Chapter 3 

Installation of Intrinsically Safe HI 6020 IT and HI 
6020JB Summing Boxes into Hazardous (Classified) 
Locations 

• • • • • •

 

This user guide is intended to provide the user with an overview regarding the proper selection of electronic 
weighing systems used in hazardous locations. This document does not provide details on the installation of 
equipment as this is typically the responsibility of the installing electrician and/ or engineering design firm. 
 
For the latest information please refer to the appropriate set of control drawings which will be one of the item 
shipped with the summing box. 

 

HI 6020JB series please refer to 

control drawing 0594-0007

 

 

HI 6020IT series please refer to 

control drawing 0594-0008

 

Additional copies this user guide and control drawings are available on the Hardy website at: 

http://www.hardysolutions.com/products/load-cells--platform-scales/accessories/product/511/hi-6020it-and-
hi-6020jb-junction-boxes

  

 

Wiring Summing Boxes 

 
IMPORTANT NOTES when wiring between load cells, summing boxes, and intrinsically safe barriers 
 

1.

 

Associated apparatus manufacturer’s installation drawing must be followed when installing this equipment. 
 

2.

 

Resistance between Intrinsically Safe Ground and earth ground must be less than 1.0 Ohm. 

 

3.

 

Install Intrinsic Safe Barriers in accordance with barrier instructions. 

 

4.

 

The total combined length of all wiring in the system, including the cable from each associated apparatus to and from 
the summing box, and to each load cell must not exceed 300 feet. 

 

a.

 

Installation should be in accordance with any applicable local electrical code, which may include ANSI/ISA 
RP12.06.01 “Installation of Intrinsically Safe System for Hazardous (Classified) Locations,” the electrical Safety 
code (ANSI/NFPA 70) Article 504. 

b.

 

The products for use in both Class I, II, III Division 1 and 2 areas (NEC 501, 502) and Class 1, Zone 0 and 2, 
Group IIC, and Zone 20 and 22, Group IIIC areas (NEC 505, 506) is the HI 6020JB-SSX-Y and the HI 6020IT-
SSX-Y (both shipped with cable glands): 

c.

 

SS = Stainless Steel enclosure 

d.

 

1 = Without trim pots, 2 = With Trim Pots 

e.

 

Y= blank is a 5-hole summing box enclosure, and Y=6 is a 6-hole summing box enclosure enabling connection 
to a second summing box 
 

5.

 

SB (summing box) maximum cable length 250 ft; used between the summing box and IS barriers. 

6.

 

Substitution of components may impair Intrinsic Safety and/or void Hazardous Area Approval. 

Summary of Contents for HI 6020IT

Page 1: ...nd HI 6020JB US Canada Hazardous Locations User Guide Class I II III Division 1 Class I Zone 0 and Zone 20 Hardy Process Solutions Document Number 0596 0352 01 REV B CONTROLLED DOCUMENT CHANGES MAY NO...

Page 2: ...L WHO ARE FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF ALL COMPONENTS IN THE SYSTEM AND THE POTENTIAL HAZARDS INVOLVED FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN BODILY HARM AND OR PROPERTY...

Page 3: ...abilities 7 Hardy Process Toolbox 7 C2 and Calibration 7 INTEGRATED TECHNICIAN 7 Chapter 3 8 Installation of Intrinsically Safe HI 6020 IT and HI 6020JB Summing Boxes into Hazardous Classified Locatio...

Page 4: ...ox is a critical component in a weighing system that enables use of Hardy s core technologies C2 electronic calibration and Integrated Technician IT Each summing box distributes excitation voltage to...

Page 5: ...thout trim pots or X 2 with trim pots Y Y blank is a 5 hole summing box enclosure Y 6 is a 6 hole summing box enclosure enabling connection to a second summing box The HI 6020JB and HI 6020IT is provi...

Page 6: ...iew the installation section for additional information Trim Pot Number of Turns 11 for use with non C2 systems Trim Pot Impedance Range 0 10 Power Rating Non Hazardous Safe area Locations Class I and...

Page 7: ...the need for test weights A C2 weighing system consists of up to eight load cell sensors per HI 6020 IT or JB summing box C2 interconnect cable and a Hardy instrument controller or module with C2 Each...

Page 8: ...atus manufacturer s installation drawing must be followed when installing this equipment 2 Resistance between Intrinsically Safe Ground and earth ground must be lessthan 1 0 Ohm 3 Install Intrinsic Sa...

Page 9: ...t controller or module you will need a summing cardorsummingboxtoaggregatethesignalstoprovideasingularweight reading Whileaplatform benchor floorscalehasabuiltinsummingcardtoperformthisfunction loadce...

Page 10: ...n C2 load sensor wiring Hardy load sensor with C2 wiring WARNING To prevent ignition of flammable or combustible atmospheres disconnect power before servicing CAUTION Observe precautions for electrost...

Page 11: ...D ASSOCIATED APPARATUS FOR USE IN CLASS I II III DIVISION 1 HAZARDOUS CLASSIFIED LOCATIONS Edition 8 Revision Date 2015 04 28 CSA C22 2 NO 157 92 INTRINSICALLY SAFE AND NON INCENDIVE EQUIPMENT FOR USE...

Page 12: ...HI 6020IT and HI 6020JB User Guide Page 12 This page intentionally left blank...

Page 13: ...ns are EASIER to install integrate commission diagnose and maintain Want MORE PRODUCTIVITY at the LEAST TOTAL COST to own Call Hardy to discover how Today 9440 Carroll Park Drive San Diego CA 92121 Te...

Reviews: