INSTALLATION

General

Refrigerated Slim Drop-In Wells are shipped from the factory 

completely assembled and ready for use. Use the following 

information and procedures to prepare the unit and installation 

site.

WARNING

ELECTRIC SHOCK HAZARD:

  •  Plug unit into a properly grounded electrical receptacle 

of the correct voltage, size, and plug configuration. If 

plug and receptacle do not match, contact a qualified 

electrician to determine and install proper voltage and 

size electrical receptacle.

  •  Unit is  not weatherproof. Locate unit indoors.

FIRE HAZARD: Install unit with a minimum of 2″ (51 mm) 

of space between all sides of condensing unit and any 

combustible surfaces.
This unit must be installed by qualified, trained installers. 

Installation must conform to all local electrical and 

plumbing codes. Check with local plumbing and electrical 

inspectors for proper procedures and codes.

CAUTION

Locate unit at the proper counter height in an area that is 

convenient for use. Location should be level and strong 

enough to support weight of unit and contents.

NOTICE

Transport and install unit in upright position only. Failure 

to do so may result in damage to refrigeration system.
This unit is designed for use in environments where 

ambient temperature is between 65°F (18°C) and 86°F 

(30°C). 
When shipped during cold weather months, store unit in 

proper ambient temperature environment for 10 hours to 

prevent compressor and/or refrigerant line damage. If unit 

is turned on and there is excessive noise and vibration, 

turn off immediately and allow additional warm up time.
Provide louvered or grill-style openings with a minimum 

size  of  12″  x  12″/144  square  inches  (31  x  31  cm/

 

961 square cm) in the cabinetry in front of and behind the 

condensing unit for proper ventilation. Failure to provide 

adequate air flow through the condensing unit may cause 

unit failure and will void the unit warranty.
Do not locate unit in an area subject to excessive 

temperatures or grease from grills, fryers, etc. Excessive 

temperatures could cause damage to the unit.

All Slim Refrigerated Drop-In Wells are shipped in a shipping 

frame for protection and stability. Keep the unit in the shipping 

frame until the unit and the installation site are completely 

prepared for the unit to be installed.
  1.  Remove all external packaging from the unit.
  2.  Remove tape, protective packaging, and literature from all 

surfaces of the unit.

NOTE: To prevent delay in obtaining warranty coverage, complete 

online warranty registration. See the 

IMPORTANT 

OWNER INFORMATION

 section for details.

Preparing the Unit for Installation

The orientation of the condensing unit on all CWB-S models 

can be adjusted to match the layout of the installation site. It 

can be rotated 90° or 180° from its factory-installed position. On  

CWB-S2, -S3, and -S4 models, the condensing unit also can be 

mounted in several positions between the center of the well and 

the evaporator coil connections. Rotating the condensing unit 

must be performed after installing the unit due to the dimension 

of the countertop cutout.
Survey the installation site and determine if adjustment to the 

orientation and/or position of the condensing unit is necessary. 

Take into account the need for louvered or grill-style openings in 

the cabinetry to provide proper ventilation for the unit as well as 

access to the control panel. One of these ventilation openings 

must be in front of the condensing coils with the other on the 

opposite side. If multiple refrigerated wells are installed in the 

same counter, each unit should intake cool air and expel hot air.
If adjustment to the orientation of the condensing unit is 

necessary, use the “Rotating the Condensing Unit” procedure 

after installing the unit. If adjustment to the position of the 

condensing unit is necessary, use the following procedure.

Moving the Condensing Unit

This procedure can be performed on CWB-S2, CWB-S3, and 

CWB-S4 models only.
  1.  Remove the two control panel bolts that secure the control 

panel to the condensing unit support frame. Set aside the 

control panel.

  2.  Remove the four mounting screws that secure the condensing 

unit support frame to the underside of the well enclosure.

  3. Move the condensing unit to the desired position. The 

condensing unit can be installed in several positions using 

pre-drilled holes at 6-1/2″ (165 mm) increments between 

the center of the unit and the evaporator coil connections.

  4. Reattach the condensing unit support frame to the well 

enclosure using the four mounting screws.

  5.  Reattach the control panel to the condensing unit support 

frame using the two control panel bolts.

Mounting

Screw

Control Panel Bolt

Condensing Unit Moved to Center Position

Condensing Unit Moved to Center Position

Condensing Unit in End Position

Condensing Unit in End Position

Moving a CWB-S4 Model Condensing Unit

Summary of Contents for CWB-S Series

Page 1: ...equipo al menos que haya le do y comprendido el contenido de este manual Cualquier falla en el seguimiento de las instrucciones contenidas en este manual puede resultar en un serio lesi n o muerte Est...

Page 2: ...e selected for maximum durability attractive appearance and optimum performance Every unit is inspected and tested thoroughly prior to shipment This manual provides the installation safety and operati...

Page 3: ...re all operators have been instructed on the safe and proper use of the unit WARNING This unit is not intended for use by children or persons with reduced physical sensory or mental capabilities Ensur...

Page 4: ...Corian Swanstone etc Hatco Slim Refrigerated Drop In Wells are designed manufactured and tested to maintain safe food holding temperatures The ecoization logo identifies products designed to reflect H...

Page 5: ...8 8 9 9 3 9 7 CEE 7 7 Schuko BS 1363 MODEL DESIGNATION SPECIFICATIONS C W B S x Cold Well Built In Slim Full Size Pan Capacity Electrical Rating Chart Plug Configuration Units are supplied from the fa...

Page 6: ...View Model CWB S4 Side View Model CWB S4 B 2 3 4 70 mm 17 3 8 441 mm 9 1 8 232 mm 15 7 16 392 mm 17 430 mm 2 3 4 70 mm Dimensions Subtract 7 1 2 190 mm from Overall Height C when control box is remote...

Page 7: ...packaging from the unit 2 Remove tape protective packaging and literature from all surfaces of the unit NOTE To prevent delay in obtaining warranty coverage complete online warranty registration See t...

Page 8: ...the desired location The control panel can be installed on one of three sides of the condensing unit support frame Do not install the control panel in front of the condenser coils The control panel ca...

Page 9: ...Refer to the Control Panel Cutout and Screw Hole Dimensions chart for the cutout dimensions 2 Remove the control box from the unit by removing the bolts on the side of the condensing unit 3 Remove th...

Page 10: ...he digital temperature controller will energize and ON will appear on the display followed by the current temperature of the unit The symbol on the display will illuminate to show the condensing unit...

Page 11: ...y until the number 22 appears on the display then press the key 4 Use the or key to scroll through the programmable parameters until dI defrost interval appears on the display 5 Press the key to selec...

Page 12: ...ld detergent Use a plastic scouring pad to remove any hardened food particles or mineral deposits 4 Wipe down well with a clean sanitized cloth to remove the detergent residue Repeat until all deterge...

Page 13: ...ive noise and vibration when turned on Internal components have not been adequately warmed before operation Turn off unit immediately Unit should be stored in a warm environment of 65 F 18 C for at le...

Page 14: ...eep Full Pan 6 152 mm Deep Stainless Steel Food Pans Slanted Base Option Slanted bases are options available for all models The slanted base gives the well a 5 tilt NOTE Water will not completely drai...

Page 15: ...ARTICULAR PURPOSE OR PATENT OR OTHER INTELLECTUAL PROPERTY RIGHT INFRINGEMENT Without limiting the generality of the foregoing SUCH WARRANTIES DO NOT COVER Coated incandescent light bulbs fluorescent...

Page 16: ...le r sultat d une recherche avanc e et d essais pratiques Les mat riaux utilis s ont t s lectionn s pour une durabilit maximale une apparence attractive et des performances optimales Chaque appareil e...

Page 17: ...erie et en lectricit AVERTISSEMENT Assurez vous que les aliments ont t correctement r frig r s une temp rature appropri e avant de les placer dans l appareil Maintenir des aliments une temp rature ina...

Page 18: ...bre service est fourni la sortie de l usine avec le nombre ad quat de barres de support de bacs de 305 mm 12 en fonction de la contenance des bacs du mod le Chaque cuve peut accueillir diff rentes com...

Page 19: ...gr e Slim allong es Contenance du bac grande taille Tableau des valeurs nominales lectriques Configuration des fiches Les appareils sont livr s avec un cordon lectrique avec fiche Diff rentes fiches...

Page 20: ...RTISSEMENT DANGER DE D CHARGE LECTRIQUE Brancher l appareil sur une prise de courant avec terre de tension de format et de configuration des broches corrects Si la fiche et la prise ne se corresponden...

Page 21: ...t tre orient 90 ou 180 de sa position originale la sortie de l usine Sur les mod les CWB S2 S3 et S4 le groupe compresseur condenseur peut galement tre install dans diff rentes positions entre le cent...

Page 22: ...voulu Le panneau de contr le peut tre install sur un des trois c t s du cadre de soutien du groupe compresseur condenseur N installez pas le panneau de contr le devant les serpentins du condenseur Le...

Page 23: ...es de passage de vis et de d coupe pour le panneau de commande pour obtenir les dimensions de d coupe 2 Retirez le bo tier de commande de l unit en retirant les boulons sur le c t du groupe de condens...

Page 24: ...est activ et refroidit la cuve NOTA Cet appareil est pr r gl la sortie de l usine une temp rature nominale de 32 F 0 C Si les conditions ambiantes n cessitent un r glage de la temp rature nominale rep...

Page 25: ...cran Pour la premi re mise en service de l appareil ce nombre sera 0 6 Appuyez sur la touche ou dans les 60 secondes pour faire d filer le nombre d heures souhait entre chaque cycle de d givrage Voici...

Page 26: ...rticule solide de nourriture ou d p t de min raux 4 Essuyez la cuve l aide d un chiffon propre et d sinfect pour enlever toute trace de d tergent R p tez l op ration jusqu ce qu il n y ait plus aucune...

Page 27: ...s avant la mise en service teignez imm diatement l appareil L appareil doit tre stock dans un environnement chaud une temp rature de 65 F 18 C pendant au moins 10 heures OFF clignote sur l cran de com...

Page 28: ...64 mm 2 1 2 de profondeu Bac grande taille 102 mm 4 de profondeu Bac grande taille 152 mm 6 de profondeu Bacs alimentaires en acier inoxydable Base inclin e en option Les bases inclin es sont disponib...

Page 29: ...VETS OU TOUTES AUTRES ATTEINTES AUX DROITS DE LA PROPRI T INTELLECTUELLE Sans restreindre la port e g n rale des nonc s pr c dents CES GARANTIES NE COUVRENT PAS LES L MENTS SUIVANTS ampoules d clairag...

Page 30: ...30 Formulaire n CWBSM 0120 Fran ais Fran ais NOTAS...

Page 31: ...Form No CWBSM 0120 31 English NOTES English...

Page 32: ...e Plattsburgh 800 634 5005 Duffy s AIS Sauquoit 800 836 1014 J B Brady Inc Syracuse 315 422 9271 NORTH CAROLINA Authorized Appliance Charlotte 704 377 4501 OHIO Akron Canton Comm Svc Inc Akron 330 753...

Reviews: