 mm 6 ft 1 8 m 5 ft 1 5 m 3 ft 914 mm 5 ft 1 5 m 10 ft 3 0 m 7 ft 2 1 m 5 ft 1 5 m 7 ft 2 1 m 14 ft 4 3 m H1 MAX 7 ft 2 1 m H1 H2 MAX 14 ft 4 3 m V1 H1 H2...

Page 30: ...STALLED HORIZONTALLY H1 H2 V2 H1 V1 V1 MIN H1 MAX 1 ft 305 mm 3 1 2 ft 1 1 m 2 ft 610 mm 5 1 2 ft 1 7 m 3 ft 914 mm 7 1 2 ft 2 3 m H MAX 7 1 2 ft 2 3 m V1 H1 MAX 40 ft 12 2 m H1 H2 MAX V1 MIN Back to...

Page 31: ...2 MAX V2 V1 V2 Minimum Back to back elbows 1 1 2 ft 457 mm 1 ft 305 mm 2 1 2 ft 762 mm 1 ft 305 mm 3 1 2 ft 1 1 m 3 ft 914 mm 6 1 2 ft 2 0 m 2 ft 610 mm 5 1 2 ft 1 7 m 5 ft 1 5 m 10 1 2 ft 3 2 m 3 ft...

Page 32: ...Have the chimney and adjacent structure inspected and cleaned by qualified professionals Hearth Home Technologies recommends that NFI or CSIA certified professionals or technicians under the directio...

Page 33: ...inlet collar on top of the DV 46DVA GCL adapter with three self tapping screws To minimize cold air drafts seal around the flex vents at the damper inside the chimney with non combustible unfaced fib...

Page 34: ...te Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm DVP heat shield designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in the existing heat...

Page 35: ...ired on one side only on interior walls If your local inspector re quires a wall shield firestop on both sides then both wall shield firestops must have a heat shield refer to Section 12 A attached to...

Page 36: ...ation around the vent Maintain clearances to vent to prevent overheating A ceiling firestop MUST be used between floors and attics DVP pipe only Frame an opening 10 in by 10 in 254 mm by 254 mm whenev...

Page 37: ...hipped WARNING Risk of Fire Elbow heat shield must be installed if required Overheating will occur ELBOW HEAT SHIELD To Install Elbow Heat Shield 1 Remove the elbow heat shield from the shipping posi...

Page 38: ...12 6 16 2 SCREWS 2 SCREWS Figure 6 7 Replace the two screws as shown WARNING Risk of Fire Do not remove heat shield Elevated header temperatures may cause a fire NOTICE Once the seal cap has been remo...

Page 39: ...he gasket to the outer wrap 2 SCREWS Rear Vent NOTICE Once appliance is set up for top or rear venting it CANNOT be changed at a later time NOTICE Once the seal cap has been removed it CANNOT be reatt...

Page 40: ...t Gas kit may be installed See Figure 6 13 Remove the knockouts from the appliance with a tin snips Center the duct collar around the exposed hole and attach it to the appliance with 3 screws Note Do...

Page 41: ...ppliance to the framing by using nails or screws through the nailing tabs Use a minimum of one fastener per nailing tab Optional Secure the appliance to the floor by inserting two screws through the p...

Page 42: ...nects directly to the horizontal termination cap Apply a bead of silicone sealant 300 F minimum con tinuous exposure rating inside the female outer pipe joint prior to joining sections See Figure 7 1...

Page 43: ...outside of connecting joint after joining sections On horizontal pipe runs it is recom mended that the tape seam is positioned on the bottom side of the vent pipe WARNING Risk of Fire or Explosion Ven...

Page 44: ...section See Figure 7 7 120 Figure 7 8 Securing Vertical Pipe Sections 120 Figure 7 9 Securing Horizontal Pipe Sections C Secure the Vent Sections WARNING Risk of Fire Explosion or Asphyxiation Improp...

Page 45: ...D Disassemble Vent Sections Rotate either section see Figure 7 10 so the seams on both pipe sections are aligned as shown in Figure 7 11 Pull carefully to separate the pieces of pipe Figure 7 11 Align...

Page 46: ...l the exposed pipe section seams that are located above the roof SEAL Figure 7 12 Figure 7 12 Assemble and Install Storm Collar CAUTION Risk of Cuts Abrasions or Flying Debris Wear protective gloves a...

Page 47: ...eat shields must overlap 1 1 2 in 38 mm mini mum There are two sections of the heat shield One section is factory attached to the wall shield firestop The other section is factory attached to the cap...

Page 48: ...seal as appropriate for siding material at outside edges of cap When installing a horizontal termination cap follow the cap location guidelines as prescribed by current ANSI Z223 1 and CAN CGA B149 i...

Page 49: ...box receptacle to the outer shell A General Information WARNING Risk of Shock DO NOT wire 110 120 VAC to the ignition module or to the appliance wall switch IPI Incorrect wiring will damage controls N...

Page 50: ...y The electrical components are installed on the component tray If it becomes necessary to remove the components use the information in Figure 8 2 to remove them and reinstall them correctly on the co...

Page 51: ...f an emergency power outage Batteries should not be used as a primary long term power source Batteries tend to corrode over time When using batteries as a power source the 6 volt transformer must be u...

Page 52: ...n box and connect to the top fan switch connector 1 4 inch male as shown Red Switch Switch Box Red Black Black Green Green White Power Supply Wires White Red Black Green White Minimum 14 3 AWG with Gr...

Page 53: ...ine pressure is greater than 1 2 psig 9 9 Gas Information Gas Pressure Natural Gas Propane Minimum inlet pressure 5 0 in w c 11 0 in w c Maximum inlet pressure 10 0 in w c 13 0 in w c Manifold pressur...

Page 54: ...otential NOTICE Flames should not appear orange or stretch to the top refractory If flames are dark orange with dark smoky tips provide more primary air to the burner by opening the air shutter accord...

Page 55: ...300 F minimum sealant Refer to Figure 10 1 and Figure 10 2 WARNING B Installing a Television If installing a television TV above the appliance see Section 3 of the appliance Owner s Manual 0 IN 0 IN 0...

Page 56: ...ible Mantel Leg or Wall Projections Acceptable on both sides of opening UNLIMITED TOP VIEW FIREPLACE OPENING See Dimension B on Appliance Dimension Diagram Figure 3 1 3 IN MIN 6 IN MAX Figure 10 6 Com...

Page 57: ...57 Heat Glo SL 5F IFT SL 7F IFT Installation Manual 2638 980 Rev H 6 22 Figure 10 8 Non Combustible Zone 1 2 in SHEETROCK OR COMBUSTIBLE MATERIAL 3 1 2 in 1 2 in NON COMBUSTIBLE ZONE...

Page 58: ...l barrier to prevent direct contact with the fixed glass panel DO NOT operate the fireplace with the barrier removed Contact your dealer or Hearth Home Technologies if the barrier is not present or he...

Page 59: ...corative barrier front of the ap pliance depending on the fireplace model Splatter guards must be removed before appliance is fired WARNING Risk of Fire Close the ball valve before in stalling the spl...

Page 60: ...own in Figure 4 Figure 3 Log 1 Bottom View Figure 1 Figure 2 Location of Log Placement Pins and Corresponding Log s Figure 4 Log 1 in Position Figure 5 Log 2 Bottom View 1 1 5 5 4 4 3 3 2 2 HOLES FOR...

Page 61: ...he appliance It will be needed for future cleaning of the logs and lava rock or servicing of the appliance Once the rock jig is removed visually inspect the burner area to ensure that no lava rock is...

Page 62: ...Log 5 is used twice in this log set The left log is located by placing the Y Shaped end on the locating grooves of Log 3 and setting the other end on the flat area of Log 1 See Figure 9 to reference...

Page 63: ...2 2033 709 Log 2 is used twice in this log set Log 2 also has holes on the bottom side that will be used for positioning them in the firebox See Figure 5 Locate the two Log 2 s and place them on the...

Page 64: ...the basepan There should be approx a 1 4 inch gap between the end of the log and the firebox The other Log 3 will be placed on the right in a position to mirror the first Log 3 Place it in position b...

Page 65: ...ayed ignition may occur Remove the burner tube slot cover by removing the shipping screw on the back Keep the burner tube slot cover and screw in the lower cavity of the appliance It will be needed fo...

Page 66: ...e Y Shaped section will rest on the left side Log 2 See Figure 16 The left branch of the Y should rest where the burned area of the left Log 2 begins See Figure 17 Figure 15 Log 4 2nd of 2 1 1 3 3 FLA...

Page 67: ...lass assembly with care Inspect the gasket to ensure it is undamaged and inspect the glass for cracks chips or scratches DO NOT strike slam or scratch glass DO NOT operate fireplace with glass removed...

Page 68: ...prevent direct contact with the hot viewing glass DO NOT operate the fireplace with the barrier removed Contact your dealer or Hearth Home Technologies if the barrier is not present or help is needed...

Page 69: ...in 289 mm 1 1 4 in 32 mm 9 1 4 in 235 mm 13 1 4 in 337 mm 1 2 in TYP DVP90ST 90 Elbow 10 in 254 mm 10 in 254 mm 1 in 25 mm DVP FS Ceiling Firestop DVP45 45 Elbow DVP Pipe see chart Effective Height Le...

Page 70: ...1 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wal...

Page 71: ...in 337 mm RF12 Roof Flashing Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC...

Page 72: ...n 356 mm 17 3 4 in 451 mm 7 1 4 in 12 in 305 mm 184 mm 5 1 4 in 133 mm 12 1 2 in 318 mm DVP TVHW VerticalTermination Cap Highwind 14 in 356 mm 12 in 305 mm 12 1 8 in 314 mm 7 1 8 in 181 mm 8 3 4 in 22...

Page 73: ...87 Effective Length 5 3 4 to 8 3 8 in 146 to 213 mm 5 1 2 in 140 mm 8 3 8 in 213 mm DVP HRC ZC SS Figure 12 5 Vent Components DECORATIVE TERMINATIONS SHROUDS Only use listed decorative termination cap...

Page 74: ...omponents Diagrams continued PVV SLP Vertical Power Vent Note A wire harness is required to power the PVV SLP and connect it to the appliance It is ordered separately from the PVV SLP Contact your dea...

Page 75: ...ordered separately from PVI SLP B Contact your dealer to order 16 IN 406 mm 15 IN 381 mm 16 11 16 IN 424 mm 9 3 16 IN 233 mm 4 1 2 IN 114 mm 16 11 16 IN 424 mm 13 5 8 IN 346 mm 12 1 2 IN 318 mm 12 1 2...

Page 76: ...2 IN 394 mm 11 1 2 IN 292 mm 8 IN 203 mm 4 3 8 IN 112 mm 10 IN 254 mm 5 1 4 IN 135 mm 2 1 4 IN 57 mm 9 1 2 IN 241 mm 4 3 4 IN 121 mm 2 1 4 IN 57 mm 1 1 2 IN 38 mm 6 1 4 IN 159 mm Front View Top View S...

Page 77: ...e Height Length SLP PIPE SLP HVS Horizontal Pipe Support SLP FS Ceiling Firestop SLP WS Wall Shield Firestop DVP SLP24 Adapter 6 1 2 in 165 mm 25 3 16 in 640 mm 8 1 16 in 205 mm 10 7 8 in 276 mm 8 7 8...

Page 78: ...han 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield Term Cap Minimum Effective Length Maximum Effective Length Trap1 3 1 8 in 4 3 4 in 79 mm 121mm Trap2 5 1 4 in 9 1 4 in 133 mm 235 mm 8 in 2...

Page 79: ...NKD Snorkel Termination Cap SLP TVHW Vertical Termination Cap 13 1 2 in 343 mm 28 1 2 in 724 mm 10 11 16 in 271mm 17 7 8 IN 454 mm 7 3 8 IN 187 mm 14 IN 356 mm 12 IN 305 mm SLP TB1 Basement Vent Cap 4...

Page 80: ...near Appliance Connector 768 380A Required Stainless Steel Flex Pipe DVP 2SL Adapter COAXIAL to COLINEAR VENTING Figure 12 13 Coaxial to Colinear Vent Components SLP HHW2 Horizontal High Wind Terminat...

Page 81: ...appliance are accessible Install approved accessories per instructions included with accessories Contact your dealer for a list of ap proved accessories WARNING Risk of Fire and Electric Shock Use ONL...

Reviews: