HS-3030 Programming Manual
38
•
All Auto:
Force all switches with timers to Auto mode. All switches with timers will go into
the state dictated by the time. The number displayed is the number of switches with timers
forced On or Off. This option has no effect on switches without timers. This option is not
shown if no timers are associated with the switches.
3.5 Battery
Displays the current battery status and charger calibration. The display shows:
Line 1: Screen Title
Line 2: AC State and Battery Charger Calibration Numbers (diagnostic use only)
Line 3: Current State of the Battery and Menu Option (see below)
Line 4: Menu Options (listed below)
The menu has the following options:
•
OK:
Return to Program Menu.
•
Calibrate:
This function is restricted to Privilege Level 2. This calibrates the Battery
Charger. The batteries must be disconnected before beginning calibration. No keypad
control is provided during calibration. The calibration display will return when calibration is
over. Calibration only needs to be done when the main circuit board/power supply board
pair is changed, or when the configuration is erased. All Battery Chargers come calibrated
from the factory.
•
Test:
Force an immediate battery test.
3.6 Conventional
This menu provides for the testing and bypassing of conventional circuits. Each function will
present each zone in turn for selection. Press
<Clear>
to return to this menu without making
changes. The menu has the following options:
•
Test:
Select which zones to test. Test Mode must be on to select zones for testing. All
zones selected are automatically deselected when Test Mode is turned off.
•
Bypass:
This function can be set to Privilege Level 1 or 2. Select conventional circuits to
bypass. A bypassed circuit will be ignored by the panel. Bypasses are retained when the
panel is re-booted. Bypasses are annunciated by a common trouble condition.
3.7 Addressable
The menu has the following options
1
:
•
Reset Max/Min:
Clears the stored values for the maximum and minimum values returned
by the addressable devices. These values are automatically cleared when the panel
reboots.
•
Duplicates Check:
This will cause an immediate check to see if more than one device is
using an address. The panel automatically does this check on the hour.
•
LED Mode:
This controls how the LEDs on the devices are used. There are three options:
-- OFF/FLASH: The device LEDs are normally off and will flash when an alarm is reported.
The flashing LED will be reset when
System Reset
is pressed.
-- FLASH/ON: The device LEDs flash each time they are polled. They will latch on in
Alarm. The LEDs will be reset when
System Reset
is pressed.
1. Panels with 64K EEPROM will not retain Bypass, Sensitivity or Control Module forced states when restarted.
a.
BRK programs dated before 2 April 1999 limit the number of LEDs on to 3 per circuit.
Note:
Due to current draw limitations, only the first 5 detectors
a
on a circuit will latch their LEDs. This has no effect
on other panel operation.