HAMWORTHY HEATING LTD
49
FLEET V series
500001213/G
Figure C6.1 - Flue equivalent lengths
Flue
Flue
Equivalent
lengths
(m)
Load
kW
Diameter
mm
Max
L
45°
90°
80
150
100
3
4
100
150
100
3
4
150
150
100
3
4
200
150
60
3
4
250
150
35
3
4
300
150
10
3
4
300
200
100
3
4
400
200
50
3
4
500
200
25
3
4
600
200
10
3
4
Accessory
Descrip on
HHL
Part
no
Flat
roof
fl
ashing
150Ø
532511174
200Ø
532511175
Pitched
roof
fl
ashing
150Ø
universal(25
‐
45°)
532511178
200Ø
(23
‐
27°)
532511179
200Ø
(33
‐
47°)
532511180
200Ø
(48
‐
52°)
532511181
Fixing
brackets
150Ø
532511033
200Ø
532511186
Figure C6.2 - Flue Accessories
NOTE
:
For all B23 flue installations, the HHL supplied air inlet filter (Pt. No. 532812008)
MUST
be fitted
Air inlet
R ear view
Side view
B23 Air Filter
B23 air inlet filter installed
In the instance that a B53 flue (ducted air inlet) is connected to a cascade (B23 outlet), the air inlet filters need
not be fitted and therefore can be discarded.