Harsco Industrial P-K SONIC SC-3000 Installation & Owner'S Manual Download Page 5

6

Harsco Industrial, Patterson-Kelley Technical Service 1.877.728.5351

S

a

Fe

TY

Gas Fired Boiler

7

Harsco Industrial, Patterson-Kelley Technical Service 1.877.728.5351

S

a

Fe

TY

Gas Fired Boiler

2.4.2 Crush hazards

lifting hazards!

 Use properly rated lifting equipment to lift and position 

the boiler. The load is unbalanced. Test balance before lifting 

off the floor. Do not allow personnel beneath the lifted load. 

Refer to approximate 

weights in the table.

2.4.5 slip, Fall hazards

tripping hazard!

 Do not install piping on floor surfaces. Maintain clear path around boiler. 

slip and fall hazard!

 Use drip pan to catch water while draining the boiler.Maintain dry floor surfaces. 

slip and fall hazard!

 Do not locate intake or exhaust terminations directly above a walkway; dripping 

of condensation can cause icing of the walking surface. 

(

See section 3.5

)

Fall hazard!

 Do not stand on boiler.

2.4.4 Pressure hazards

Pressure hazard!

 Hot fluids. Install isolation valves on boiler 

water inlet and outlet. Make sure isolation valves are closed 

before servicing boiler.

Pressure hazard!

 Hot fluids. Annually test safety relief valve 

for proper operation. Do not operate boiler with faulty relief 

valve.

2.4.1 electrical hazards

shock hazard! 

Properly lockout/tagout the electrical service 

and all other energy sources before working on or near the 

boiler. 

shock hazard!

 Do not spray water directly on this boiler or 

on any electrical components.

electrical hazard!

 Do not alter wiring connections.

Proper training is the best protection against accidents. It is 

essential

 to 

read, understand, and follow the recommendations of this manual before 

installing, operating, or servicing this equipment. Failure to do so could 

result in fire or explosion and serious injury, death, and/or property damage. 
Operating and service personnel must be thoroughly familiar with the basic 

construction of the 

SC-3000

 and 

SC-4000

 boilers, the use and locations 

of the controls, the operation of the boilers, adjustment of their various 

mechanisms, and all applicable safety precautions. If any of the provisions 

of this manual are not fully and completely understood, contact Harsco 

Industrial, Patterson-Kelley Technical Service at 

570.476.7261

 or toll free at 

877.728.5351.

2.4 h

azard

 W

arnIngs

2.3 T

raInIng

Boiler size

Weight in Pounds

SC-3000

1,850 lbs

SC-4000

1,900 lbs

Gas may lose its odor. Proper gas

 

sensing equipment and procedures 

should be used for leak checks.

!

WARNING

!

WARNING

!

AVERTISSEMENT

!

Improper installation, adjustment,

alteration, service, or maintenance

can cause property damage, personal

injury or loss of life.
Read and understand the installation

and Owner’s manual provided with this

boiler. Installation and service must be

performed by experienced and

knowledgeable personnel who have

been trained on this series boiler.

!

Une installation, un réglage, un

changement ou un entretien

inappropriés peuvent causer des

dommages matériels, des blessures

corpoeiles ou la mort.
Lire et bien comprendre le Manuel

d’installation et du propriétaire fourni avec

cette chaudière. L’installation et le service

dolvent être effectués par un personnel

expérimenté et compétent qui a reçu une

formation sur la chaudière de cette série. 

!

CAUTION

!

ATTENTION

Burn hazard.

Some components

are hot to the touch.

Allow time to cool after

shutdown and do not touch

during operation.

Risque de brûlures.

Certains composants

sont très chauds.

Allouer un temps de 

refroidissement après 

l’arrêt et ne pas toucher 

pendant le functionnement.

!

AVERTISSEMENT

!

WARNING

Electrical Hazard.

Contact may cause electrical 
shock and injury. 

Follow lockout/tagout procedure 
when servicing.

Risque électrique.

Un contact causera un choc 
électrique et des blessures.

Suivre les procédures de 
verrouillage/signalisation lors de 
l’entretien.

!

WARNING

Improper use may

result in fire or injury.

Read instructions/safety 

manual before installing, 

operating or servicing boiler.

The safety labels shown below 

are affixed to your boiler. Although 

the labels are of high quality, 

they may become dislodged or 

unreadable over time. Contact 

Harsco Industrial, Patterson-Kelley 

at 570.476.7261 or toll-free at 

877.728.5351 for replacements.

n

oTICe

!

2.4.6 Chemical hazards

Chemical hazards from cleaning products.

 Use caution 

when cleaning the system. The use of professional 

assistance is recommended. Use safe procedures for the 

disposal of all cleaning solutions.
Combustion Condensate – an acidic pH of approximately 3.0 

to 5.0 can be expected. Use 

PVC

CPVC

, or other corrosion 

resistant piping for drainage. Collection and disposal must be in accordance with all applicable regulations. 

A condensate neutralization kit is available. Please contact your local Harsco Industrial, Patterson-Kelley 

representative for more information.

!

General Warning

!

General Warning

!

General Warning

!

General Warning

!

General Warning

2.4.7 Burn, Fire and explosion hazards

Burn, fire, and explosion hazards!

 Installation must be in strict conformance to all applicable codes 

and standards including 

NFPA 54, ANSI Z223.1

 and 

CAN/CSA B.149

. Install all required vent lines for gas 

devices. Refer to 

Section 3.6

hazard from incorrect fuels!

 Possible fire, explosion, overheating, and damage. Do not use any 

fuels except the design fuels for the unit.

Overfire hazards!

 High pressure in gas supply could result in overfiring of this or other devices 

supplied from the same source.

Fire and explosion hazards!

 Close the main gas shutoff before servicing boiler. 

Fire and explosion hazards!

 Do not store or use gasoline or other flammable vapors or liquids in the 

vicinity of this or any other gas fired appliance.

Burn hazard!

 Possible hot surfaces. Do not touch gas vent during firing operation. Use only factory recommended 

vent components.

Burn hazard!

 Pipes, vents, and boiler components could be hot. Do not touch piping or stack surfaces during 

operation or immediately after shutdown of the boiler. 

Burn hazard!

 Hot flue! Use caution when servicing or draining boiler. 

Fire and explosion hazards!

 Use caution when servicing burner. Propane (

LPG

) is heavier than air and may linger 

in the combustion chamber, vent lines, or elsewhere. 

Gas leak hazard!

 Make sure the burner is installed correctly and blower/transition is securely fastened following 

any maintenance performed on them. These connections may leak gas if assembled incorrectly.

Gas leak hazard!

 All threaded gas connections must be made using a pipe compound that is resistant to liquefied 

petroleum gas. Do not use Teflon™ tape on threaded gas piping.

Gas leak hazard!

 Check entire gas train for leaks after installation. If there is a smell of gas, shut down the boiler 

and obtain immediate assistance from trained service personnel and/or your local fire department. 

Overfire hazard!

 Possible fire and explosion from excess gas pressure. Make sure that gas inlet pressure does not 

exceed 14 inches wc. 

Overfire hazard!

 Possible fire and explosion. Possible malfunction of regulators and/or gas safety shut off/control 

valves. Maintain all gas train components in good condition. Do not alter wiring connections. Annual inspection by 

factory-trained personnel for proper set-up and operation is recommended. 

Overfire and underfire hazards!

 Possible fire, explosion, overheating, and component failure. Do not attempt to 

adjust firing rate of the boiler. The firing rate must be adjusted only by factory trained personnel. 

!

General Warning

!

WARNING

Improper use may

result in fire or injury.

Read instructions/safety 

manual before installing, 

operating or servicing boiler.

Hot Surface

2.4.3 Bump Hazard from overhead ductwork and piping.

 

 

              Install components with adequate vertical clearance.

!

General Warning

Summary of Contents for P-K SONIC SC-3000

Page 1: ...ee 877 728 5351 Fax 570 476 7247 www harscopk com 2013 Harsco Industrial Patterson Kelley SONIC201 Revised June 12 2014 C S A Design Certified Complies with ANSI Z21 13 CSA 4 9 Gas Fired Low Pressure...

Page 2: ...al connections for tightness as connections may come lose during shipping Venting Maintain exhaust pressure from 04 wc to 22 wc Hydronics Maximum Flow SC 4000 384 gpm SC 3000 285 gpm Minimum Flow Igni...

Page 3: ...itches 23 3 10 Initial Adjustments 23 3 10 1 Operating Temperature Controller 23 3 10 2 Boiler Set Point 24 3 10 3 Other CH Parameters 24 3 10 4 Other Parameters 24 3 10 5 Additional Menu Items 24 3 1...

Page 4: ...s fired boilers are fully modulating using variable speed combustion blowers sophisticated microprocessor controls modulating gas safety shut off control valves and a unique stainless steel heat excha...

Page 5: ...res de verrouillage signalisation lors de l entretien WARNING Improper use may result in fire or injury Read instructions safety manual before installing operating or servicing boiler The safety label...

Page 6: ...ainer and be covered by a tarpaulin or other waterproof covering 3 1 1 Initial Inspection Upon receiving the boiler inspect it for signs of shipping damage Some damage may be hidden Unpack the boiler...

Page 7: ...connected to the DHW temperature sensor or thermostat This circuit is energized by the boiler with a 5V potential The temperature sensor must be a NTC having 12k 77 F Header Temp Sensor TB1 9 and TB1...

Page 8: ...re that may cause excessive condensate production in the vent Direct Vent An appliance that is constructed and installed so that all air for combustion is derived directly from outdoors and all flue g...

Page 9: ...d by deducting the blockage area of any fixed louvers grilles or screens from the total area of the opening 2 Screens shall be not smaller than 3 Motorized louvers shall be interlocked with the applia...

Page 10: ...echnical Service 1 877 728 5351 INSTALLATION Gas Fired Boiler The boiler vent should not be connected into any portion of another mechanical draft system without consulting the vent manufacturer The b...

Page 11: ...ll operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 4 Place the appliance being inspected in operation Follow the lighting instructions Adjust the thermostat so tha...

Page 12: ...tted to the boiler The boiler shall not be used as a pipe anchor When installed in a two pipe system that provides both chilled and hot water the control system should be configured so as to limit the...

Page 13: ...guration 2 Place the boiler in operation at the high fire setting BNR TEST MODE HI 3 Smoothly close the downstream manual isolation valve to reduce the gas flow and cause flame failure 4 The display w...

Page 14: ...hnician to hold the boiler in high or low fire during firing operation so that the combustion adjustment can be performed as indicated below The second test mode checks the fan rate with the burner of...

Page 15: ...ssary 3 11 3 Checking Flame Signal Using the control panel enter the information mode and scroll down view the flame signal This shows A when the boiler is firing and shows 0 A when the boiler is not...

Page 16: ...orrective action or repair 5 1 2 Weekly Observe the conditions of the main flame A normal high fire flame is mostly orange with a blue halo while at low fire the burner will glow yellowish orange Corr...

Page 17: ...temperature low water level WARNING 5 6 Troubleshooting 5 6 3 Low Gas Pressure The low gas pressure switch opens when there is or has been insufficient gas pressure available for proper operation of...

Page 18: ...INTERNAL ERROR 31 Internal Error 31 Call for service Code ENVI Display Lockout Description E01 OUT TEMP SENS OPEN Outlet Temperature Sensor Open Boiler outlet water temperature sensor open circuit E02...

Page 19: ...o not ground through the conduit Terminal Number Label Description 3 120V AC Neutral Neutral for use with TB2 10 Switched Output 4 120V AC Neutral Neutral for use with TB2 11 3 Way Valve 5 120V AC Neu...

Page 20: ...ly configured for either 208V 220 240V or 440 480V three phase 60 hertz service Improper configuration of the transformer could result in serious injury or death The high voltage TB2 terminal block is...

Page 21: ...77 728 5351 Gas Fired Boiler 38 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT SC 3000 SC 4000 220 240 VAC three p...

Page 22: ...1 877 728 5351 Gas Fired Boiler 40 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT 6 1 5 SC 3000 SC 4000 Boiler Wir...

Page 23: ...lley Technical Service 1 877 728 5351 Gas Fired Boiler 42 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT 6 1 5 2 S...

Page 24: ...on Kelley Technical Service 1 877 728 5351 Gas Fired Boiler 44 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT 6 1...

Page 25: ...on Kelley Technical Service 1 877 728 5351 Gas Fired Boiler 46 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT 6 1...

Page 26: ...5 7 6 4 B 2 4 A Mark Description 1 Heat Exchanger 2 Blower Burner Assembly 3 Base 4 A Gas train LP 4 B Gas Train Natural Gas 5 Controller 6 Electrical Box 7 Front Door Control Panel 8 Cabinet 6 2 1 Ma...

Page 27: ...Water Connection 5 Condensate Collector 6 Igniter 7 Burner 8 Burner Gasket 9 Burner Hood 6 2 3 SC 3000 SC 4000 Heat Engine Mark Description 1 Burner 2 Burner Transition Piece 3 Blower 4 Venturi 5 Manu...

Page 28: ...cial or consequential damages such as loss of the use of products facilities or production inconvenience loss of time or labor expense involved in repairing or replacing the alleged defective Product...

Page 29: ...Date Hi Low Fire O2 CO CO2 Stack Temp pH Action By Appendix 1 Maintenance Log 54 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 APPENDIX 1 Gas Fired Boiler...

Page 30: ...in section 3 10 4 to get 5 O2 in the flue gas If this cannot be achieved perform the following steps If the O2 is too high then the inlet gas pressure should be adjusted to the minimum pressure allow...

Page 31: ...ntire hydronic system Samples of the system water with cleaner should be taken and analyzed to ensure proper cleaner strength Once cleaned the system should be flushed with fresh fill water until the...