HAMWORTHY HEATING LTD
57
Wessex ModuMax
mk3
Boilers
500001308/C
Individual boilers enabled from B.M.S. using 0
-
10V analogue input
Legend
E = End user
I = Commissioning
F = Heating engineer
Navistem settings
BMS 0
-
10v Power Control
Menu
Operating Line
User Level
Function
Setting
LPB System
6600
F
Device address
1
Configuration
5710
F
Heating circuit 1
Off
5950
F
Function input H1
Output req VK1 10v
5951
F
Contact type H1
NO
5953
F
Voltage value H1
0.1v
5954
F
Function value 1 H1
200 (200 = 20% modulation)
5955
F
Voltage value 2 H1
10.0v
5956
F
Function valve 2 H1
1000 (1000 = 100% modulation)
5890
F
Relay output QX1
Boiler pump Q1
BMS 0
-
10v Temperature
Menu
Operating Line
User Level
Function
Setting
LPB System
6600
F
Device address
1
Configuration
5710
F
Heating circuit 1
Off
5950
F
Function input H1
Consumer req VK1 10v
5951
F
Contact type H1
NO
5953
F
Voltage value H1
0.5v
5954
F
Function value 1 H1
0 (0 = 0°C)
5955
F
Voltage value 2 H1
10.0v
5956
F
Function valve 2 H1
800 (800 = 80°C)
5890
F
Relay output QX1
Boiler pump Q1
Note:
Use H1 wiring connection for 0
-
10V analog input from B.M.S.
Optional extras required for this configuration:
None
Boiler Parameter Settings: Multiple Boilers