HAMWORTHY HEATING LTD
35
SHERBORNE
500001167/E
APPENDIX A - GAS DATA
Natural Gas
LPG Propane
NOTE: - It is strongly recommended that on LPG installations, Gas Detection Equipment is fitted. This
equipment should be positioned near the boiler & at low level. It is also important that the space housing
the boiler is adequately ventilated at High & Low level; refer to Appendix D.
There are minimal differences between the propane & natural gas fired boilers :-
a) The addition of a control orifice located in the gas valve outlet - see figure11.4
b) Warning labels are attached to indicate the use of LPG.
c) The nominal gas inlet pressure for LPG should be 37mbar.
d) The target CO
2
value is detailed in the respective table.
GAS DATA
Gas Inlet Connection Pipe Thread Size
Rp 3/4”
Nominal Gas Inlet Pressure
-
mbar
20
Maximum Gas Inlet Pressure
-
mbar
25
Minimum Gas Inlet Pressure
-
mbar
12.5
Gas Flow Rate (maximum)
-
m
3
/h
Target CO
2
% at High / Low fire ±0.25%
8.7
7.4
GENERAL DATA
BOILER MODEL
Model
Sherborne
SE64he
Sherborne
SE71c
Boiler Input (maximum)
- kW (Gross)
77.7
Boiler Input (maximum)
- kW (Nett)
70.0
Boiler Input (minimum)
- kW (Gross)
15.5
Boiler Input (minimum)
- kW (Nett)
14.5
Boiler Output kW (minimum)
- kW
Boiler Output kW (maximum) condensing
- kW
-
71.3
Boiler Output (minimum) non-condensing
- kW
64.0
13.6
66.6
GENERAL DATA
BOILER MODEL
Model
Sherborne
SE64he
Sherborne
SE71c
Boiler Input (maximum)
- kW (Gross)
76.0
Boiler Input (maximum)
- kW (Nett)
70.0
Boiler Input (minimum)
- kW (Gross)
15.2
Boiler Input (minimum)
- kW (Nett)
14.0
Boiler Output kW (minimum)
- kW
Boiler Output kW (maximum) condensing
- kW
-
71.4
Boiler Output (minimum) non-condensing
- kW
64.0
13.6
66.5
GAS DATA
Nominal Gas Inlet Pressure
-
mbar
37
Maximum Gas Inlet Pressure
-
mbar
45
Minimum Gas Inlet Pressure
-
mbar
25
Gas Flow Rate (maximum)
- m
3
/h (kg/h)
2.9 (5.5)
Target CO
2
% at High / Low fire ±0.25%
10.0
Summary of Contents for Sherborne Series
Page 2: ......
Page 10: ...HAMWORTHY HEATING LTD 8 SHERBORNE 500001167 E 4 Boiler Layout Description 4 1 Accessory Pack...
Page 27: ...HAMWORTHY HEATING LTD 25 SHERBORNE 500001167 E...
Page 29: ...HAMWORTHY HEATING LTD 27 SHERBORNE 500001167 E 8 9 Wiring Diagram...
Page 30: ...HAMWORTHY HEATING LTD 28 SHERBORNE 500001167 E 8 10 Wiring Diagram LMU...
Page 53: ......
Page 54: ......