background image

Heat & Glo  •  ST-36TR-IPI, PIER-36TR-IPI  •  2176-900 Rev. L  •  4/15

46

G.  Install Metal Roof Flashing

•  See minimum vent heights for various pitched roofs 

(Figure 10.14) to determine the length of pipe to extend 
through the roof.

•  Slide the roof 

fl

 ashing over the pipe sections extending 

through the roof as shown in Figure 10.15.

Roof Pitch                            H (Min.) Ft.

Flat to 6/12........................................1.0*
Over 6/12 to 7/12 ............................1.25*
Over 7/12 to 8/12 ..............................1.5*
Over 8/12 to 9/12 ..............................2.0*
Over 9/12 to 10/12 ............................2.5*
Over 10/12 to 11/12 ......................... 3.25
Over 11/12 to 12/12 ........................... 4.0
Over 12/12 to 14/12 ........................... 5.0
Over 14/12 to 16/12 ........................... 6.0
Over 16/12 to 18/12 ........................... 7.0
Over 18/12 to 20/12 ........................... 7.5
Over 20/12 to 21/12 ........................... 8.0

* 3 foot minimum in snow regions

Figure 10.14  Minimum Height From Roof To Lowest Discharge  
 

    Opening

HORIZONTAL

OVERHANG

VERTICAL

WALL

GAS DIRECT VENT 
TERMINATION CAP

12

X

ROOF PITCH

IS  X/ 12

LOWEST 

DISCHARGE 

OPENING

2 FT.

MIN.

20 INCHES MIN.

H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING

CAULK

NOTICE: 

Failure to properly caulk the roof 

fl

 ashing could 

cause water entry.

•  Caulk the gap between the roof 

fl

 ashing and the outside 

diameter of the pipe. 

•  Caulk the perimeter of the 

fl

 ashing where it contacts the 

roof surface. See Figure 10.15.

Figure 10.16   Insert Bolt into Brackets

Figure 10.16   Insert Bolt into Brackets

Figure 10.15   

Figure 10.15   

H.  Assemble and Install Storm Collar

CAUTION! Risk of Cuts, Abrasions or Flying Debris. 

Wear protective gloves and safety glasses during instal-
lation. Sheet metal edges are sharp.

•   Slide the storm collar onto the exposed pipe section  

and align brackets.

•  Insert a bolt (provided) through the brackets and install 

nut. Do not completely tighten.

•  Slide the assembled storm collar down the pipe section 

until it rests on the roof 

fl

 ashing (see Figure 10.16).

•   Tighten nut and make sure the collar is tight against the 

pipe section.

•  Caulk around the top of the storm collar. See Figure 10.17.

Summary of Contents for PIER-36TR-IPI

Page 1: ...s in Canada This appliance is only for use with the type s of gas indicated on the rating plate This appliance is not convertible for use with other gases unless a certified kit is used DO NOT store o...

Page 2: ...utilise utilise avec avec un un combustible combustible solide solide This This appliance appliance must must be be installed installed in in accordance accordance with with local local codes codes i...

Page 3: ...ances A Selecting Appliance Location 18 B Constructing the Appliance Chase 19 C Clearances 19 D Mantel and Wall Projections 21 6 Termination Locations A Vent Termination Minimum Clearances 23 B Contin...

Page 4: ...Fixed Glass Assembly 63 B Remove the Shipping Materials 63 C Clean the Appliance 63 D Accessories 63 E Lava Rock Teco Sil and Glowing Ember Placement 63 F Install the Log Assembly 65 G Fixed Glass Ass...

Page 5: ...date of original purchase In the case of new home construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent aut...

Page 6: ...USIONS This warranty does not cover the following Changes in surface finishes as a result of normal use As a heating appliance some changes in color of interior and exterior surface finishes may occur...

Page 7: ...material that can ignite and burn whether flame proofed or not or plastered or unplastered shall be considered combustible materials NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE This appliance is te...

Page 8: ...led heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas in...

Page 9: ...REN TO TOUCH GLASS Keep children away CAREFULLY SUPERVISE children in same room as fireplace Alert children and adults to hazards of high temperatures High temperatures may ignite clothing or other fl...

Page 10: ...xed glass panel DO NOT operate the fireplace with the barrier removed Contact your dealer or Hearth Home Technologies if the barrier is not present or help is needed to properly install one For more i...

Page 11: ...ation and operating instruc tions accompanying appliance Hot while in operation DO NOT touch Keep children clothing furniture gasoline and other liquids having flammable vapors away DO NOT operate the...

Page 12: ...nsation will disappear Blue flames This is a result of normal operation and the flames will begin to yellow as the fireplace is al lowed to burn for 20 to 40 minutes Odor from fireplace When first ope...

Page 13: ...aintained your fireplace will give you many years of trouble free service We recommend an nual service by a qualified service technician Surrounds Decorative Fronts Frequency Annually By Homeowner Too...

Page 14: ...teel wool cloths mineral spirits primer and touch up paint Inspect for paint condition warped surfaces corrosion or perforation Sand and repaint as necessary Replace fireplace if firebox has been perf...

Page 15: ...re battery failure or leaking Check for smooth lighting and ignition carryover to all ports Verify that there is no ignition delay Inspect for lifting or other flame problems Verify air shutter settin...

Page 16: ...ILING FIRESTOP ON FLOOR OF ATTIC SECTION 8 C VERTICAL TERMINATION CAP SECTION 10 J VENT PIPE PENETRATES ROOF PREFERABLY WITHOUT AFFECTING ROOF RAFTERS SECTION 8 C FRAMING HEADED OFF IN CEILING JOISTS...

Page 17: ...nce dry C Tools and Supplies Needed Before beginning the installation be sure that the following tools and building supplies are available Tape measure Framing material Pliers Non corrosive leak check...

Page 18: ...service access Due to high temperatures the appliance should be locat ed out of traffic and away from furniture and draperies NOTICE Illustrations reflect typical installations and are FOR DESIGN PURP...

Page 19: ...ith a minimum of Figure 5 2 Clearances to Combustibles ST 36TR IPI C Clearances NOTICE Install appliance on hard metal or wood surfaces extending full width and depth DO NOT install directly on carpet...

Page 20: ...hing such as sheetrock PIER 36TR IPI A B C D E F G H I DVP Pipe SLP Pipe Rough Opening Height DVP Pipe Rough Opening Width Clearance to Ceiling Combustible Floor Combustible Flooring Ends of Appliance...

Page 21: ...han the minimums listed must be constructed entirely of noncom bustible materials i e steel studs concrete board etc Figure 5 5 Minimum Vertical and Maximum Horizontal Dimensions of Combustibles Figur...

Page 22: ...Min 2 3 4 in Min 1 2 in Min Unlimited 1 in Max FIREPLACE OPENING Note Clearance from opening to perpendicular wall Figure 5 10 Non Combustible Zone Figure 5 9 Combustible Mantel Leg or Wall Projectio...

Page 23: ...CHES MIN H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING 6 6 Termination Locations Fire Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with insulation or ot...

Page 24: ...A V V H Electrical Service V K V K V L C V N 6 inches non vinyl sidewalls 12 inches vinyl sidewalls O 18 inches non vinyl soffit and overhang 42 inches vinyl soffit and overhang P 8 ft QMIN RMAX 1 cap...

Page 25: ...the time of install the elbow heat shield may be screwed to the exhaust pipe see Figure 6 6 Cut the tabs as shown and bend down Secure the heat shield to the pipe maintaining 3 inch to 4 inch between...

Page 26: ...length of straight pipe is allowed between two 45 elbows see Figure 7 1 Figure 7 1 7 7 Vent Information and Diagrams B Vent Table Key The abbreviations listed in this vent table key are used in the ve...

Page 27: ...grams Top Vent Horizontal Termination Two 45 Elbows Installation requirements to replace the first 90 elbow with two 45 elbows 4 ft min 1 22 m 16 ft max 4 87 m 1 4 in max 6 mm Figure 7 3 Minimum Insta...

Page 28: ...1 2 ft 610 mm 1 ft 305 mm 3 ft 914 mm 2 ft 610 mm 6 ft 1 8 m 3 ft 914 mm 9 ft 2 7 m 4 ft 1 2 m 12 ft 3 7 m 5 ft 1 5 m 15 ft 4 6 m 6 ft 1 8 m 18 ft 5 5 m V1 H1 50 ft 15 2 m Maximum H1 18 ft 5 5 m Maxim...

Page 29: ...ft 305 mm 6 in 152 mm 1 ft 305 mm 6 in 152 mm 1 ft 305 mm 6 in 152 mm 3 ft 914 mm 6 in 152 mm 2 ft 610 mm 1 ft 305 mm 3 ft 914 mm 1 ft 305 mm 6 ft 1 8 m 1 ft 305 mm 6 ft 1 8 m 2 ft 610 mm 12 ft 3 7 m...

Page 30: ...l Termination No Elbow NOTE If installing a vertical vent termination off the top of the appli ance the optional vertical termina tion baffle should be used V1 Figure 7 7 Figure 7 8 Exhaust restrictor...

Page 31: ...4 5 Vertical TOP VENT REAR VENT NG LP NG LP 4 ft 1 1 No Restrictor No Restrictor No Restrictor 8 ft 2 2 1 2 1 1 No Restrictor 15 ft 3 3 3 2 2 2 1 2 20 ft 3 4 3 3 3 3 2 3 25 ft 3 4 3 3 3 3 2 3 30 ft 4...

Page 32: ...t exceed 50 ft 15 2 m Figure 7 11 Two Elbows H1 V2 V1 Three Elbows INSTALLED HORIZONTALLY H1 H2 V2 V1 Figure 7 12 V1 H1 H2 V2 V1 V2 Minimum H1 H2 Maximum ELBOW ONLY 1 ft 305 mm 1 ft 305 mm 1 ft 305 mm...

Page 33: ...IPI PIER 36TR IPI 2176 900 Rev L 4 15 3 Rear Vent Horizontal Termination Figure 7 13 Figure 7 14 No Elbow One 45 Elbow H1 16 in 406 mm Maximum H1 H1 DO NOT use a 45 elbow in corner installations Use t...

Page 34: ...m 7 ft 2 1 m 9 ft 2 7 m 3 ft 914 mm 4 ft 1 2 m 10 ft 3 m 12 ft 3 7 m 3 ft 914 mm 5 ft 1 5 m 12 ft 3 7 m 15 ft 4 6 m 3 ft 914 mm 6 ft 1 8 m 15 ft 4 6 m 18 ft 5 5 m V1 H1 H2 50 ft 15 2 m Maximum H1 3 ft...

Page 35: ...H1 V1 Minimum H1 Maximum 1 ft 305 mm 3 ft 914 mm 2 ft 610 mm 5 ft 1 5 m 3 ft 914 mm 7 ft 2 1 m 4 ft 1 2 m 8 ft 2 4 m 5 ft 1 5 m 8 ft 2 4 m V1 H1 40 ft 12 2 m Maximum V1 Minimum H1 H2 Maximum Back to B...

Page 36: ...o specific restrictions on this value EXCEPT V1 H1 H2 H3 cannot exceed 50 ft 15 2 m Maximum H1 H2 H3 6 ft 1 8 m Maximum H1 Maximum V1 Minimum H2 H1 H2 Maximum 1 ft 305 mm 1 ft 305 mm 1 ft 305 mm 2 ft...

Page 37: ...VP SLP Pipe Shown 3 in 76 mm top clearance 1 in 25 mm clearance bottom sides Heat Shield Wall Shield Firestop Heat Shield WALL 3 in 76 mm top clearance 1 in 25 mm clearance bottom sides Heat Shield Wa...

Page 38: ...may be installed above or below the ceiling joists when installed with a attic insulation shield It must be under joists between floors that are not insulated Refer to Figure 8 4 Secure with three fas...

Page 39: ...Secure the vent gasket to the appliance with two self tapping screws found in the manual bag Note The vent gasket can found in the manual bag Proceed to Section 9 C Figure 9 2 Fold heat shield back a...

Page 40: ...Figure 9 6 Cut the metal retaining band Figure 9 7 Remove the seal cap Figure 9 8 Discard the seal cap insulation plug and the insulation basket Figure 9 9 Attach the first vent section it will snap i...

Page 41: ...ustibles 3 Level the appliance from side to side and front to back It is acceptable to use wood shims under the appliance 4 Fasten the appliance to the floor using the pilot holes located at the botto...

Page 42: ...ther If predrilling holes DO NOT penetrate inner pipe For 90 and 45 elbows that are changing the vent direction from horizontal to vertical one screw minimum should be put in the outer flue at the hor...

Page 43: ...All unit collar pipe slip section elbow and cap outer flues shall be sealed in this manner unless otherwise stated Figure 10 5 Adding Venting Components WARNING Risk of Fire or Explosion DO NOT break...

Page 44: ...very 8 ft 2 44 m after the maximum allowed 25 ft 7 62 m of unsupported rise Vertical runs originating off the rear of the appliance or after any elbow must be supported every 8 ft 2 44 m Horizontal ru...

Page 45: ...rt box on the outside roof Remove shingles or other roof covering as necessary to cut the rectangular hole for the support box Cut the hole 1 8 in 3 mm larger than the support box outline Lower the su...

Page 46: ...OPENING 2 FT MIN 20 INCHES MIN H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING CAULK NOTICE Failure to properly caulk the roof flashing could cause water entry Caulk the gap between the roo...

Page 47: ...at shields must extend through the entire wall thick ness DO NOT remove the heat shields attached to the wall shield firestop and the horizontal termination cap shown in Figure 10 19 Heat shields must...

Page 48: ...RIOR Note When using termination caps with factory supplied heat shield attached no additional wall shield firestop is required on the exterior side of a combustible wall L Install Horizontal Terminat...

Page 49: ...lution DO NOT use open flame Fittings and connections could have loos ened during shipping and handling WARNING Risk of Fire DO NOT change valve settings This valve has been preset at the factory WARN...

Page 50: ...e appliance junction box to supply power to the unit OR install two D cell batteries not included into the battery pack before use NOTICE Batteries should not be placed in the battery pack while using...

Page 51: ...endations Determine Location Determine the location for the wall switch The chosen location should provide an accessible location in the same space as the gas fireplace Never place this unit in a sepa...

Page 52: ...ALVE IPI MODULE BROWN BLACK FAN CONNECTION YELLOW YELLOW FRONT VIEW REAR VIEW RED GREEN YELLOW OR WHITE FAN THERMOSTAT 3V DC BROWN BROWN RED BLACK BATTERIES BLACK RED K C A L B D E R 1 2 3 4 5 6 7 8 M...

Page 53: ...unger blue natural gas red propane into the flame control solenoid Thread the flame control solenoid with correct plunger into the thread hole in the variable regulator Turn into valve approximately t...

Page 54: ...ton Press Fan High 3 Button Press Fan Medium 2 Button Press Fan Low 1 Button Press Fan Off Temperature Button Button Press will toggle between Automatic and Manual Operation Press and Hold the button...

Page 55: ...ion capability of the wall switch flip switch to OFF position after 120 VAC power is restored Set Temperature Button Button Press Displays Set Point Use UP and Down Arrows to adjust set point Press Se...

Page 56: ...2 Folding Top Flap Step 3 Crease flaps on left and right sides of splatter guard using the scored line as the guide See Figure 13 2 Step 4 Center the splatter guard in front of the unit as shown in F...

Page 57: ...and right bottom of splatter guard and fit them into the square holes The tabs are now inside the front of the splatter guard carefully bend them down See Figure 13 9 To Close the Lower Access Panel...

Page 58: ...teel studs concrete board etc Failure to comply could cause fire Figure 13 12 Minimum Vertical and Maximum Horizontal Dimensions of Combustibles Figure 13 13 Minimum Vertical and Maximum Horizontal Di...

Page 59: ...Facing and or finishing materials must never overhang into the glass opening Observe all clearances when applying combustible materials Seal joints between the finished wall and appliance top and side...

Page 60: ...ative front models and the finishing material thickness allowed For an inside fit there is an available template to assist with sizing the finishing material Stop finishing material flush with opening...

Page 61: ...61 Heat Glo ST 36TR IPI PIER 36TR IPI 2176 900 Rev L 4 15 Figure 13 22 Pier Decorative front Finishing 33 5 8 in 37 1 4 in FINISHING MATERIAL...

Page 62: ...VATED APPLIANCE DIMENSION See Note 1 MARBLE LEG CUT LENGTH See Note 2 KENWOOD MANTEL AFKDMPB 0 See Note 3 27 3 8 in KENWOOD MANTEL W BASE AFKDMPB W HTKDMPB 9 1 4 in 29 3 8 in LAURENT SURROUND LAURENT...

Page 63: ...arranty 14 14 Appliance Setup E Lava Rock Teco Sil and Glowing Ember Placement Prepare Electric Ember Bed and Lava Rock The elec tric ember bed must be prepared before the logs are set up See Figure 1...

Page 64: ...uld be taken not to cover the lighting trail of ports from back to front When placing Glowing Embers onto the burner care should be taken so that the ports are not covered Place the dime size ember pi...

Page 65: ...ine as shown above Position the thin end of log 1 one inch from port pattern as shown STEP 3 LOG 2 SRV2005 700 Position log 2 on the left grate bar and the pilot assembly Use the cut out notches on th...

Page 66: ...tine as shown The smooth cutout on the bottom of log 4 should rest on the burner surface The side of Log 4 must be 3 4 inch from the nearest port hole on the right side of log 4 DO NOT cover any port...

Page 67: ...t the front right grate tine Set the other end of the log so it rests on the flat area of log 1 The orientation of log 6 in relation to the grate tine is shown below 6 6 5 5 4 4 3 3 2 2 1 1 1 2 4 4 5...

Page 68: ...cracks chips or scratches DO NOT strike slam or scratch glass DO NOT operate fireplace with glass removed cracked broken or scratched Replace as a complete assembly Air Shutter Settings H Install Trim...

Page 69: ...shorted sparker wire or cracked insulator around electrode Replace pilot if necessary 2 Pilot won t light there is no noise or spark a No power or transformer installed incorrectly Verify that transf...

Page 70: ...lot orifice is installed and gas inlet is set to pres sure specifications Polish flame sensing rod with fine steel wool to remove any contaminants that may have accumu lated on flame sensing rod c Mod...

Page 71: ...ons and clearances refer to Section 5 Figure 16 1 See Through Dimensions B C FRONT VIEW RIGHT VIEW ELECTRICAL ACCESS GAS LINE ACCESS LEFT VIEW A P J K L K D F G H M O i N E Location Inches Millimeters...

Page 72: ...VIEW LEFT VIEW A P L K D M O N E ELECTRICAL ACCESS GAS LINE ACCESS J K F G H i Location Inches Millimeters I 1 1 2 38 J 27 686 K 8 203 L 12 305 M 9 1 2 241 N 38 965 O 34 5 8 880 P 24 610 Location Inc...

Page 73: ...n 356 mm 1 in 25 mm 8 in 203 mm 6 in 152 mm 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm UP DVP HVS Vent Support DVP WS Wall Shield Firestop DVP FS Ceiling Firestop DVP45 45 Elbow DVP Pipe see...

Page 74: ...mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness...

Page 75: ...ick Extension 13 3 4 in 349 mm 5 in 127 mm 13 3 4 in 349 mm Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12...

Page 76: ...in 41 mm 16 7 8 in 429 mm DVP HPC High Performance Cap 1 in 25 mm 14 in 356 mm 3 8 in 10 mm 1 in 25 mm 7 1 4 in 184 mm 7 3 4 to 10 3 8 in 197 to 264 mm DVP FBHT FireBrickTermination Cap PVK 80 For use...

Page 77: ...VI WH80 100 ft PV Wire Harness PVI WH100 PVI SLP Power Vent Inline Note Wire harnesses required to power the PVI SLP connect to the appliance and are ordered separately from PVI SLP Contact your deale...

Page 78: ...36 914 SLP FLEX 5 60 1524 SLP FLEX 10 120 3048 8 3 4 in 222 mm 6 1 2 in 165 mm 6 5 8 in 168 mm 6 in 152 mm 6 1 2 in 165 mm 6 5 8 in 168 mm 9 7 8 in 251 mm 6 1 2 in 165 mm 9 1 4 in 235 mm SLP45 45 Elbo...

Page 79: ...uired Heat Shield Term Cap Minimum Effective Length Maximum Effective Length Trap1 3 1 8 in 4 3 4 in 79 mm 121mm Trap2 5 1 4 in 9 1 4 in 133 mm 235 mm 8 in 203 mm 12 in 305 mm Max Effective Length 14...

Page 80: ...318 mm 12 in 305 mm SLP FLEX TRAP Horizontal Termination Kit 14 in 356 mm 14 1 16 in 357 mm 7 1 2 in 192 mm 10 3 4 in 273 mm SLP CCS BK Cathedral Ceiling Support Box Black SLP DCF BK Ceiling Firestop...

Page 81: ...dealer to order Note The PVLP SLP requires a PVLP CK be installed on this appliance The PVLP CK is ordered separately from the PVLP SLP Contact your dealer to order Figure 16 11 PVLP SLP Vent Componen...

Page 82: ...SRV2005 701 2 Log 2 SRV2005 700 3 Log 3 SRV2005 702 4 Log 4 SRV2005 703 5 Log 5 SRV2005 704 6 Log 6 SRV2005 705 7 Non Comb Qty 2 req 2130 196 8 Sheetrock Ledge Side Qty 2 req 2128 118 9 Glass Door Ass...

Page 83: ...005 700 3 Log 3 SRV2005 702 4 Log 4 SRV2005 703 5 Log 5 SRV2005 704 6 Log 6 SRV2005 705 7 Non Comb Long Qty 2 req 2130 199 8 Sheetrock Ledge Side Qty 2 req 2130 118 9 Glass Door Assembly Qty 2 req GLA...

Page 84: ...y LP 2090 013 Y 17 4 Pilot Bracket 2176 118 17 5 Ember Box Assembly 2005 114 Y 17 6 Ori ce NG 32C 582 832 Y Ori ce LP 50C 582 850 Y 17 7 Valve Bracket 2176 120 17 8 Flex Ball Valve Assembly 302 320A Y...

Page 85: ...RIPTION COMMENTS PART NUMBER Gasket Assembly 2128 081 Contains Vent Seal Cap Burner Neck Shutter Bracket and Valve Plate Gaskets Lava Rock 2005 790 Mineral Wool 050 721 Multifunction Remote WSK MLT Ac...

Page 86: ...___________________________________ ________________________________________________________________________________ ________________________________________________________________________________ __...

Reviews: