6. Select valve type
Valve-specific settings, such as minimum current, maximum current, dither amplitude and dither frequency are crucial for ensuring
that operation is as accurate as possible.
Basic settings have been pre-defined for the common valves.
Display
Valve type
Minimum current
Maximum current
Dither amplitude
Dither frequency
(P-)
No selection, invalid input
(P1)
General information
0.0 A (12 VDC)
0.0 A (24 VDC)
1.0A (12 VDC)
0.5A (24 VDC)
50%
100 Hz, PWM
(P2)
PSL 2
0.34A (12 VDC)
0.17A (24 VDC)
1.16A (12 VDC)
0.58A (24 VDC)
50%
100 Hz, PWM
(P3)
PSL 3 & 5
0.37A (12 VDC)
0.18A (24 VDC)
1.26A (12 VDC)
0.63A (24 VDC)
50%
100 Hz, PWM
(P4)
EDL
0.46A (12 VDC)
0.23A (24 VDC)
1.56A (12 VDC)
0.78A (24 VDC)
50%
100 Hz, PWM
(P5)
EMP to V
0.4A (12 VDC)
0.2A (24 VDC)
1.6A (12 VDC)
0.8A (24 VDC)
50%
100 Hz, PWM
(P6)
NA
(P7)
NA
(P8)
NA
(P9)
NA
Operating mode using the
UP
and
DOWN
buttons
Confirm the selected operating mode with
OK
→
The display shows the setting for the first selection point "operating mode"
7.
Press the
OK
button to check the selected settings again
8.
Press the
UP
and
DOWN
buttons simultaneously for 2 seconds to save the settings
9.
Set the input signal and test the function