HS-3030 Programming Manual
12
The System Window has the following push buttons on the right hand side:
•
Exit:
Closes the System Window and, if editing, saves the database. At this time, a
requester will ask if the database should be Verified. A database has to verify without
errors before it can be downloaded.
•
Panels:
Displays the Panel Window. If the system has no panels defined, the Add Panel
Box is displayed to obtain the first control panel for the system.
•
Switches:
Displays the Switches Window. This window determines which devices are
attached to the switches and the timers associated to each switch. See section 2.3 for the
Switches Window
.
•
Groups:
Displays the Groups Window. This window is used to define groups of relates.
See section 2.4 for the
Groups Window
.
•
Map:
Displays and/or updates the Map Window. See section
2.8
Map Window
of the
Network Plus User Guide
.
•
Verify List:
Displays the Verify List. If there is no Verify List, a requester will appear asking
whether you wish to perform a verification. See section
Verify
of the
Network Plus User
Guide
for a full description of the Verify List and its uses.
•
Settings:
Defines the Verify warnings to disable and/or errors to reduce to warnings for
the current database. Not all warnings/errors can be disabled/reduced. The use of this is
not recommended, but provided for special circumstances.
2.3 Switches Window
The Switches Window (see
Figure 6
) allows for the
setting of the On/Off (Day/
Night) switches. There are
16 system wide switches
available. All panels in the
network will keep track of
their own portion of the
devices related to each
switch. Relays, LEDs and
control modules will follow
the On/Off state of the
switch they are related to.
Addressable sensors will
use Day sensitivity while the
switch is on and Night
sensitivity while the switch is
off. The timers are used to
have the switch change state at set times each day. Switches can also be operated manually at
the panel. If the Switch is associated to a Hot Key, the Hot Key will then operate the switches.
Changing a switch manually at one panel will affect all panels in the network.
The title bar of the window will always list the currently highlighted switch.The
Switches
Table
shows all 16 possible switches and highlights the current one. Select any one to make it the
current switch. List entries will show the message RELATES FOUND for switches that have
related devices.
Note:
1.Each addressable detector can only be related to a single switch.
2.Relays, LEDs and control modules controlled by more than one switch will stay on as long as any switch
operating them is on.
Figure 6: Switches Window
Summary of Contents for Network Plus HS-3030
Page 2: ......
Page 4: ......
Page 6: ......
Page 65: ...Harrington Signal Inc 2519 4th Avenue Moline IL 61265 HARRINGTON FIRE ALARM SIGNAL INC ...