111
Note:
It is strongly recommended to install a muffler or buffer before the economizer port because of nature of pulsation
caused by screw compressor.
ECO application by flash tank
Note : When apply the economizer to compressor, it is strongly recommended to install a economizer stop valve
before the economizer gas return port to operate as a buffer or muffler ( or install a muffer after stop valve as the
charts shown above) could efficiently prevent the vibration of piping caused by compression pulse.