HAMWORTHY HEATING LTD
26
Wessex ModuMax
mk3
Boilers
500001308/C
(Note:
Above readings taken with front cover removed and 200mm probe insertion CO = < 60 ppm*).
High Fire Target
Nat Gas
-
9.0% ±0.25% CO
2
LPG
-
10.6% ±0.25% CO
2
If combustion level is outside of this range use the
Throttle Screw to adjust the mixture.
T
HIS
SETTING
MUST
BE
CORRECT
BEFORE
CONTINUING
To increase the CO
2
level, turn the adjustment
anti
-
clockwise.
Figure 8.6.4
-
Adjusting gas valve throttle
Low Fire Target
Nat Gas 9.0% ±0.25% CO
2
LPG
-
10.6% ±0.25% CO
2
If combustion readings are outside target range use a
screwdriver to make adjustments
To increase the CO
2
level, turn the adjustment
clockwise.
Figure 8.6.5—Adjusting gas valve offset
97 / 116 / 147
97 / 116 / 147
196 / 254
196 / 254
If combustion is outside of the ranges defined below the factory sealed valves may be adjusted using the
following procedure :
High Fire Target
Nat Gas 9.0% ±0.25% CO
2
LPG
-
10.6% ±0.25% CO
2
If combustion level is outside of this range use the
Cross Head Throttle Screw to adjust the mixture.
T
HIS
SETTING
MUST
BE
CORRECT
BEFORE
CONTINUING
To increase the CO
2
level, turn the adjustment
anti
-
clockwise.
Figure 8.6.4
-
Adjusting gas valve throttle
Low Fire Target
Nat Gas 9.0% ±0.25% CO
2
LPG
-
10.6% ±0.25% CO
2
If combustion readings are outside target range use
Torx Bit to make adjustments
To increase the CO
2
level, turn the adjustment
clockwise.
Figure 8.6.5—Adjusting gas valve offset