94
PROBLEMS
PROBABILITY CAUSES
REMEDY / CORRECTIVE ACTION
Compressor losses
oil
Lack of refrigerant
Check for leaks. Charge additional refrigerant.
Improper system piping
Check and correct the piping or install an external oil
separator
Refrigerant fills back
Maintain suitable suction superheat at compressor
Low suction pressure
Lack of refrigerant
Check for leaks. Charge additional refrigerant.
Evaporator dirty or iced
Defrost or clean coil
Clogged liquid line filter drier
Replace the cartridge
Clogged suction line or compressor suction strainer
Clean or change suction strainer
Expansion valve malfunctioning
Check and reset for proper superheat
Condensing temperature too low
Check means for regulating condensing temperature
Note: The replacement of compressor internal parts should be perform only by a qualified / certified service
technician with full knowledge of HANBELL screw compressor or it should be a Service Engineer from
HANBELL.