background image

24

Harsco Industrial, Patterson-Kelley Technical Service 1.877.728.5351

INST

alla

TION

Gas Fired Boiler

25

Harsco Industrial, Patterson-Kelley Technical Service 1.877.728.5351

INST

alla

TION

Gas Fired Boiler

Additional 

CH

 Parameters are available and used for 

the various 

CH

 Modes other than mode 0, the standard 

Setpoint & (Thermo)Stat control mode. These modes are 

further described in the 

ENVI®

 Control Advanced User’s 

Guide.

The standby screen is shown upon startup. This screen shows the date, 

time, boiler status, supply temp and setpoint temp. Pushing the menu 

button displays a menu of options. The menu includes access to the 

Standby, Information, Errors, Program Parameters, Configuration, Cascade, 

and Service Menu. The Up and Down buttons are used to position the 

arrow next to the desired option and the enter button is pushed to enter that 

option. The list is displayed and may have more than four lines. Use the down arrow to view the complete list.

Operating Temperature Controller, continued

The factory default setpoint is 180 °F. If a different setpoint is desired, push the menu button and then select 

PARAMETERS

 from the menu. A screen opens that allows the user to view and change operating parameters. 

Select the CH settings to adjust parameters related to the boilers Comfort Heat function.

3.10.2 Boiler set Point

3.10.3 Other Ch Parameters

For example, selecting the Setpoint parameter opens up a screen that allows the setpoint to be changed. The up 

or down buttons are used to adjust the CH setpoint up or down as desired. The enter button is pushed once the 

desired temperature is reached.

3.10.4 Other Parameters

Other parameters include the settings for 

DHW 

(Domestic Hot Water), Boiler Settings and 

OEM

 Settings. 

Boiler and 

OEM

 Settings are used during the initial 

programming of the control and are not adjustable.

3.10.5 Additional menu Items

In the main menu, Standby, Information, Errors, Program Parameters, Configuration, Cascade, and Service 

Menus are available. They are used for various functions of the boiler. These functions are described further in 

the 

ENVI®

 Control Advanced User’s Guide.

These menu items will be described briefly here:

• STANDBY is the default screen and is shown during normal boiler operation.
• The INFORMATION menu lists items that the boiler monitors such as temperatures, operating conditions, and status of 

switches and components.
• The ERRORS menu has information about the boiler status at the time of an error.
• The PARAMETERS menu allows the user to set up selected boiler functions and operating modes.
• The CONFIGURATION menu covers basic display information such as language, units, date/time, etc.
• The CASCADE menu is used to sequence multiple boilers (up to 24 max) in a Master/Member network system. Use of this 

function is described in detail in the Advanced User’s Guide.

3.10.6 Service Menu

Two test modes are available in the service menu.

BNR ON TEST HI LOW
BNR OFF FAN HI LOW

The first test mode allows the service technician to hold the boiler in high or low 

fire during firing operation so that the combustion adjustment can be performed as indicated below.
The second test mode checks the fan rate with the burner off at high speed or at low speed.
These test modes will automatically terminate after 15 minutes of inactivity or can be terminated from the control/

display panel by pressing the cancel/reset button.

The SC-3000 and SC-4000 boilers 

are equipped with a gas/air ratio 

control valve and a gas safety shut 

off control valve, combined into 

one valve assembly. The valve 

functions in series with the variable 

speed combustion blower to 

supply the correct gas air ratio for 

optimum firing performance and 

efficiency. The combustion blower speed is controlled automatically by the 

boiler controller. The blower speed determines the amount of air flow and 

the amount of suction/negative pressure at the gas valves. The gas valve 

adjusts gas flow to maintain the proper delivery pressure at the outlet of 

the valve.

3.11 f

uel

/a

Ir

 a

djusTMenT

n

oTICe

!

 

Adjustments shall only be 

performed by qualified and 

knowledgeable installer or service 

agency specifically trained and 

certified to perform maintenance 

and/or startup on the Harsco 

Industrial, Patterson-Kelley® 

boiler.

3.11.1 Gas Pressure Adjustment

See rating plate for the minimum and maximum gas pressure of the boiler. 

The supply pressure during main burner operation must be greater than the 

minimum indicated on the rating plate. Nominal gas supply pressure is 7” wc for natural gas. The gas pressure 

must not exceed 14” wc which is the maximum allowable pressure on the gas train components. Each boiler is 

furnished with a manual shut-off valve which has an integrated test port. This port is located on the upstream side 

of the valve body for measuring supply pressure. (See Figure 3.10.6b)
The air flow is pre-set at the factory prior to shipment. Gas flow is dependent primarily on fan speed not upstream 

gas pressure. The automatic gas valve may have to be adjusted to obtain proper combustion readings for specific 

local conditions. A combustion analyzer must be used. Combustion should be set in accordance with 

Table 3.11.2

.

Fuel

Nominal Gas Pressure High Fire Setting

Low Fire Setting

% O

2

% CO

2

% O

2

% CO

2

Natural Gas

7" wc

4.8

 

±

 

0.2

9.2 

± 

0.1 5.0

 

±

 

0.2

9.1

 

±

 

0.1

Propane Gas

11" wc

4.8

 

±

 

0.2 10.4

 

±

 

0.3 5.0

 

±

 

0.2 10.3

 

±

 

0.3

3.11.2 Combustion setup and Adjustment

Set the combustion using the Service Menu 

BNR ON TEST HI 

BNR ON TEST LOW

 modes. These test modes 

should be used when checking and setting the gas safety shut off/control valves on the 

SC-3000

 or 

SC-4000

 boiler. 

In this mode a heat request is required. Once the boiler cycles on, use the arrow keys to access the Service 

Menu and select the 

BNR ON TEST HI

 or the 

BNR ON TEST LOW

 mode and push enter. The boiler will ramp up to 

high or low fire. 

Description

Value

units

CH Setpoint

###

o

F

BLR OP (Off = 0, On = 1, Off/Pump 

On = 2, and On/Pump On = 3)

#

0-3

CH Mode

#

0-8

Hysteresis On (On Differential)

##

o

F

Hysteresis Off (Off Differential

##

o

F

Post Pump Time

###

Sec

Figure 3.10.1b

Figure 3.10.2b

Figure 3.10.2c

Figure 3.10.2a

Table 3.10.3

Figure 3.10.6a

Figure 3.10.6b

Table 3.11.2  (PLACE Holder)

Summary of Contents for P-K SONIC SC-3000

Page 1: ...ee 877 728 5351 Fax 570 476 7247 www harscopk com 2013 Harsco Industrial Patterson Kelley SONIC201 Revised June 12 2014 C S A Design Certified Complies with ANSI Z21 13 CSA 4 9 Gas Fired Low Pressure...

Page 2: ...al connections for tightness as connections may come lose during shipping Venting Maintain exhaust pressure from 04 wc to 22 wc Hydronics Maximum Flow SC 4000 384 gpm SC 3000 285 gpm Minimum Flow Igni...

Page 3: ...itches 23 3 10 Initial Adjustments 23 3 10 1 Operating Temperature Controller 23 3 10 2 Boiler Set Point 24 3 10 3 Other CH Parameters 24 3 10 4 Other Parameters 24 3 10 5 Additional Menu Items 24 3 1...

Page 4: ...s fired boilers are fully modulating using variable speed combustion blowers sophisticated microprocessor controls modulating gas safety shut off control valves and a unique stainless steel heat excha...

Page 5: ...res de verrouillage signalisation lors de l entretien WARNING Improper use may result in fire or injury Read instructions safety manual before installing operating or servicing boiler The safety label...

Page 6: ...ainer and be covered by a tarpaulin or other waterproof covering 3 1 1 Initial Inspection Upon receiving the boiler inspect it for signs of shipping damage Some damage may be hidden Unpack the boiler...

Page 7: ...connected to the DHW temperature sensor or thermostat This circuit is energized by the boiler with a 5V potential The temperature sensor must be a NTC having 12k 77 F Header Temp Sensor TB1 9 and TB1...

Page 8: ...re that may cause excessive condensate production in the vent Direct Vent An appliance that is constructed and installed so that all air for combustion is derived directly from outdoors and all flue g...

Page 9: ...d by deducting the blockage area of any fixed louvers grilles or screens from the total area of the opening 2 Screens shall be not smaller than 3 Motorized louvers shall be interlocked with the applia...

Page 10: ...echnical Service 1 877 728 5351 INSTALLATION Gas Fired Boiler The boiler vent should not be connected into any portion of another mechanical draft system without consulting the vent manufacturer The b...

Page 11: ...ll operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 4 Place the appliance being inspected in operation Follow the lighting instructions Adjust the thermostat so tha...

Page 12: ...tted to the boiler The boiler shall not be used as a pipe anchor When installed in a two pipe system that provides both chilled and hot water the control system should be configured so as to limit the...

Page 13: ...guration 2 Place the boiler in operation at the high fire setting BNR TEST MODE HI 3 Smoothly close the downstream manual isolation valve to reduce the gas flow and cause flame failure 4 The display w...

Page 14: ...hnician to hold the boiler in high or low fire during firing operation so that the combustion adjustment can be performed as indicated below The second test mode checks the fan rate with the burner of...

Page 15: ...ssary 3 11 3 Checking Flame Signal Using the control panel enter the information mode and scroll down view the flame signal This shows A when the boiler is firing and shows 0 A when the boiler is not...

Page 16: ...orrective action or repair 5 1 2 Weekly Observe the conditions of the main flame A normal high fire flame is mostly orange with a blue halo while at low fire the burner will glow yellowish orange Corr...

Page 17: ...temperature low water level WARNING 5 6 Troubleshooting 5 6 3 Low Gas Pressure The low gas pressure switch opens when there is or has been insufficient gas pressure available for proper operation of...

Page 18: ...INTERNAL ERROR 31 Internal Error 31 Call for service Code ENVI Display Lockout Description E01 OUT TEMP SENS OPEN Outlet Temperature Sensor Open Boiler outlet water temperature sensor open circuit E02...

Page 19: ...o not ground through the conduit Terminal Number Label Description 3 120V AC Neutral Neutral for use with TB2 10 Switched Output 4 120V AC Neutral Neutral for use with TB2 11 3 Way Valve 5 120V AC Neu...

Page 20: ...ly configured for either 208V 220 240V or 440 480V three phase 60 hertz service Improper configuration of the transformer could result in serious injury or death The high voltage TB2 terminal block is...

Page 21: ...77 728 5351 Gas Fired Boiler 38 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT SC 3000 SC 4000 220 240 VAC three p...

Page 22: ...1 877 728 5351 Gas Fired Boiler 40 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT 6 1 5 SC 3000 SC 4000 Boiler Wir...

Page 23: ...lley Technical Service 1 877 728 5351 Gas Fired Boiler 42 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT 6 1 5 2 S...

Page 24: ...on Kelley Technical Service 1 877 728 5351 Gas Fired Boiler 44 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT 6 1...

Page 25: ...on Kelley Technical Service 1 877 728 5351 Gas Fired Boiler 46 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT 6 1...

Page 26: ...5 7 6 4 B 2 4 A Mark Description 1 Heat Exchanger 2 Blower Burner Assembly 3 Base 4 A Gas train LP 4 B Gas Train Natural Gas 5 Controller 6 Electrical Box 7 Front Door Control Panel 8 Cabinet 6 2 1 Ma...

Page 27: ...Water Connection 5 Condensate Collector 6 Igniter 7 Burner 8 Burner Gasket 9 Burner Hood 6 2 3 SC 3000 SC 4000 Heat Engine Mark Description 1 Burner 2 Burner Transition Piece 3 Blower 4 Venturi 5 Manu...

Page 28: ...cial or consequential damages such as loss of the use of products facilities or production inconvenience loss of time or labor expense involved in repairing or replacing the alleged defective Product...

Page 29: ...Date Hi Low Fire O2 CO CO2 Stack Temp pH Action By Appendix 1 Maintenance Log 54 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 APPENDIX 1 Gas Fired Boiler...

Page 30: ...in section 3 10 4 to get 5 O2 in the flue gas If this cannot be achieved perform the following steps If the O2 is too high then the inlet gas pressure should be adjusted to the minimum pressure allow...

Page 31: ...ntire hydronic system Samples of the system water with cleaner should be taken and analyzed to ensure proper cleaner strength Once cleaned the system should be flushed with fresh fill water until the...

Reviews: