22
Heat & Glo • 6000TRSI-AUC • 2078-900 Rev. Q • 6/10
Figure 1.34
Figure 1.33
F. Mantel Clearances
Clearance to a mantelpiece is 12 inches (305 mm).
See Figure 1.33.
Note: all dimensions are shown in millimeters
.
IF JOINTS BETWEEN THE FINISHED WALLS
AND THE HEATER SURROUND (TOP AND SIDES)
ARE SEALED, A 150º C. MINIMUM SEALANT
MATERIAL MUST BE USED. THESE JOINTS
ARE NOT REQUIRED TO BE SEALED. ONLY
NON-COMBUSTIBLE MATERIAL (USING 150°
C. MINIMUM ADHESIVE, IF NEEDED) CAN BE
APPLIED AS FACING TO THE HEATER SURROUND.
SEE Figure 1.34.
FINISH WALL MATERIAL MAY BE
COMBUSTIBLE - TOP AND SIDES
NON-COMBUSTIBLE
BOARD
HIGH TEMPERATURE (150 ºC MIN.)
TOP AND SIDE SEAL JOINT
89
127
152
178
203
254
279
51
76
102
127
305
279
254
229
203
178
152
38
25
76
102
114
229
TOP FRONT EDGE
OF FIREPLACE
NON-COMBUSTIBLE
BOARD
NOTE:
Zero clearance fi nishing allowed on sides
of surround and top of non-combustible
board.