15
06/21
8390-016A
9: Flame stabilization mode begins. Appliance will feed
at .8 second “on time” for 3 minutes.
Operation Flow Chart
7: Exhaust probe senses a 6 degree increase per minute
for 2 consecutive minutes.
8: Igniter turns off.
10: Convection blower turns on and increases speed as
the appliance heats up.
The exhaust probe will
sense 140 degrees and
turn on the convection
blower at a low speed.
11: Green blink on the dial
control will change its
blinks to show the current
power level. Power level
will vary depending on
room temp vs set temp
on the dial.
These times are at trim 0: (7 Second Cycle)
PP60/PP60-B
PP130
PP70
PP130-B
Power Level 1:
0.9 sec “on time” 0.9 sec “on time” 0.8 sec “on time” 1.0 sec “on time”
Power Level 2:
1.3 sec “on time” 1.5 sec “on time” 1.1 sec “on time” 1.2 sec “on time”
Power Level 3:
1.6 sec “on time” 2.0 sec “on time” 1.4 sec “on time” 1.6 sec “on time”
Power Level 4:
2.0 sec “on time” 2.5 sec “on time” 1.7 sec “on time” 2.1 sec “on time”
Power Level 5:
2.4 sec “on time” 3.1 sec “on time” 2.0 sec “on time” 2.6 sec “on time”
12: Set temperature is met.