9.5 Commissioning
Commissioning must be executed in accordance with the documentation of Harmonic Drive AG.
Before commissioning, please check that:
• The actuator is properly mounted
• All electrical connections and mechanical connections are designed according to requirements
• The protective earth is properly connected
• All attachments (brakes, etc) are operational
• Appropriate measures have been taken to prevent contact with moving and live parts
• The maximum speed n
max
is specified and cannot be exceeded
• The set up of the drive parameters has been executed
• The commutation is adjusted correctly
Check the direction of rotation of the load uncoupled.
In the event of changes in the normal operating behaviour, such as increased temperature, noise or vibration, switch the actu-
ator off. Determine the cause of the problem and contact the manufacturer if necessary. Even if the actuator is only on test,
do not put safety equipment out of operation.
This list may not be complete. Other checks may also be necessary.
Due to heat generation from the actuator itself, tests outside the final mounting position should be limited to 5 minutes of
continuous running at a motor speed of less than 1000 rpm.
These values should not be exceeded in order to avoid thermal damage to the actuator.
9.6 Overload Protection
To protect the servo actuators and motors from temperature
overload sensors are integrated into the motor windings.
The temperature sensors alone do not guarantee motor
protection. Protection against overload of the motor winding
is only possible with an input speed > 0. For special applica-
tions (eg. load at standstill or very low speed) is an additional
overload protection by limiting the overload period.
The built specification of the integrated temperature sensors
can be found in the technical data.
In addition, it is recommended to protect the motor winding
against overload by the use of I²t monitoring integrated in
the controller. The graph shows an example of the overload
characteristic for the I²t monitoring. The overload factor is
the ratio between the actual RMS current and continuous
stall current.
ADVICE
70,00
60,00
50,00
40,00
30,00
20,00
10,00
0,00
0,00 0,50 1,00 1,50 2,00 2,50 3,00 3,50 4,00 4,50 5,00
time [s
]
I / Is
Over load characteristic
Illustration 50.1
l
s
= Continuous stall current
l = Actual effective current (l ≤ l
max
)
NOTE