39
OUTPUT
OUTPUT
OUTPUT
OUTPUT
OUTPUT
CALIBRATION
CALIBRATION
CALIBRATION
CALIBRATION
CALIBRATION
CALIBRATION
CALIBRATION
CALIBRATION
CALIBRATION
CALIBRATION
CALIBRATION
CALIBRATION
CALIBRATION
CALIBRATION
CALIBRATION
TYPE
TYPE
TYPE
TYPE
TYPE
CODE
CODE
CODE
CODE
CODE
POINT 1
POINT 1
POINT 1
POINT 1
POINT 1
POINT 2
POINT 2
POINT 2
POINT 2
POINT 2
0-1 mA
0
0 mA
1 mA
0-20 mA
1
0 mA
20 mA
4-20 mA
2
4 mA
20 mA
0-5 VDC
3
0 VDC
5 VDC
1-5 VDC
4
1 VDC
5 VDC
0-10 VDC
5
0 VDC
10 VDC
• Press CFM to confirm the selected parameter that will stop
blinking on the primary display. The secondary display shows
the HI 931002 or multimeter input value as lower limit of
the interval.
• Use the
ñ
or
ò
to make the HI
931002 or multimeter output cor-
respond to the meter’s value
shown on the secondary display
(e.g. 4).
• Wait for approximately 30 seconds (until the reading of the
calibrator is stable).
• Press CFM to confirm. The meter will switch to the second
calibration point. Repeat the above procedure.
• After the desired readings are obtained, press CFM and
the meter will skip back to normal operational mode.