Hearth & Home Technologies  •  IFT-RC400 & IFT-ACM Installation Instructions  •  2326-982 Rev. Q  •  4/21

18

Symptom

Possible Cause

Corrective Action

Pilot sparks but does not light, after  

90 sec, 3 Red/1 Green Lockout.

No gas supply.

Verify incoming gas line ball valve is ‘Open’.  Verify inlet pres

-

sure is within requirement for gas type used.  Contact gas sup-
plier.

ECM has poor ground.

Verify  wiring,  check  valve  harness  black  wire  is  securely 

grounded to metal chassis.

Gas valve defective.

Check pilot valve solenoid kick and hold voltages during igni-

tion cycle.  Kick V should be >1 V, hold V minimum 0.26 V.  If 

voltages are OK, replace gas valve.

Pilot lights but main burner does 
not light.   Pilot continues to spark 

for 90 sec then goes into 3 Red/1 

Green Lockout.

No flame detected. Flame 

rectification issue.

Check if white sense lead is securely connected to ‘S’ terminal 
of 

IFT-

ECM.  Check resistance of sense lead between sense 

rod tip and connector to 

IFT-

ECM, should be less than 1 ohm 

- if not, replace pilot assembly.  Check system ground, ensure 

black valve harness wire is securely attached to metal chassis.  

Check wiring for damage.  With system OFF, check resistance 

between tip of sense rod and pilot hood, should be resistance 

(>1 M-ohm). 

No flame detected or sense 

rod contamination. 

With  glass  assembly  installed,  verify  pilot  flame  is  engulfing 

flame sense rod on pilot assembly.  Verify inlet gas pressure 

is correct for gas type.  Polish flame sense rod with fine steel 

wool to remove any contaminants that may have accumulated.

Pilot lights and rectifies, but main 

burner does not light.

Main valve solenoid.

Check if green wire in valve harness is connected to green 

main valve solenoid.  Check main valve solenoid resistance, 

nominal is 60 ohms.  If open or shorted, replace valve.  Verify 

valve inlet pressure is correct for gas type.

Pilot and main do not light, ECM 

goes into 5 Red/1 Green Lockout.

Power Vent (PV) Failure.

Power Vent blower defective - check wiring to 

IFT-

ACM, check 

if blower is working.  Check if PV pressure switch is connected 
to brown and black wire in 6-pin valve wire harness.  Check if 
pressure switch is closed (shorted) when PV blower is running.  
Refer to PV troubleshooting instructions. 

Appliance lights and runs for a few 

minutes then shuts down and/or 

appliance cycle ON and OFF with 

less than 90 sec of ON time. 

Shorted or loose connection in 

flame detection circuit.

Check if white sense lead is securely connected to ‘S’ terminal 
of 

IFT-

ECM.  Check resistance of sense lead between sense 

rod tip and connector to 

IFT-

ECM, should be less than 1 ohm 

- if not, replace pilot assembly.  Check system ground, ensure 

black valve harness wire is securely attached to metal chassis.  

Check wiring for damage.  With system OFF, check resistance 

between tip of sense rod and pilot hood, should be resistance 

(>1 M-ohm). 

Poor flame rectification or 

contaminated sense rod. 

With  glass  assembly  installed,  verify  pilot  flame  is  engulfing 

flame sense rod on pilot assembly.  Verify inlet gas pressure 

is correct for gas type.  Polish flame sense rod with fine steel 

wool to remove any contaminants that may have accumulated.  
Verify no soot deposits are in sense rod to pilot hood gap.

Logs are set up wrong. 

Remove and re-install logs per the log placement instructions.

Damaged pilot assembly.

Verify  the  pilot  assembly  ceramic  insulator  around  the  flame 

sensing  rod  is  not  cracked,  damaged  or  loose.    Check  re

-

sistance between tip of sense rod and 

IFT-

ECM  connector, 

should be less than 1 ohm.  Replace pilot assembly if damage 
is detected.

Troubleshooting 

(continued)

Summary of Contents for IntelliFire Touch IFT-ACM

Page 1: ...nce Hearth Home Technologies disclaims any responsibility for and the warranty will be voided by the following actions Installation and use of any damaged system component Modification of the system component Installation other than as instructed by Hearth Home Technologies Installation and or use of any component part not approved by Hearth Home Technologies Any such action may cause a fire hazar...

Page 2: ...as supplied in your power vent kit into the three male pins on the IFT ACM See Figure 4 6 Connect the IFT ACM to the IFT ECM by aligning the pins and tabs and pushing the IFT ACM onto the IFT ECM until both tabs latch in place Ensure the IFT ECM and IFT ACM are aligned with each other and fastened securely See Figure 3 Figure 3 Connecting IFT ACM and IFT ECM WARNING Risk of Shock DO NOT touch male...

Page 3: ...the junction box has power See Figure 4 9 Move the three position switch on the IFT ECM to the REMOTE position The green LED will blink three times A few seconds later an audible beep will oc cur to indicate that the system is ready 10 Set the RC400 face down on flat surface when install ing batteries DO NOT touch the screen during bat tery installation or removal 11 Remove the battery cover from ...

Page 4: ...audible beep will be heard from the IFT ECM 3 If the pairing is unsuccessful repeat steps 1 2 Note If additional components are added such as blowers lights or Power Vent after initial pairing the pairing process must be repeated again to detect additional components NOTICE Only one IFT RC400 remote control and one IFT RC150 wireless wall switch can be programmed into an IFT ECM To program both an...

Page 5: ...ure 8 Figure 8 Pairing Remote If the Now pairing remote to product icon occurs 1 Verify that all the wire connections are complete and verify that the ACM is powered by 120V 2 On the IFT ECM move the ON OFF REMOTE switch to the REMOTE position The green LED will blink three times A few seconds later an audible beep will occur to indicate that the system is ready 3 Remove the battery cover and inst...

Page 6: ...he filled circles For best results use a stylus You will be prompted to repeat this clockwise around the four corners of the screen Figure 12 Touch and Release 5 After touching and releasing this last point the following screen appears Figure 13 Touch and Release 6 Touch screen anywhere to return IFT RC400 to normal screen display Figure 14 Touch anywhere on the Screen 3 With RC400 software versio...

Page 7: ...ERY PACK BLK RED BRN ORANGE PILOT GREEN MAIN IFT RC400 REMOTE CONTROL GRN WHT BLK RED BLK RED BLK BLK RED IFT RC150 WIRELESS WALL SWITCH OPTIONAL OPTIONAL OPTIONAL APPLIANCE ON OFF CONTROL BRN BLK WIRE ASSEMBLY MODULE RESET SWITCH OPTIONAL ON SOME MODELS ONLY SPLITTER BLK RED I Wiring Diagram IntelliFire Touch System Wiring Diagram without Power Vent Figure 15 IFT RC400 Wiring Diagram without Powe...

Page 8: ...PTER I S 6 PIN RED BLK ORANGE PILOT GREEN MAIN GRN WHT BLK RED BLK RED BLK OPTIONAL OPTIONAL IFT RC400 REMOTE CONTROL RED BLK BRN BRN JUMPER WIRE BRN WIRE ASSEMBLY MODULE RESET SWITCH OPTIONAL ON SOME MODELS ONLY ACCESSORY CABLE POWER VENT OPTIONAL I Wiring Diagram continued IntelliFire Touch System Wiring Diagram with Power Vent Figure 16 IFT RC400 Wiring Diagram with Power Vent ...

Page 9: ... row keys and press ON to confirm the setting The actual room temperature RT measured by your IFT RC400 remote will be displayed in the upper right corner of the main menu screen To turn the thermostat function off simply select thermostat on the main menu screen and select OFF If the RT cools to more than 2 F lower than the ST for at least 2 minutes then your appliance will automatically turn ON ...

Page 10: ...mer will turn the flame off automatically at the selected preset time To use the timer function press Timer on the main screen select time by using up and down arrows then press ON To turn the timer off select timer from main screen and select OFF Child Lock Diagnostics Menu Tap anywhere in the gray indicator bar area to display all functions below When red it indicates an error has been detected ...

Page 11: ...ower source in the event of a power outage Batteries should not be used as a primary long term power source Note Battery backup is not available if a Power Vent is installed Your remote control is not able to communicate with your appliance Verify that you have power to your appliance If there is a power outage verify that appliance battery backup is fitted with new batteries After taking these ac...

Page 12: ...s and hold a paperclip type object in the P button hole for at least 10 seconds 3 Double beep from the remote will indicate that the remote will reset the 300 hour maintenance reminder If the remote 300 hour maintenance message does not clear on the first try repeat above steps To reset the 300 hour maintenance reminder if the RC400 displays the following message 1 Wake up your remote control disp...

Page 13: ...n front of it The remote acts as the thermostat mode room temperature sensor IFT RC400 is placed in the path of an air draft or vent Move the IFT RC400 away from the direct path of air flow The remote acts as the thermostat room temperature sensor Flame Modulation The IFT system is designed to automatically adjust the flame intensity based on the difference between the desired room temperature and...

Page 14: ...flame modulation will result in more control of the tem perature but will cause the appliance to cycle OFF ON less The appliance turns OFF the flame after extended periods of operation 9 hour safety shutdown timer This is normal behavior The appliance has a safety timer that will automatically turn OFF the flame after nine hours of unin terrupted operation IFT RC400 does not pair or unpair from th...

Page 15: ... previous symptom Fan is not plugged into IFT ACM Check wiring and connections Spade connectors are miswired Some Fans may be connected to the IFT ACM using spade con nectors For safety turn off the power to the appliance and check to see if the wires on either end of the spade connector do not match in color as they might be miswired IFT RC400 display the following message on screen Call Dealer E...

Page 16: ...l switch is NOT available if a Power Vent is used 3 The Pilot button on the IFT ECM activates the Cold Climate function of the fireplace This function lights the pilot flame ONLY to provide enough heat in the firebox to reduce condensation in cool high humidity ambient conditions To activate the Cold Climate IFT ECM Detailed Operating Instruction CAUTION Risk of burns Appliance surfaces are hot wh...

Page 17: ...n OFF position Verify IFT ECM slider switch is in ON or IFT REM position Verify AC power available to junction box Verify AC DC adap tor is plugged into junction box and ECM Verify AC DC adaptor output voltage is between 5 7 6 3 Vdc If battery pack is used check battery pack voltage is 4 2 V if not replace batteries Shorted or loose connection in system wiring or wiring harness Verify system wirin...

Page 18: ...noid Check main valve solenoid resistance nominal is 60 ohms If open or shorted replace valve Verify valve inlet pressure is correct for gas type Pilot and main do not light ECM goes into 5 Red 1 Green Lockout Power Vent PV Failure Power Vent blower defective check wiring to IFT ACM check if blower is working Check if PV pressure switch is connected to brown and black wire in 6 pin valve wire harn...

Page 19: ...ever there is no guarantee that in terference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation b...