39
Holding Registers (4xxxx Addresses)
Address Register Function
Size
Min.
Value
Max.
Value
Default
Value Details
40146
CH2 Setpoint 2 minim OnTime
uint16_t
1
10
3
[seconds]
40147
CH2 Setpoint 2 Value
float
Low limit
parameter
High Limit
parameter
Param. default
control
Low part of float
(bytes
1‑0
)
40148
High part of float
(bytes
3‑2
)
40149
CH2 Setpoint 2 control action
uint8_t
0
1
0
0
= low direction
1
= high direction
40150
CH2 Setpoint 2 control period
uint16_t
10
1800
60
[seconds]
40151
CH2 Setpoint 2 deviation
float
Parameter
dependent
Parameter
dependent
Parameter
dependent
Low part of float
(bytes
1‑0
)
40152
High part of float
(bytes
3‑2
)
40153
CH2 Setpoint 2 hysteresis
float
Parameter
dependent
Parameter
dependent
Parameter
dependent
Low part of float
(bytes
1‑0
)
40154
High part of float
(bytes
3‑2
)
40155
CH2 Setpoint 2 reset time
uint16_t
60
60000
60000
[seconds]
40156
CH2 Setpoint 2 rate time
uint16_t
0
60000
0
[seconds]
40161
CH1 Main Param. Alarm High Enable
uint8_t
0
1
0
0
= Disable
1
= Enable
40162
CH1 Main Param. Alarm Low Enable
uint8_t
0
1
0
0
= Disable
1
= Enable
40163
CH1 Main Param. Alarm High
DelayOff Time
uint16_t
5
999
5
[seconds]
40164
CH1 Main Param. Alarm High
Mask Time
uint16_t
0
1800
5
[seconds]
40165
CH1 Main Param. Alarm High Value
float
Param. low
limit measured
Param. high
limit measured
Param. dep.
default
Low part of float
(bytes
1‑0
)
40166
High part of float
(bytes
3‑2
)
40167
CH1 Main Param. Alarm Low Value
float
Param. low
limit measured
Param. high
limit measured
Param. dep.
default
Low part of float
(bytes
1‑0
)
40168
High part of float
(bytes
3‑2
)
40169
CH1 Temp. Param. Alarm High Enable
uint8_t
0
1
0
0
= Disable
1
= Enable
40170
CH1 Temp. Param. Alarm Low Enable
uint8_t
0
1
0
0
= Disable
1
= Enable
40171
CH1 Temp. Param. Alarm High
DelayOff Time
uint16_t
5
999
5
[seconds]
40172
CH1 Temp. Param. Alarm High
Mask Time
uint16_t
0
1800
5
[seconds]
40173
CH1 Temp. Param. Alarm High Value
float
Param. low
limit measured
Param. high
limit measured
Param. dep.
default
Low part of float
(bytes
1‑0
)
40174
High part of float
(bytes
3‑2
)
40175
CH1 Temp. Param. Alarm Low Value
float
Param. low
limit measured
Param. high
limit measured
Param. dep.
default
Low part of float
(bytes
1‑0
)