background image

Form No. 3CSFRM-0118

7

English

Model

Voltage

Kilowatts

(kW)

Phase

Amps

Wiring Sizing

AWG*†

Fuse or 

Circuit

Breaker*

Shipping

Weight

3CS-3B

208

3.0

3 (Bal.)

8.3

14

15

30 lbs. (14 kg)

240

3.0

3 (Bal.)

7.2

14

15

30 lbs. (14 kg)

480

3.0

3 (Bal.)

3.6

14

15

30 lbs. (14 kg)

380–400–415 2.8–3.1–3.4

3 (Bal.)

4.3–4.5–4.7

14

15

30 lbs. (14 kg)

3CS-4B

208

4.5

3 (Bal.)

12.5

12

20

30 lbs. (14 kg)

240

4.5

3 (Bal.)

10.8

14

15

30 lbs. (14 kg)

480

4.5

3 (Bal.)

5.4

14

15

30 lbs. (14 kg)

380–400–415 3.8–4.1–4.5

3 (Bal.)

5.7–6–6.2

14

15

3CS-6B

208

6.0

3 (Bal.)

18.8

10

30

30 lbs. (14 kg)

240

6.0

3 (Bal.)

14.4

12

20

30 lbs. (14 kg)

480

6.0

3 (Bal.)

7.2

14

15

30 lbs. (14 kg)

380–400–415 5.6–6.3–6.7

3 (Bal.)

8.6–9–9.4

14

15

30 lbs. (14 kg)

3CS-9B

208

9.0

3 (Bal.)

25

10

40

30 lbs. (14 kg)

240

9.0

3 (Bal.)

21.7

10

30

30 lbs. (14 kg)

440

9.0

3 (Bal.)

11.8

14

15

30 lbs. (14 kg)

480

9.0

3 (Bal.)

10.8

14

15

30 lbs. (14 kg)

380–400–415 7.5–8.3–9.0

3 (Bal.) 11.4–11.9–12.5

12

20

30 lbs. (14 kg)

SPECIFICATIONS

Electrical Rating Chart—3CS-XB Models

 The shaded areas contain electrical information for 

International models only

.

*

  Wire size is based on THHN wire for branch circuit protection at 0.91 derate factor. Circuit breakers and fused disconnects 

are to be mounted remote and wired by contractor. Sizes are based on the 2002 NEC table 310-16. Conduit size based on 

conductors plus ground wire sizing per Table C1 from Appendix C.

 Based upon THHN wire rated 90ºC.

♦ Open Delta–standard construction (Amperage higher than Balanced 3-phase)

NOTE: Shipping Weight includes packaging.

Summary of Contents for FR-3

Page 1: ...erning the maintenance use and operation of this product If you re unable to understand the contents of this manual please bring it to the attention of your supervisor Keep this manual in a safe locat...

Page 2: ...ne 800 558 0607 414 671 6350 E mail support hatcocorp com 24 Hour 7 Day Parts and Service Assistance available in the United States and Canada by calling 800 558 0607 Additional information can be fou...

Page 3: ...ment to hazardous electrical voltage resulting in electrical shock or burn Genuine Hatco Replacement Parts are specified to operate safely in the environments in which they are used Some aftermarket o...

Page 4: ...ing The requirements mirror the requirements for food rethermalizing in the FDA Food Code The basic requirement is that food reach a temperature of 165 F 74 C in a time period of two hours or less App...

Page 5: ...3 heater The Corn Cooker is completely assembled and comes equipped with an electrical power cord and plug The unit may include a stand or as a vessel inserted into a countertop POWER ON LOW WATER REF...

Page 6: ...16 2 12 20 27 lbs 12 kg 208 6 0 3 25 8 40 27 lbs 12 kg 240 6 0 3 21 7 10 30 27 lbs 12 kg 380 400 415 5 6 6 3 6 7 3 12 9 13 5 14 12 20 27 lbs 12 kg 415 6 0 3 14 12 20 27 lbs 12 kg 480 6 0 3 10 8 14 15...

Page 7: ...9 9 4 14 15 30 lbs 14 kg 3CS 9B 208 9 0 3 Bal 25 10 40 30 lbs 14 kg 240 9 0 3 Bal 21 7 10 30 30 lbs 14 kg 440 9 0 3 Bal 11 8 14 15 30 lbs 14 kg 480 9 0 3 Bal 10 8 14 15 30 lbs 14 kg 380 400 415 7 5 8...

Page 8: ...lbs 11 kg 380 400 415 3 8 4 2 4 5 3 8 6 9 0 9 4 14 15 24 lbs 11 kg 415 4 5 3 9 4 14 15 24 lbs 11 kg 480 4 5 3 5 4 14 15 24 lbs 11 kg FR 6 208 6 0 1 28 8 8 40 27 lbs 12 kg 240 6 0 1 25 8 40 27 lbs 12 k...

Page 9: ...kg 480 9 0 3 Bal 10 8 14 15 30 lbs 14 kg 380 400 415 7 6 8 3 9 0 3 Bal 11 5 11 9 12 5 12 20 30 lbs 14 kg Model Voltage Kilowatts kW Phase Amps Wiring Sizing AWG Fuse or Circuit Breaker Shipping Weight...

Page 10: ...R X 16 7 8 429 mm 5 1 2 140 mm 8 1 2 216 mm 2 7 8 73 mm 6 3 4 171 mm 3 3 8 86 mm 3CS XB and FR XB 17 1 8 435 mm 4 5 8 117 mm 8 1 2 216 mm 4 102 mm 8 203 mm 4 102 mm SPECIFICATIONS Dimensions A B C D E...

Page 11: ...mine and install proper electrical connection Units supplied with an electrical cord plug and receptacle require installation of receptacle to on site electrical system Connection must be properly gro...

Page 12: ...Bottom Two Thick Rubber Washers Fiber Washer Locknut Union Washer Union Nut Installing the Drain Spud Assembly 5 Unscrew the drain spud assembly from the welded pipe on the heater 6 Unscrew the lockn...

Page 13: ...priate Electrical Rating Chart for wiring and voltage requirements WARNING Turn OFF power switch disconnect unit from power source and allow unit to cool before performing any cleaning adjustments or...

Page 14: ...90 F 88 C DO NOT set temperature controls to a setting higher than 190 F 88 C Water over 190 F 88 C is very active and could splash onto operator causing serious burns or injury Do not add cold food f...

Page 15: ...not supplied in place and free of debris FR units only Delime unit using a non corrosive deliming solution Daily Cleaning Use the following procedure to clean the unit The unit should be cleaned daily...

Page 16: ...he front and rear openings with fresh water for several minutes until discharge is clear 9 Re install drain cap and close sump drain 10 Upon visual inspection if tank is not thoroughly clean repeat st...

Page 17: ...ord may be unplugged Check for proper fuse sizing and replace fuses check reset circuit breaker and or check replace power cord TROUBLESHOOTING GUIDE WARNING This unit must be serviced by trained and...

Page 18: ...R PURPOSE OR PATENT OR OTHER INTELLECTUAL PROPERTY RIGHT INFRINGEMENT Without limiting the generality of the foregoing SUCH WARRANTIES DO NOT COVER Coated incandescent light bulbs fluorescent lights h...

Page 19: ...assistance et de pi ces de rechange disponible 7j 7 24h 24 aux tats Unis et au Canada en composant le 800 558 0607 Des renseignements suppl mentaires sont disponibles sur notre site Web www hatcocorp...

Page 20: ...acit s physiques sensorielles ou mentales diminu es Assurez vous que les enfants sont bien surveill s et tenez les l cart de l appareil AVERTISSEMENT DANGER D INCENDIE Installez l appareil avec un min...

Page 21: ...de d bris trop importante peut affecter la performance et r duire la dur e de vie de l appareil Une panne de l appareil caus e par une accumulation de calcaire ou de s diments n est pas couverte par l...

Page 22: ...II Hatco utilisent des r chauffeurs FR 3 Hatco Le cuiseur de ma s est enti rement assembl et est quip d un cordon et d une prise lectrique L appareil peut tre quip d un support ou d une cuve ins r e...

Page 23: ...6 7 3 12 9 13 5 14 12 20 12 kg 27 lbs 415 6 0 3 14 12 20 12 kg 27 lbs 480 6 0 3 10 8 14 15 12 kg 27 lbs 3CS 9 208 9 0 1 43 3 4 60 12 kg 27 lbs 240 9 0 1 37 5 6 50 12 kg 27 lbs 480 9 0 1 18 8 10 30 12...

Page 24: ...lbs 440 9 0 3 Bal 11 8 14 15 14 kg 30 lbs 480 9 0 3 Bal 10 8 14 15 14 kg 30 lbs 380 400 415 7 5 8 3 9 0 3 Bal 11 4 11 9 12 5 12 20 14 kg 30 lbs Tableau des Caract ristiques lectriques Mod les 3CS XB...

Page 25: ...s 380 400 415 3 8 4 2 4 5 3 8 6 9 0 9 4 14 15 11 kg 24 lbs 415 4 5 3 9 4 14 15 11 kg 24 lbs 480 4 5 3 5 4 14 15 11 kg 24 lbs FR 6 208 6 0 1 28 8 8 40 12 kg 27 lbs 240 6 0 1 25 8 40 12 kg 27 lbs 480 6...

Page 26: ...al 8 6 9 9 4 14 15 14 kg 30 lbs 480 6 0 3 Bal 7 2 14 15 14 kg 30 lbs FR 9B 208 9 0 3 Bal 25 10 40 14 kg 30 lbs 240 9 0 3 Bal 21 7 10 30 14 kg 30 lbs 380 9 0 3 Bal 12 9 12 20 14 kg 30 lbs 440 9 0 3 Bal...

Page 27: ...6 7 8 140 mm 5 1 2 216 mm 8 1 2 73 mm 2 7 8 171 mm 6 3 4 86 mm 3 3 8 3CS XB et FR XB 435 mm 17 1 8 117 mm 4 5 8 216 mm 8 1 2 102 mm 4 203 mm 8 102 mm 4 Dimensions Mod les 3CS et FR A B C D E 73 mm 2 7...

Page 28: ...Le c blage doit tre mis la terre de mani re appropri e Son voltage ses dimensions et sa configuration doivent galement correspondre aux sp cifications lectriques de l appareil Contactez un lectricien...

Page 29: ...xception de la rondelle de caoutchouc mince Rondelle de caoutchouc mince Raccord d vacuation Partie inf rieure du bac r cipient 2 rondelles de caoutchouc mince Rondelle en fibre Contre crou Rondelle d...

Page 30: ...ur conna tre l alimentation lectrique appropri e Tous les raccordements lectriques internes ont t effectu s en usine Veuillez consulter le Tableau de classification des tensions lectriques appropri po...

Page 31: ...essages de s curit de la section Consignes de s curit importantes avant d utiliser ce mat riel ATTENTION DANGER DE BR LURE L eau contenue dans le r cipient peut atteindre des temp ratures sup rieures...

Page 32: ...ie et assurez vous qu elle ne contient aucun r sidu appareils FR uniquement D tartrez l appareil l aide d une solution de d tartrage non corrosive Nettoyage Quotidien Suivez la proc dure ci apr s pour...

Page 33: ...non toxique et non corrosive Suivez les instructions de d tartrage 7 Une fois le nettoyage termin vidangez toute la solution r pandue de l appareil via le carter de vidange et la vidange de la chambr...

Page 34: ...du personnel qualifi Les r parations par des per sonnes non qualifi es peuvent provoquer des d charges lectriques et des br lures AVERTISSEMENT DANGER DE D CHARGE LECTRIQUE teignez l appar eil d bran...

Page 35: ...INTES AUX DROITS DE LA PROPRI T INTELLECTUELLE Sans restreindre la port e g n rale des nonc s pr c dents CES GARANTIES NE COUVRENT PAS LES L MENTS SUIVANTS ampoules d clairage incandescence enduites l...

Page 36: ...15 Appliance Installation Buffalo 716 884 7425 Duffy s Equipment Services Inc Buffalo 800 836 1014 3Wire Northern Plattsburgh 800 634 5005 Duffy s Equipment Services Inc Sauquoit 800 836 1014 J B Brad...

Reviews: