HAMWORTHY HEATING LTD
47
FLEET V series
500001213/G
APPENDIX C - FLUE DATA - Natural Gas
C1.0 FLUE SYSTEM
1. Detailed recommendations for flue systems are given in BS 6644, and IGE/UP/10. All flue discharges for plant
exceeding 150kW output must comply with the third edition of the 1956 Clean Air Act Memorandum.
WARNING: THE FLUE DISCHARGE FROM A FLEET BOILER WILL GENERATE A PLUME
AT THE TERMINAL EXIT. THIS MUST BE CONSIDERED WITH REGARD TO TERMINAL
LOCATION AND ADJACENT BUILDING FABRIC.
FOR B23 INSTALLATIONS THE AIR INLET FILTER (Pt. No. 532812008)
MUST
BE USED.
C1.1 General Requirements
The Fleet
V series boilers are designed to be used with natural draught or pressurised flues. Flue systems should
be designed in accordance with regulations and with reference to BS 6644 and IGE/UP/10.
The following points should be noted:
a. Due to the high thermal efficiency of the boiler, condensation will occur in the flue. It is strongly recommended
that the design of the flue system recognises this. HHL supply plastic flue components and suitable terminals to
discharge the flue gases safely. The Fleet flue systems supplied by Hamworthy are non UV stabilised polypropylene
and are therefore suitable for internal use only. For external flue runs and termination, either use the dedicated kits
supplied by Hamworthy or refer to a chimney specialist .
b. Care should be taken to ensure that the flue is installed such that any condensation is continuously drained.
Any flue system with a horizontal section should have a maximum slope of 3° upwards in the direction of the
exhaust gas flow. All joints should be such that any condensation is directed back down the slope to an open
drain connection in the flue. The drain pipe must be manufactured from a corrosion resistant material and be at
least 15mm diameter. It must also have a fall of at least 3° (approx. 50mm per meter) and connect to a drain via a
waste trap.
c. Boiler flue outlet sizes - A flue system designed with the same diameter as the boiler flue outlet may not provide
*
Note:-
Flue gas volumes are corrected to a flue gas temperature of 15°C and barometric pressure of
1013.25mbar.
FLUE DATA
BOILER MODEL
F40- 80V
F40-120V
F50-100V F50-150V
Flue connections - mm
150
150
150
150
Pressure at the boiler flue outlet - Pa/mbar
150/1.5 150/1.5 150/1.5 150/1.5
Approx. Flue Gas Volume @ 9% CO
2
- m
3
/h*
104 156 130 195
Approx. Flue Gas Temperature 80/60° (50/30°C) gross
60/ (40)
F60– 120V F60-180V
F70-140V F70-210V
Flue connections - mm
150
150
150
150
Pressure at the boiler flue outlet - Pa/mbar
150/1.5 150/1.5 150/1.5 150/1.5
Approx. Flue Gas Volume @ 9% CO
2
- m
3
/h*
156 234 182 273
Approx. Flue Gas Temperature 80/60° (50/30°C) gross
60/ (40)
F85– 170V F85-255V F100-200V F100-300V
Flue connections - mm
150
Pressure at the boiler flue outlet - Pa/mbar
150/1.5 150/1.5 150/1.5 150/1.5
Approx. Flue Gas Volume @ 9% CO
2
- m
3
/h*
220 330 260 390
Approx. Flue Gas Temperature 80/60° (50/30°C) gross
60/ (40)
150 150 150
F125– 250V F125-375V F150-300V F150-450V
Flue connections - mm
150
Pressure at the boiler flue outlet - Pa/mbar
150/1.5 150/1.5 150/1.5 150/1.5
Approx. Flue Gas Volume @ 9% CO
2
- m
3
/h*
326 489 390 585
Approx. Flue Gas Temperature 80/60° (50/30°C) gross
60/ (40)
200 150 200