Hardy Process Solutions HI 6020IT User Manual Download Page 6

HI 6020IT and HI 6020JB User Guide 

 

Page | 6 

 

Connector Type 

 

Removable Plug-In Terminal Blocks 

 

4 off, 7 pin, 1 row, 3.5 mm pitch (load points) 

 

2 off, 9 pin, 1 row, 3.5 mm pitch (instrument and auxiliary ports) 

 

Temp Range 

-10 to +60°C (14 to 140°F) 

 

Maximum Excitation Voltage and estimated Excitation Current 

The maximum excitation voltage, on the summing box side of the IS barrier, is 5VDC. 
The maximum excitation current is 70mA under normal operating conditions, and is limited to 100mA by the 
selected IS barriers. 
 
The required IS barrier supply voltage and actual excitation current drawn for a load cell weighing system, 
depends upon the IS barriers selected, the load cell resistance, the cable length between the excitation voltage 
source and the summing box, the number of summing boxes, and the number of  load cells required for the 
weighing system. 
 
Please review the installation section for additional information. 
 

Trim Pot Number of Turns 

11 (for use with non-C2 systems) 

 

Trim Pot Impedance Range 

0-10 Ω  

 

Power Rating 

Non Hazardous, Safe area Locations, 

Class I and II, Division 2 Hazardous and Class III Division 1 and 2 Hazardous (Classified) Locations, and 

Class I, Zone 0 and 2 Groups IIC, Zone 20 and 22 Groups IIIC 

HI 6020IT: 5 VDC, Class 2 source, max. 50 mA 

HI 6020JB: 2-15 VDC, Class 2 source, max. 275 mA 

 

Class I and II, Division 1 Hazardous (Classified) Locations and Class I, Zone 0 and 2 Groups IIC, Zone 20 

and 22 Groups IIIC 

Power must be supplied to the summing box through approved intrinsically safe barriers per control 

drawing 0594-0007 (HI 6020JB) or 0594-0008 (HI 6020IT) 

HI 6020IT: 5 VDC, Class 2, max. 50 mA 

HI 6020JB: 5 VDC, Class 2, max. 50 mA 

 

Warranty 

Two-year warranty against defects in workmanship 

 

Housing Torque Specification 

Enclosure Bolt Torque Specification:  50-55 in/lb 

Additional Instruction:  Be sure to lubricate (oil) the screw threads to prevent galling of the screw and 

enclosure screw flange threads. 

Summary of Contents for HI 6020IT

Page 1: ...nd HI 6020JB US Canada Hazardous Locations User Guide Class I II III Division 1 Class I Zone 0 and Zone 20 Hardy Process Solutions Document Number 0596 0352 01 REV B CONTROLLED DOCUMENT CHANGES MAY NO...

Page 2: ...L WHO ARE FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF ALL COMPONENTS IN THE SYSTEM AND THE POTENTIAL HAZARDS INVOLVED FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN BODILY HARM AND OR PROPERTY...

Page 3: ...abilities 7 Hardy Process Toolbox 7 C2 and Calibration 7 INTEGRATED TECHNICIAN 7 Chapter 3 8 Installation of Intrinsically Safe HI 6020 IT and HI 6020JB Summing Boxes into Hazardous Classified Locatio...

Page 4: ...ox is a critical component in a weighing system that enables use of Hardy s core technologies C2 electronic calibration and Integrated Technician IT Each summing box distributes excitation voltage to...

Page 5: ...thout trim pots or X 2 with trim pots Y Y blank is a 5 hole summing box enclosure Y 6 is a 6 hole summing box enclosure enabling connection to a second summing box The HI 6020JB and HI 6020IT is provi...

Page 6: ...iew the installation section for additional information Trim Pot Number of Turns 11 for use with non C2 systems Trim Pot Impedance Range 0 10 Power Rating Non Hazardous Safe area Locations Class I and...

Page 7: ...the need for test weights A C2 weighing system consists of up to eight load cell sensors per HI 6020 IT or JB summing box C2 interconnect cable and a Hardy instrument controller or module with C2 Each...

Page 8: ...atus manufacturer s installation drawing must be followed when installing this equipment 2 Resistance between Intrinsically Safe Ground and earth ground must be lessthan 1 0 Ohm 3 Install Intrinsic Sa...

Page 9: ...t controller or module you will need a summing cardorsummingboxtoaggregatethesignalstoprovideasingularweight reading Whileaplatform benchor floorscalehasabuiltinsummingcardtoperformthisfunction loadce...

Page 10: ...n C2 load sensor wiring Hardy load sensor with C2 wiring WARNING To prevent ignition of flammable or combustible atmospheres disconnect power before servicing CAUTION Observe precautions for electrost...

Page 11: ...D ASSOCIATED APPARATUS FOR USE IN CLASS I II III DIVISION 1 HAZARDOUS CLASSIFIED LOCATIONS Edition 8 Revision Date 2015 04 28 CSA C22 2 NO 157 92 INTRINSICALLY SAFE AND NON INCENDIVE EQUIPMENT FOR USE...

Page 12: ...HI 6020IT and HI 6020JB User Guide Page 12 This page intentionally left blank...

Page 13: ...ns are EASIER to install integrate commission diagnose and maintain Want MORE PRODUCTIVITY at the LEAST TOTAL COST to own Call Hardy to discover how Today 9440 Carroll Park Drive San Diego CA 92121 Te...

Reviews: