HAMPTON BAY Hampton H25-NG Owners & Installation Manual Download Page 22

22

Hampton H25 Direct Vent Freestanding Gas Stove

Diagram 7

DURA-VENT VERTICAL

TERMINATION

1)

Maintain the 1-1/4" clearances (air spaces)
to combustibles when passing through
ceilings, walls, roofs, enclo-
sures, attic rafter, or other
nearby combustible surfac-
es. Do not pack air spaces
with insulation. Check page
10 for the maximum vertical
rise of the venting system and
the maximum horizontal offset
limitations.

2)

Set the gas appliance in its
desired location. Drop a
plumb bob down from the ceil-
ing to the position of the appli-
ance flue exit, and mark the
location where the vent will
penetrate the ceiling. Drill a
small hole at his point. Next,
drop a plumb bob from the roof
to the hole previously
drilled in the ceiling, and
mark the spot where the
vent will penetrate the
roof. Determine if ceiling
joists, roof rafters or oth-
er framing will obstruct

Diagram 4

Diagram  3

NOTE: For Snorkel terminations  in ABOVE

grade installations, follow national
or local code requirements.

Below Grade Snorkel Installation

If the Snorkel Termination must be installed
below grade, i.e. basement application,
proper drainage must be provided to pre-
vent water from entering the Snorkel Ter-
mination. Refer to Dura-Vent Installation
instructions for details.. Do not attempt to
enclose the Snorkel within the wall, or any
other type of enclosure.

4)

Install wall penetration heat shield in the
center of the 9-1/2" round hole and attach
with wood screws. The four wood screws
provided should be replaced with appropri-
ate fasteners for stucco, brick, concrete,
or other types of sidings. Dia. 3.

5)

If installing termination on a siding covered
wall, a vinyl siding standoff or furring strips
must be used to ensure that the termination
is not recessed into the siding.  Dia. 3.

6)

Take the Riser Vent terminal and separate
the Backing Plate from the Riser Vent Front
by removing 8 screws as shown in dia-
gram 4.

7)

Install the Backing Plate into the wall pene-
tration heat shield and attach using 4
screws. Dia. 4.

8)

Connect all pipe sections to unit and install
into wall:

a)

Measure pipe length required and cut to
length. Hint: use the cut end of the 6-5/8" dia.
outer pipe at the vent terminal end.

b)

Push the pipe sections completely together,
the minimum pipe overlap is 1-1/4".  Secure
all outer pipe joints by using at least two
screws. Locate the screws at the bottom
of the pipe so that the screw heads are
hidden on the final installation. Apply seal-
ant "Mill-Pac" to inner pipe and high temp
silicone sealant or "Mill-Pac" to outer pipe on
every joint.

Diagram 5

c)

Before connecting the vent pipe to the  vent
termination, slide the black decorative wall
thimble cover over the vent pipe, then slide
the Wall Penetration Heat Shield (Part #
946-202) over the vent pipe. Dia. 3.

d)

Slide the appliance and vent assembly
towards the wall carefully inserting the
vent pipe into the riser vent terminal assem-
bly. It is important that the vent pipe extends
into the Riser Vent Backing Plate a suffi-
cient distance so as to result in a minimum
pipe overlap of 1-1/4 inches. Secure the
connection between the vent pipe and the
vent cap by attaching the two sheet metal
strips extending from the Riser Vent Back-
ing Plate into the outer wall of the vent pipe.
Use two aluminum screws provided to
connect the strips to the pipe section. Bend
any remaining portion of the sheet metal
strip back towards the vent cap and cut off
any excess, it will be concealed by the
decorative wall thimble cover. See diagram
5.

8)

Slide the decorative wall thimble up to the
wall surface being careful not to scratch
the paint.  See diagram 5.

9)

Back outside: Apply sealant to the 4" inner
flue and slide the Riser Vent Front into the
Backing Plate and fasten with 8 screws.

IMPORTANT:
When connecting the pipe to the Riser
Vent, apply Mill-Pac to the inner pipe
on the Riser Vent Terminal, around
the bead. Ensure that the vent pipe is
pushed past the bead for a secure fit.

10)

Seal around the outer edge of the Riser
Vent Backing Plate.

Hint: Apply seal-
ant to female
end.

INSTALLATION

Summary of Contents for Hampton H25-NG

Page 1: ...What to do if you smell gas Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Foll...

Page 2: ...and crafted appliance and has been designed to provide you with all the warmth and charm of a wood fireplace at the flick of a switch The model H25 has been approved by Warnock Hersey for both safety...

Page 3: ...formation 6 Installation Checklist 6 Clearances to Combustibles 6 Locating Your Gas Stove 7 Manufactured Mobile Home Requirements 7 Combustion and Ventilation Air 7 Optional Fan Installation 7 Venting...

Page 4: ...ton units are constantly being improved Checkthelabelontheunitandifthere isadifference thelabelontheunitisthecorrect one For the State of Massachusetts installation and repair must be done by a plumbe...

Page 5: ...ured USA only or mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is not converti ble for use with other...

Page 6: ...onal Fan see page 7 3 Set vent restrictor page 9 4 Install venting Check all venting require ments pages 9 13 Vertical Termination with Co linear Flex System page 16 Hor izontal Termination Kits page...

Page 7: ...N OPTIONAL FAN INSTALLATION Fan Kit Contains Qty Description 1 Fan Assembly c w green wire attached 1 Thermodisc 1 power cord 2 2 1 4 x 20 hex nut 1 Fan Speed Control 2 Remove the rear access panel on...

Page 8: ...tove and secure with the 2 supplied bolts 2 1 4 20 hex head 12 Before re attaching the rear access panel the valve wires and the fan wires need to be connected Re connect the red and grey valve wires...

Page 9: ...y Warnock Hersey These units use the balanced flue technol ogy Co Axial system The inner liner vents productsofcombustiontotheoutsidewhilethe outer pipe draws outside combustion air into the combustio...

Page 10: ...p min 12 30cm with Riser Vent min 6 15cm H Not to be installed above a meter regulator assembly within 3 90cm horizontally from the centerline of the regulator J Clearance to service regulator vent ou...

Page 11: ...h 7 Black N A N A 4D7AB Adjustable Length 12 Galvinized N A N A 4D12A Adjustable Length 12 Black N A N A 4D12AB 45O Elbow Galvinized 945 4DT EL45 4D45L 45O Elbow Black 945B 4DT EL45B 4D45LB 45O Elbow...

Page 12: ...onal Ltd Dura Vent and Direct Vent GS are registered and or proprietary trademarks of Simpson Dura Vent Co Inc ThisproducthasbeenevaluatedbyIntertekfor using a Dura Vent Flue Adaptor in conjunction wi...

Page 13: ...he vent is ENCLOSED in a chase min size 9 x 9 maintain a 1 1 4 clearance to combustibles May be installed in Manufactured Mobile Homes after first sale Horizontal Terminations for All Venting Systems...

Page 14: ...ipe length is 30 feet with min of 8 feet total vertical and max 8 feet total horizontal Please note min 1 foot between 90o elbows is required With these options maxi mum total pipe length is 30 feet w...

Page 15: ...e note min 1 foot between 90o elbows is re quired Option H H1 V A 2 Max 2 Min B 3 Max 3 Min C 4 Max 4 Min D 5 Max 5 Min E 6 Max 6 Min Withtheseoptions max total pipelengthis30feetwithmin of 6 feet tot...

Page 16: ...ting Arrangements chart below for minimum and maximum flue lengths See chart below for minimumdistancesfromroof Periodicallycheck that the vent is unrestricted Masonry chimneys may take various contou...

Page 17: ...e to length Attach the 45o elbow to the rigid pipe and ensure that the pipe length when cut with the 45o elbow will seat onto both the starter collar and the 90o elbow Crimped sec tionofrigidpipeseats...

Page 18: ...fit of the liner onto the 4 dia starter collar 8 Cut the 4 dia flex liner to the desired size Hint leaveanextra12 to16 oflength this willmakethefinalassemblyeasiertowork with 9 Securethe4 dia flexline...

Page 19: ...to the wall It is also important to notethewallthickness Beforecuttingthevent hole through the wall ensure that ALL vent and termination clearances see page 10 will be met If this is an outside corner...

Page 20: ...pipe and nearby combustible surfaces is 1 1 4 inch Be sure to check the vent termination clearance require ments from decks windows soffits gas reg ulators air supply inlets and public walkways as sp...

Page 21: ...equired Other parts may be re quired for your particular installa tion See above for a list of vent parts Ifinstallingterminationonasidingcoveredwall a vinyl siding standoff or furring strips can be u...

Page 22: ...he Backing Plate into the wall pene tration heat shield and attach using 4 screws Dia 4 8 Connect all pipe sections to unit and install into wall a Measure pipe length required and cut to length Hint...

Page 23: ...re sili cone to the out er pipe before connecting the inner pipe 4 Assemblethedesiredlengthsofblackpipe and elbows necessary to reach from the appliance adapter up though the Round Support Box Insure...

Page 24: ...n place and sealed before installing a Direct Vent sys tem within the chimney If the appliance shuts off during opera tion contact a qualified service person to determine if a negative pressure and or...

Page 25: ...rities and the CAN CGA B149 installation codes ForUSAinstallationsfollowlocalcodesand or the current National Fuel Gas Code ANSI Z223 1 When using copper or flex connectors use onlyapprovedfittings Al...

Page 26: ...authorized Hampton Installer at the time of installation or service 4 Light the pilot and turn the valve to ON position Read manometer 5 The pressure check should be carried out with the unit burning...

Page 27: ...hold on to the elbow behind the orifice 9 Reinstall new burner orifice LP stamped 54 and tighten 10 Reverse steps 3 to 2 11 Attach the Conversion label This unit has been converted to Propane on top...

Page 28: ...lly and refer to the dia grams If the logs are broken do not use the unit until they are replaced Broken logs can interfere with the pilot operation The gas log kit contains the following a Rear Log 9...

Page 29: ...oto below 7 Place the center cross log on the locating pin in the top of the rear log and position as shown below Logs must be oriented as shown below 8 Test fire to ensure proper light off make sure...

Page 30: ...n interior wall Hamptonoffersanoptionalprogrammablether mostat but any 250 750 millivolt rated non anticipator type thermostat that is CSA ULC or UL approved may be used 14 GA 16 GA 18 GA 20 GA 22 GA...

Page 31: ...are away from sharp edges WARNING Electrical Grounding Instructions This appliance is equipped with a three pronged grounding plug for your protection against shock haz ard and should be plugged dire...

Page 32: ...rocess Theglassshould be cleanedor the film will bake on and become very difficult to remove Use a non abrasive cleaner and NEVER clean the glass while it is hot 1 TurnstoveOFFusingtheBurner ON OFF sw...

Page 33: ...Hampton H25 Direct Vent Freestanding Gas Stove 33 Copy of the Lighting Plate instructions OPERATING INSTRUCTIONS...

Page 34: ...Body Firebox Different types and thicknesses of steel will expandandcontractatdifferentratesresulting in some cracking and ticking sounds will be heard throughout the cycling process WARNING CHILDREN...

Page 35: ...ions orfittingshavebeendisturbed andconse quently loosened Also check mechanical supportssuchasWallStraps orplumbers tape for rigidity 5 Verify proper operation after servicing LOG REPLACEMENT Theunit...

Page 36: ...alve assembly continue 14 Remove two 2 thermopile wires 15 Removethermocouplewitha9mm metric wrench 16 Remove pilot nut with an 11 mm wrench 17 Remove valve to orifice nut with a 13 16 wrench 18 Remov...

Page 37: ...tion Part Description Part Description 50 W260260 Top Relief Frame Gasket 51 942 117 Top Relief Frame 52 W260280 Top Relief Plate Gasket 53 290 021 Top Relief Plate 54 Capscrew 1 4 x 1 3 4 NC 55 Side...

Page 38: ...Pilot Assy S I T 3 flame LP 67 Pilot Holder 68 W840470 Pilot Assembly Gasket 69 Valve Shield 70 Valve Bracket 71 260 042 Valve Gasket 73 Valve Cover Plate 74 Valve Access Door 75 350 930 Log Set Part...

Page 39: ...turned to FPI and evaluated for manufacturer defect The authorized selling dealer is responsible for all in field service work carried out on your Waterford product FPI will not be liable for results...

Page 40: ...________________________________________________ Printed in Canada Hampton is a trademark of FPI Fireplace Products International Ltd Hampton fireplace products are designed with reliability and simpl...

Reviews: