18
Code
Valid Values
Default
PW
21 Relay 2 mode (M2)
same as relay 1
0
no
22 Relay 2 setpoint (S2)
0.5 to 99.5% full scale
75% f.s.
no
23 Relay 2 hysteresis (H2)
0 to 5% f.s.
1% f.s.
no
24 Relay 2 deviation (D2)
0.5 to 10% f.s.
1% f.s.
no
25 Relay 2 reset time
0.1 to 999.9 minutes
999.9
no
26 Relay 2 rate time
0.0 to 999.9 minutes
0.0
no
30 Alarm relay
0.5 to 99.5% full scale
95% f.s.
no
High Alarm (HA)
HA-Hys
U
LA
+
Hys,Hys
=
1.5%f.s.,HA
U
S1 or HA
U
S2
31 Alarm relay
0.5 to 99.5% full scale
5% f.s.
no
Low Alarm (LA)
LA
+
Hys
T
HA-Hys,Hys
=
1.5%f.s.,LA
T
S1 or LA
T
S2
32 Proportional control
1 to 30 min
5
no
mode period
33 Maximum relay ON time 1 to 10 min
10
no
(after which an alarm mode is entered)
34 Alarm mask time
00:00 to 30:00
00:00
no
40 Analog output selection
0: 0-1mA
2
no
1: 0-20 mA
2: 4-20 mA
3: 0-5 VDC
4: 1-5 VDC
5: 0-10 VDC
41 Analog output
0 to 100% full scale
0
no
lower limit (O_VARMIN)
(O_VARMIN
T
O_VARMAX - 5% f.s.)
42 Analog output
0 to 100% full scale
100% f.s.
no
upper limit (O_VARMAX)
(O_VARMIN
T
O_VARMAX - 5% f.s.)
60 Current day
01 to 31
from RTC
no
61 Current month
01 to 12
from RTC
no
62 Current year
1998 to 9999
from RTC
no
63 Current time
00:00 to 23:59
from RTC
no