HAUBER-Elektronik GmbH
16
13.3
Limit values and delay times
SET
Position
Limit values (mm/s)
Measuring
range
0
– 8
mm/s
0
– 10
mm/s
0
– 16
mm/s
0
– 20
mm/s
0
– 25
mm/s
0
– 32
mm/s
0
– 50
mm/s
0
– 64
mm/s
0
– 128
mm/s
0
0.0
0
0
0
0
0
0.00
0
0
1
0.5
0.625
1
1.25
1.563
2
3.13
4
8
2
1.0
1.25
2
2.5
3.125
4
6.25
8
16
3
1.5
1.875
3
3.75
4.688
6
9.38
12
24
4
2.0
2.5
4
5
6.25
8
12.50
16
32
5
2.5
3.125
5
6.25
7.813
10
15.63
20
40
6
3.0
3.75
6
7.5
9.375
12
18.75
24
48
7
3.5
4.375
7
8.75
10.938
14
21.88
28
56
8
4.0
5
8
10
12.5
16
25.00
32
64
9
4.5
5.625
9
11.25
14.063
18
28.13
36
72
10
5.0
6.25
10
12.5
15.625
20
31.25
40
80
11
5.5
6.875
11
13.75
17.188
22
34.38
44
88
12
6.0
7.5
12
15
18.75
24
37.50
48
96
13
6.5
8.125
13
16.25
20.313
26
40.63
52
104
14
7.0
8.75
14
17.5
21.875
28
43.75
56
112
15
7.5
9.375
15
18.75
23.438
30
46.88
60
120
Tab. 7: Limit values
The
SET rotary button
has 16 positions, representing the limit value of an alarm. The
measuring range of the vibration monitoring unit is divided into 16 linear steps.
In general:
𝑇ℎ𝑟𝑒𝑠ℎ𝑜𝑙𝑑 𝑣𝑎𝑙𝑢𝑒 =
𝑡𝑜𝑝 𝑙𝑖𝑚𝑖𝑡 𝑜𝑓 𝑚𝑒𝑎𝑠𝑢𝑟𝑖𝑛𝑔 𝑟𝑎𝑛𝑔𝑒
16
× 𝑆𝐸𝑇 𝑃𝑜𝑠𝑖𝑡𝑖𝑜𝑛
Example:
Limit setting
Measuring range:
0-32 mm/s
SET rotary button Pos.: 8 (9)
Limit value:
16 mm/s (18 mm/s)
Delay times
TIME Position
0
1
2
3
4
5
6
7
8
9
10
11 12 13 14 15
Delay time
(secs)
0
1
2
3
4
5 7.5 10 12.5 15 17.5 20 25 30 45 60
Tab. 8: Delay times