Functional safety instructions
10.1
Safety level / key indicators
The HE250 vibration monitoring hardware was tested by TÜV Süd. The results meet the criteria
according to SIL2 and Pl-d.
Safety marking placeholder1
….
Safety marking placeholder2
….
10.2
General notes
A reboot of the vibration monitoring unit must be performed annually in order to
test the relay switching.
10.3
Instructions for the Fail Safe State
When the power supply is switched on, the vibration monitoring unit will perform a self-test.
During operation, self-tests are performed automatically in cycles. If a self-test fails, the vibration
monitoring unit switches to the Fail Safe State.
In the Fail Safe State all status LEDs are lit, all relays are open and the analogue current output
supplies 0 mA.