HOT GAS DEFROST NOMINAL VALVE SIZING (TONS)

REFRIG.

APPLICATION

PORT SIZE

3/4”

1”

1-1/4”

1-1/2”

2”

2-1/2”

R717

Hot Gas Solenoid

9 to 15

15 to 28

28 to 39

39 to 73

73 to 106

106 to 165

Defrost Relief Regulator

17 to 24

24 to 45

45 to 60

60 to 96

96 to 140

140 to 225

R22

Hot Gas Solenoid

6 to 8

8 to 15

15 to 20

20 to 32

32 to 47

47 to 75

Defrost Relief Regulator

6 to 8

8 to 15

15 to 20

20 to 32

32 to 47

47 to 75

Evaporator tons at 10ºF (5°C) temperature differential.  Ideal sizing could vary with desired time for defrosting, 
available supply pressure, amount of ice on evaporator, usage of pre-defrost pumpout, etc.  For other control 
valve sizing, see detailed Hansen bulletins on specific valve types.

VALVE SELECTION

* Type HCK2, HCK2W requires single pilot solenoid valve to operate and has minimal internal bleed to down stream side of main 

valve.  Type HS9B, HS9BW uses dual pilot solenoid valve assembly and has no internal bleed.

HT100 CONDENSATE 
DRAINER

This  unit  is  ideally  suited  for  the 

removal  of  liquid  condensate  from 
hot gas mains and headers.  Helps 
assure refrigerant gas will be available at inlet of hot 
gas supply valve leading to evaporator.  This avoids 
moving condensed liquid through valve before frost 
melting can begin.  Typical rating at 86ºF to 10ºF is 

7.5 lbs./min. (0.063 kg/sec.) for ammonia and 24.5 lbs./

min. (0.117 kg/sec.) for R22.  For greater capacities, 
contact factory.  Inlet/outlet connections: combination 

¾” FPT/1”Weld.

HD101 DEFROST 

CONDENSATE LIQUID 

DRAINER

Mechanical/non-electrical  float 
regulator drains liquid condensate 
from evaporator during defrost.  It 
has built-in gas vent plus expansion valve bypass as 
is necessary to avoid gas binding.  Suitable capacity 
for 42 ton (147 kW) max. ammonia evaporator or 11 
ton (39 kW) max. R22 evaporator; for larger capacities, 
contact factory.   Inlet/outlet connections: combination  

¾” FPT/1” Weld. 

DESCRIPTION

PORT SIZES

1/2”

3/4”

1”

1-1/4” 1-1/2”

2”

2-1/2”

3”

4”

5”

6”

Liquid Line Solenoid 

Valve

HS8A

HS7 

HS4A

HS7 

HS4A

HS7 

HS4A

HS4A

HS4A

HS4A

Suction 

Line 

Solenoid 

Valve

Down 

to -20ºF 

(-30ºC)

HS7 

HS4A

HS7 

HS4A

HS7 

HS4A

HS4A

HS4A

HS4A

HS4A

HS4A

HS4W

HS4W

Down 

to -60ºF 

(-50ºC) 

Gas-

Powered 

(Normally 

Open)*

HCK2

HCK2

HCK2

HCK2

HCK2 HCK2

HCK2W

HCK2W

HCK5

HCK5

HCK5

HCK5

HCK5

HCK5

HCK5W

HCK5W

HS9B

HS9B

HS9B

HS9B

HS9B

HS9B

HS9BW

HS9BW

Hot Gas Line 

Solenoid Valve

HS8A

HS7 

HS4A

HS7 

HS4A

HS7 

HS4A

HS4A

HS4A

HS4A

Defrost Relief 

Regulator

HA4AK HA4AK HA4AK HA4AK HA4AK HA4AK

Defrost Relief 

Regulator w/Wide 

Opening

HA4AB HA4AB HA4AB HA4AB HA4AB HA4AB

Equalize Line and 

Soft Gas Solenoid 

Valve

HS8A

HS7 

HS4A

HS7 

HS4A

HS7 

HS4A

HS4A

HS4A

HS4A

Liquid Line and Drain 

Pan Check Valve

HCK4

HCK4

HCK4

HCK4

HCK4

HCK4

HCK4

Summary of Contents for FM-71

Page 1: ... specifically for defrosting industrial and large commercial refrigeration systems the Frost Master sequences solenoid valves and relays to provide quick and efficient defrosting of evaporator coils Because of its SPDT relays and time adjustable defrost steps this controller is suitable for almost every defrost application including top and bottom feed unit coolers blast freezer evaporators and ic...

Page 2: ...of defrosts per day or week by not defrosting unless necessary the time clock can be used to prevent defrost from happening when it would not be advantageous Temperature terminate contacts are provided to optionally connect a thermostat or other device for minimized defrost time The Remote Initiate models clockless require only an external momentary dry contact closure of the initiate terminals fr...

Page 3: ... begins Less liquid means more internal evaporator surface is exposed to entering hot gas It also reduces the amount of liquid accommodated by the system during defrost HOT GAS 0 to 45 minutes The HOT GAS step begins the actual melting of the frost accumulation The amount of time required to remove the frost is dependent on many factors including the following design of evaporator quantity of fros...

Page 4: ...and a time clock tab must trip before a defrost will begin In other words initiate for a clock equipped defrost controller will only occur if called for by an initiation device during a clock scheduled defrost period On the other hand a clockless Remote Initiate Model FM 01 FM 02 FMP 01 could initiate defrost any time the initiate device closed the terminals The Frost Master is supplied with a fac...

Page 5: ...vaporator shown on page 9 Other wiring schemes are possible to meet system requirements This wiring diagram is for illustration purposes only and does not show all controls and safety devices Final control wiring is the responsibility of the system designer See above table for relay operation Relays shown with no power to Frost Master See above for relay operation relay energized POWER INPUT RELAY...

Page 6: ...sture Field sensor wire size should be at least 20 AWG 0 5 mm2 and limited to a distance of 500 ft 152 m Avoid running wires through evaporator air stream or with high voltage wiring Connect field sensor wires to terminate temperature sensor quick disconnect plug inside defrost controller enclosure terminate temperature sensor INTRODUCTION This deluxe model Frost Master Plus includes an additional...

Page 7: ...ator shown on page 9 Other wiring schemes are possible to meet system requirements This wiring diagram is for illustration purposes only and does not show all controls and safety devices Final control wiring is the responsibility of the system designer See above table for relay operation Relays shown with no power to Frost Master Plus See above for relay operation relay energized POWER INPUT RELAY...

Page 8: ...al Typically the defrost relief regulator is set at about 70 psig 5 bar for ammonia When a defrost condensate liquid drainer is used an outlet pressure regulator in the hot gas supply line should be used to limit the internal evaporator pressure Check valves are installed after the liquid solenoid valve to prevent higher pressure gas from entering the liquid supply line during defrost Also check v...

Page 9: ...NOID VALVE WITH ELECTRIC SHUT OFF STOP VALVE OR REGULATOR OR GAS POWERED SUCTION SUCTION SOLENOID VALVE FOR EQUALIZING WITH WIDE OPENING FEATURE DEFROST RELIEF REGULATOR OVERFEED LIQUID LINE SUCTION LINE OVERFEED BOTTOM FEED EVAPORATOR TOP FEED EVAPORATOR EVAPORATOR WITH GAS POWERED SUCTION STOP VALVE EVAPORATOR WITH DEFROST CONDENSATE LIQUID DRAINER DEFROST RELIEF HOT GAS SOLENOID VALVE SOFT GAS ...

Page 10: ...frost melting can begin Typical rating at 86ºF to 10ºF is 7 5 lbs min 0 063 kg sec for ammonia and 24 5 lbs min 0 117 kg sec for R22 For greater capacities contact factory Inlet outlet connections combination FPT 1 Weld HD101 dEFROST CONDENSATE LIQUID DRAINER Mechanical non electrical float regulator drains liquid condensate from evaporator during defrost It has built in gas vent plus expansion va...

Page 11: ...se requires no pressure drop to operate Requires a single pilot solenoid valve to control Typically used to close off evaporators from system suction especially below 20F 30C HS9B GAS POWERED SOLENOID VALVE This valve uses a remote gas or liquid pressure source to close requires no pressure drop to operate Dual pilot solenoid valve assembly controls opening and closing of valve without internal bl...

Page 12: ...me of day and defrost start times WARRANTY Hansen defrost controllers are guaranteed against defective materials or workmanship for 90 days F O B our plant No consequential damages or field labor is included REMOTE INITIATE MODELS Remote Initiate Models FM 01 FM 02 and FMP 01 are supplied less any time clock and horizontal jumper wire The defrost begins when the initiate spade terminals are moment...

Reviews: