ROOF
Pa
ra
pe
t
W
all
If Air intake is below
Parapet wall. Air intake
must be Min. 10' away
3/4"=1'
Reference dimensions are ± 10%
All dimensions are ± 1"
Custom
Dwg No.
Customer / Job name:
Scale:
Description:
Drawn/
Revised by:
Checked/
Apv. by:
Revision:
MM/DD/YY
Date:
1/4" per ft. slope to appliance
All horizontal runs must be
supported every 24"
Air intake
90º Elbow w/
Bird Screen
Exhaust w/
Coupler &
Bird Screen
24" or 12" above
Maximum snow level
whichever is greater
18" Minimum
24" Maximum
8" Minimum
Min. 12" Above
Parapet wall if
within 10' of wall
Recommended Drain
Fitting Before Vertical Run
1/4” per ft. slope to appliance.
All horizontal runs must be supported
every 24” (CPVC only)
Recommended Drain Fitting Before
Vertical Run (CPVC only)
With HOT Controls
by Hamilton Engineering Co., Inc.
35
PART 4. VENTING
(FIGURE 4-4) VERTICAL VENT WITH PVC/CPVC