Hansen FM-71 Installation Manual Download Page 4

4

F100d 
JAN 2011

SETTING DEFROST START TIMES

To  set  the  time-of-day  or  day-of-the-week  (7-day 

clock) rotate the time clock clockwise until the exact 
time matches up with the triangle shaped time marker 

located on the inner dial.  To set defrost start times, 
push  the  time  clock  tabs  next  to  the  desired  times 
towards the center.  Defrosts will begin at each of these 
times, provided the initiate terminals are closed (for 
time-only defrost, a factory installed, removable jumper 

closes these terminals; see DEMAND INITIATE).

Typically, no more than a 1/3 of a plant’s evaporators 

should be in defrost at one time because an adequate 
supply of hot gas is required.  About 100 psig minimum 
of hot gas pressure should be available for ammonia 
or  a  pressure  equivalent  to  40ºF  (4°C)  saturation 
pressure  plus  about  30  psi  line  pressure  drop  for 
other refrigerants.

For  multiple  evaporators  with  individual  defrost 
controllers, if necessary the defrost start time settings 
can be staggered by 15 minutes (or multiples thereof) 
and the 24 hour quartz time clock will maintain this 
interval accurately.  (The 7-day time clock can stagger 
start times by 2 hours or multiples.)  At least one tab 
must be set away from the center of the time clock 
between  defrosts.    Therefore,  a  ½  hour  minimum 
between defrosts for 24 hour time clocks and a 4 hour 
minimum for 7-day clocks is required.

SETTING DEFROST STEPS

Each  defrost  step  has  its  own  slide  knob  time 
adjustment.    After  determining  the  proper  setting, 
move  each  slide  knob  to  a  position  corresponding 
to an appropriate amount of time (minutes).  Defrost 
step lights will illuminate during each respective step 
to inform operator of defrost status.  After observing 
several defrosts, the setting may be easily re-adjusted 
to  more  closely  match  the  actual  conditions  of  the 
application.

DEFROST STEP AND MODE LIGHTS

These lights inform the operator of defrost controller 

status.    A  green  L .E.D.  light  indicates  normal 
refrigeration.  A combination of two red L.E.D. lights 
indicates the defrost mode and its particular step.  If 
no lights are on, check power to controller.

MANUAL STEPPING

A  manual  stepping  button  is  provided  for  initiating 

and optionally advancing through the defrost steps.  

This will be helpful when testing electrical operation 

and  connections,  as  well  as  manually  initiating  a 
defrost during a period of unusual frost accumulation.  
IMPORTANT:  Control devices (solenoid valves, control 
relays,  etc.)  can  operate  while  using  the  manual 
stepping button.  Care should be taken not to advance 
the defrost steps so rapidly that the evaporator, piping, 
and other refrigerant components experience sudden 
or unfavorable conditions.

DEMAND INITIATE

The defrost initiate feature is a normally open (N.O.) pair 

of ¼” spade terminals (INIT).  They must be closed and 
a time clock tab must trip before a defrost will begin.  
In other words, initiate for a clock equipped defrost 
controller will only occur if called for by an initiation 
device 

during

 a clock scheduled defrost period.  On 

the other hand, a “clockless” Remote Initiate Model 
(FM-01,  FM-02,  FMP-01)  could  initiate  defrost  any 
time  the  initiate  device  closed  the  terminals.    The 
Frost  Master®  is  supplied  with  a  factory  installed 
jumper wire which closes the initiate terminals.  If a 
remote demand initiate defrost device is to be used 
for a clock model, simply cut and remove this small, 
horizontal  jumper  wire  which  is  soldered  between 
the base of the initiate terminals.  Then connect the 
normally  open  leads  from  the  initiate  device  to  the 
initiate spade terminals.

The  demand  defrost  cycle  will  occur  only  when  the 

time clock tabs are pushed in and when the initiate 
device calls for defrost.  This prevents defrosts from 
occurring at inappropriate times.  At least one time 
clock  tab  must  be  set  away  from  the  center  of  the 
time clock between defrost initiate times to “RE-ARM” 
controller.  If there are periods when a demand defrost 
would not be advantageous (i.e. when loading a room 
or at the beginning of a work shift), pull the time clock 
tabs which correspond to these times away from the 
center of the time clock.  A defrost will not be able 
to  start  during  these  times.    Should  a  defrost  be 
requested by the initiate device during this restricted 
time  period,  it  will  not  start  until  the  next  following 
pushed-in time clock tab time is reached.  This is also 
ideal in preventing too many or several evaporators 
in the same room from going into defrost at once.  It 
is feasible to use a computer or similar device in lieu 
of a frost sensor for demand initiate.

Frost Master® Remote Initiate Models (less any time 
clock)  offer  many  features  suitable  for  computer 
initiate,  manual  push  button,  and  demand  defrost 
devices only; see page 12.

TERMINATE

The defrost terminate feature is a normally open (N.O.) 

pair of ¼” spade terminals. When there is a closure 
of  these  terminals  during  the  HOT  GAS  step  only, 
the  Frost  Master®  ceases  hot  gas  defrost  supply, 
advances to EQUALIZE and proceeds at the set time 
intervals through to the other steps.  The coil clean 
terminate  device  is  usually  a  customer  supplied 
thermostat  (temperature  switch)  set  at  about  40ºF 
(4°C) whose sensing bulb is located at the last place 
on  the  evaporator  coil  where  frost  or  ice  remains 
during  a  defrost.    By  ending  the  HOT  GAS  step  as 
soon as the coil is clean, a quick and efficient defrost 
occurs.  When using a terminate device be sure that 
the HOT GAS step duration setting is long enough to 
always permit a complete defrost. If not sure, set to 
maximum. If the terminate device or thermostat is not 
actuated,  the  hot  gas  supply  or  other  frost  melting 
medium will be terminated by this step time setting.  
For  defrost  controller  with  built-in  Temperature 

Terminate feature and sensor, see Frost Master® 

Plus

 

models on page 6.

Summary of Contents for FM-71

Page 1: ... specifically for defrosting industrial and large commercial refrigeration systems the Frost Master sequences solenoid valves and relays to provide quick and efficient defrosting of evaporator coils Because of its SPDT relays and time adjustable defrost steps this controller is suitable for almost every defrost application including top and bottom feed unit coolers blast freezer evaporators and ic...

Page 2: ...of defrosts per day or week by not defrosting unless necessary the time clock can be used to prevent defrost from happening when it would not be advantageous Temperature terminate contacts are provided to optionally connect a thermostat or other device for minimized defrost time The Remote Initiate models clockless require only an external momentary dry contact closure of the initiate terminals fr...

Page 3: ... begins Less liquid means more internal evaporator surface is exposed to entering hot gas It also reduces the amount of liquid accommodated by the system during defrost HOT GAS 0 to 45 minutes The HOT GAS step begins the actual melting of the frost accumulation The amount of time required to remove the frost is dependent on many factors including the following design of evaporator quantity of fros...

Page 4: ...and a time clock tab must trip before a defrost will begin In other words initiate for a clock equipped defrost controller will only occur if called for by an initiation device during a clock scheduled defrost period On the other hand a clockless Remote Initiate Model FM 01 FM 02 FMP 01 could initiate defrost any time the initiate device closed the terminals The Frost Master is supplied with a fac...

Page 5: ...vaporator shown on page 9 Other wiring schemes are possible to meet system requirements This wiring diagram is for illustration purposes only and does not show all controls and safety devices Final control wiring is the responsibility of the system designer See above table for relay operation Relays shown with no power to Frost Master See above for relay operation relay energized POWER INPUT RELAY...

Page 6: ...sture Field sensor wire size should be at least 20 AWG 0 5 mm2 and limited to a distance of 500 ft 152 m Avoid running wires through evaporator air stream or with high voltage wiring Connect field sensor wires to terminate temperature sensor quick disconnect plug inside defrost controller enclosure terminate temperature sensor INTRODUCTION This deluxe model Frost Master Plus includes an additional...

Page 7: ...ator shown on page 9 Other wiring schemes are possible to meet system requirements This wiring diagram is for illustration purposes only and does not show all controls and safety devices Final control wiring is the responsibility of the system designer See above table for relay operation Relays shown with no power to Frost Master Plus See above for relay operation relay energized POWER INPUT RELAY...

Page 8: ...al Typically the defrost relief regulator is set at about 70 psig 5 bar for ammonia When a defrost condensate liquid drainer is used an outlet pressure regulator in the hot gas supply line should be used to limit the internal evaporator pressure Check valves are installed after the liquid solenoid valve to prevent higher pressure gas from entering the liquid supply line during defrost Also check v...

Page 9: ...NOID VALVE WITH ELECTRIC SHUT OFF STOP VALVE OR REGULATOR OR GAS POWERED SUCTION SUCTION SOLENOID VALVE FOR EQUALIZING WITH WIDE OPENING FEATURE DEFROST RELIEF REGULATOR OVERFEED LIQUID LINE SUCTION LINE OVERFEED BOTTOM FEED EVAPORATOR TOP FEED EVAPORATOR EVAPORATOR WITH GAS POWERED SUCTION STOP VALVE EVAPORATOR WITH DEFROST CONDENSATE LIQUID DRAINER DEFROST RELIEF HOT GAS SOLENOID VALVE SOFT GAS ...

Page 10: ...frost melting can begin Typical rating at 86ºF to 10ºF is 7 5 lbs min 0 063 kg sec for ammonia and 24 5 lbs min 0 117 kg sec for R22 For greater capacities contact factory Inlet outlet connections combination FPT 1 Weld HD101 dEFROST CONDENSATE LIQUID DRAINER Mechanical non electrical float regulator drains liquid condensate from evaporator during defrost It has built in gas vent plus expansion va...

Page 11: ...se requires no pressure drop to operate Requires a single pilot solenoid valve to control Typically used to close off evaporators from system suction especially below 20F 30C HS9B GAS POWERED SOLENOID VALVE This valve uses a remote gas or liquid pressure source to close requires no pressure drop to operate Dual pilot solenoid valve assembly controls opening and closing of valve without internal bl...

Page 12: ...me of day and defrost start times WARRANTY Hansen defrost controllers are guaranteed against defective materials or workmanship for 90 days F O B our plant No consequential damages or field labor is included REMOTE INITIATE MODELS Remote Initiate Models FM 01 FM 02 and FMP 01 are supplied less any time clock and horizontal jumper wire The defrost begins when the initiate spade terminals are moment...

Reviews: