12/20/11
888-2595-001
A-19
WARNING: Disconnect primary power prior to servicing.
Appendix A - FM Web Remote Option
ZX Series
STEP 3
Web remote memory resets IP address, subnet mask, default gateway,
and expert password to values listed above.
STEP 4
Connect to web remote configuration page with PC to 192.168.1.99/
config.htm and change IP address and/or expert password to desired
values.
STEP 5
Procedure complete.
A.5.4
Change Clock Battery
Purpose:
The on-board 3V Lithium battery has an expected lifetime of over 10 years.
If it becomes exhausted, the internal clock will reset to 1 Jan 00 after an AC mains
failure.
Special tools:
Small screwdriver to pry out battery.
NOTE:
This procedure is ideally performed with the transmitter off air and all mains
power removed. Wait until a scheduled maintenance period to perform this pro-
cedure. Consult Figure A.1 for a photo of battery location / appearance.
STEP 1
Remove AC mains power to transmitter.
STEP 2
Remove amplifier chassis I/O panel.
STEP 3
Locate 3V battery on web remote PC board.
STEP 4
Pry battery loose with small screwdriver.
STEP 5
Insert new battery.
STEP 6
Reinstall I/O panel in amplifier chassis.
STEP 7
Reapply AC mains power to amplifier chassis.
STEP 8
Procedure complete.
A.5.5
Calibrate Clock Speed
Purpose:
If no special precautions are taken, the on-board clock in the web remote can
slip several seconds a day. To prevent this, the user can fine trim the clock speed to add
or subtract several seconds a day. This adjustment occurs at midnight each night.
Special tools:
High quality clock for comparison purposes.
STEP 1
While accessing main page, issue on command via ON button to create a
log entry.
Summary of Contents for ZX10
Page 2: ...ii 888 2595 001 12 20 11 WARNING Disconnect primary power prior to servicing ...
Page 4: ...iv 888 2595 001 12 20 11 WARNING Disconnect primary power prior to servicing ...
Page 6: ...MRH 2 888 2595 001 12 20 11 WARNING Disconnect primary power prior to servicing ...
Page 8: ...viii 888 2595 001 12 20 11 WARNING Disconnect primary power prior to servicing ...
Page 9: ...12 20 11 888 2595 001 ix WARNING Disconnect primary power prior to servicing ...
Page 10: ...x 888 2595 001 12 20 11 WARNING Disconnect primary power prior to servicing ...
Page 14: ...xiv 888 2595 001 12 20 11 WARNING Disconnect primary power prior to servicing ...
Page 18: ...Table of Contents Continued 4 ...