HS-3030 Programming Manual
26
The
SIA Max Events
option sets the maximum number of events the dialer will send for one SIA
transmission. When 20 per Round is selected, SIA sends a maximum of 20 events per round.
When 8 per Round is selected, SIA sends maximum of 8 events per round.
The
Contact ID Rep. Codes
option determines whether the dialer will send automatic reporting
codes, or use the values that are programmed in the Zone Data and Maintenance/Common
reporting codes sections. See Appendix D for a list of the automatic Contact ID Reporting Codes.
The
Test Transmission Line
option determines how the dialer chooses a telephone line to send the
automatic test transmission. If Alternate is selected, the dialer will alternate between using lines 1
and 2 for transmissions, regardless of telephone line troubles. If Available is selected, the dialer
will use Line 1 for test transmissions. If a trouble exists on Line 1, the dialer will switch to Line 2.
When the
Force Dialing
option is set to enabled, if the first attempt by the panel to call the
monitoring station fails, on every subsequent attempt the panel will dial regardless of the presence
of dial tone. When Disabled is selected, the panel will not dial the programmed telephone number
if dial tone is not present.
When the
Busy Tone Detection
option is enabled, if busy tone is detected, the dialer will disengage
the phone line and try to place the call again following the delay between dialing attempts. When
Disabled is selected, the dialer will use the standard dialing procedure for every attempt.
The
Pulse Make/Break Ratio
option is for panels in international applications. When 40/60 is
selected, the pulse dialing make/break ratio is the 40/60, and when 33/67 is selected it is 33/67.
The
Handshake
option determines the handshake used for BPS transmissions. When 1600 Hz is
selected, the dialer responds to a 1600 Hz handshake. When Standard is selected, the dialer
responds to the handshake designated by the format selected (1400 or 2300 Hz).
The
ID Tone
can be set to 1300Hz or 2100 Hz. The panel will emit a tone at the selected frequency
for 500 ms every 2 seconds when it places a call to indicate that it is a digital equipment call, not
voice. When Disabled is selected, this feature will not be used.
Dialer Configuration 2
The Dialer Configuration 2
screen (see
Figure 17
)
contains the Swinger Shutdown
Variables, Other Options and
Test Transmission options.
The
Swinger Shutdown
options
determine the maximum
number of zone and trouble
events that the dialer will
transmit in one day. The alarm
or trouble will still be displayed
on the panel and logged in the
archive, but the dialer will not
transmit the event. There are
individual counters for Zone
Alarm and Restore, Zone
Supervisory and Restore, Zone
Trouble and Restore and Maintenance Trouble and Restore. This feature will be reset at midnight.
To disable the feature, program 000.
The
Test Transmission Time of Day
determines when the automatic test transmission will occur.
The entry is four digits (HH:MM). To disable the feature, program the time as [9999].
Figure 17: Dialer Configuration 2