VI. Electrical Wiring Instructions
Note:
The HealthyAir
®
Ceiling Mount Source Capture
®
Air Purification system
must be hard wired when recess mounted. All wiring must comply with
applicable electrical codes and ordinances.
6.1 Hard Wire
120V AC, 60 Hz
6.1.1 Install an external circuit breaker sized for a Maximum 2.5 AMP to bring
power to the unit.
6.1.2 Run three (3) No. 14 Color-Coded Wires through the conduit to the
Wiring Box of the unit, as shown in Fig. 27.
6.1.3 Attach the Green wire to the external Ground. Note that, the Black wire
and White wire are the power carries.
6.1.4 Attach the conduit to the knockout.
6.1.5 Attach the Green ground wire to the ground screw and to the terminal
marked G in the Wiring Box. Ground the unit for proper operation and
safety.
6.1.6 Attach the Black wire to the terminal marked L and the White wire to the
terminal marked N in the Wiring Box, as shown in Fig. 27.
Fig. (27)
– Electrical Wiring Diagram