Chapter 1 

HI 6020IT and HI 6020JB Overview  

• • • • • •

 

This  user  guide  describes  installation,  setup  and  operating  procedures  for  the  HI  6020IT  and  HI  6020JB 
summing boxes. Be sure to read and understand all cautions, warnings, and safety procedures in this user guide 
to ensure safe installation and operation of the summing boxes. 
 
Hardy Process Solutions sincerely appreciates your business. We encourage input about the performance and 
operation of our products from our customers. Should you not understand any information in this user guide or 
experience any problems with this product, please contact our Technical Support Department at: 

 

Phone:  

(858) 278-2900   

Toll Free:   

1-800-821-5831   

FAX:           

(858) 278-6700 

E-Mail:  

[email protected] or [email protected]   

Website:

    www.hardysolutions.com  

Please visit our website for the latest revision of this User Guide and sign up for the Hardy Newsletter to get 
the latest information on all Hardy products and services. For answers to technical issues and service problems, 
please visit the Hardy WebTech section of our  website or contact a technician by phone during our normal 
operating hours (6:30 AM to 5:30 PM Pacific Time). 
 

Introduction to the HI 6020IT and HI 6020JB Summing Boxes 

The Hardy HI 6020 summing box is a critical component in a weighing system that enables use of Hardy’s core 

technologies - C2

®

 electronic calibration and Integrated Technician

® 

(IT).   

 

Each  summing  box  distributes  excitation  voltage  to  up  to  four  load  cells  and  transfers  each  load  cell’s 

performance characteristics and  weight  signals to the Hardy  weighing instrument.  A  summing card  with IT 
allows a weighing instrument operator to switch to the summing card’s internal test circuit and diagnose the 
entire weighing system from the front panel of the instrument or a remote location over the Internet.   Individual 

load cells can be isolated from each other for weight and voltage readings, allowing a technician or operator to 

quickly and safely troubleshoot weighing system faults and anomalies. 

 

The HI 6020 Summing box is available with a variety of options, including Integrated Technician

® 

(IT) and 

trim pots (for non-Hardy load cells). The UL Type 4/4X stainless steel enclosure features a thick-wall design 

with an interior seal for a long lasting, robust wash-down installation. Two configurations are available, a 5-

hole version for connecting up to four load cells to a Hardy weight indicator, controller, or module; or a 6-hole 

version that connects to a second HI 6020 summing box to enable up to eight load cells to be connected to a 

Hardy  weight  indicator or controller. The HI 6020 summing  box comes  with  four packaged hole-plugs,  six 

cable grip fittings, suitable for load cell cables with an outside diameter of 4.3mm to 11.4mm. 

 

Summary of Contents for HI 6020IT

Page 1: ...nd HI 6020JB US Canada Hazardous Locations User Guide Class I II III Division 1 Class I Zone 0 and Zone 20 Hardy Process Solutions Document Number 0596 0352 01 REV B CONTROLLED DOCUMENT CHANGES MAY NO...

Page 2: ...L WHO ARE FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF ALL COMPONENTS IN THE SYSTEM AND THE POTENTIAL HAZARDS INVOLVED FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN BODILY HARM AND OR PROPERTY...

Page 3: ...abilities 7 Hardy Process Toolbox 7 C2 and Calibration 7 INTEGRATED TECHNICIAN 7 Chapter 3 8 Installation of Intrinsically Safe HI 6020 IT and HI 6020JB Summing Boxes into Hazardous Classified Locatio...

Page 4: ...ox is a critical component in a weighing system that enables use of Hardy s core technologies C2 electronic calibration and Integrated Technician IT Each summing box distributes excitation voltage to...

Page 5: ...thout trim pots or X 2 with trim pots Y Y blank is a 5 hole summing box enclosure Y 6 is a 6 hole summing box enclosure enabling connection to a second summing box The HI 6020JB and HI 6020IT is provi...

Page 6: ...iew the installation section for additional information Trim Pot Number of Turns 11 for use with non C2 systems Trim Pot Impedance Range 0 10 Power Rating Non Hazardous Safe area Locations Class I and...

Page 7: ...the need for test weights A C2 weighing system consists of up to eight load cell sensors per HI 6020 IT or JB summing box C2 interconnect cable and a Hardy instrument controller or module with C2 Each...

Page 8: ...atus manufacturer s installation drawing must be followed when installing this equipment 2 Resistance between Intrinsically Safe Ground and earth ground must be lessthan 1 0 Ohm 3 Install Intrinsic Sa...

Page 9: ...t controller or module you will need a summing cardorsummingboxtoaggregatethesignalstoprovideasingularweight reading Whileaplatform benchor floorscalehasabuiltinsummingcardtoperformthisfunction loadce...

Page 10: ...n C2 load sensor wiring Hardy load sensor with C2 wiring WARNING To prevent ignition of flammable or combustible atmospheres disconnect power before servicing CAUTION Observe precautions for electrost...

Page 11: ...D ASSOCIATED APPARATUS FOR USE IN CLASS I II III DIVISION 1 HAZARDOUS CLASSIFIED LOCATIONS Edition 8 Revision Date 2015 04 28 CSA C22 2 NO 157 92 INTRINSICALLY SAFE AND NON INCENDIVE EQUIPMENT FOR USE...

Page 12: ...HI 6020IT and HI 6020JB User Guide Page 12 This page intentionally left blank...

Page 13: ...ns are EASIER to install integrate commission diagnose and maintain Want MORE PRODUCTIVITY at the LEAST TOTAL COST to own Call Hardy to discover how Today 9440 Carroll Park Drive San Diego CA 92121 Te...