61
PART 7. SERVICING
(TABLE 7-3) BCB HARD LOCKOUT (HLO) CODES
Code
Cause
Recommended Action
A1/A2
Excessive pressure differential (∆P) on water side of heat exchanger
Check for scaling or blockage on water side of heat exchanger, also check pump performance.
B03
Neutralizer/trap has little or no Condensate (water)
Fill neutralizer (or trap if not a factory neutralizer) with water to avoid flue gases spilling into the
room through a dry trap.
B04
Pressure at flue/condensate sensor is too low
Check flue gas vent connection or sensor connection located at condensate drain line. Also
check for a disconnected or open condensate drain line and last, look for a leak in the heat
exchanger outer casing (behind the insulation).
DW7
Temperature rise (∆T) through heat exchanger is too high
Appliance has been through multiple tests and checks including operating at a reduced input to
avoid this shut down. The ∆P across the heat exchanger indicates reduced water flow. Check the
pump performance, check for partially closed valves and if all ok, perform a descaling operation
on the water side of the heat exchanger.
FL01
Flue gas temperature has exceeded the maximum safe level set in the
operating parameters
Flue gas temperature setting has been exceeded by a significant amount even after operation at
a reduced firing rate. Check entire burner assembly, if ok, then a complete fire side cleaning must
be initiated immediately.
FL05
Flue gas temperature too high
Unit is burning at a reduced BTU input rate. The cause of the high flue gas should be investigated
and corrected ASAP—See FL01
FL09
Fire side of heat exchanger is severely fouled
Remove burner and check condition of fire side of tubes in the burner area.
G01
Gas pressure too low
Find cause of low pressure and correct; piping or regulator sizing is the general culprit
G03
Gas pressure too high during a burn cycle
Correct the cause of the high gas pressure - either adjust regulator or replace and repair as
required - maximum allowed by code is 14"w.c.
H15/H16
Water temperature limit set point exceeded
Check set point(s), sensors, pumping etc. Correct cause of high water temperature
H24
Water Temperature Manual Reset High Limit set point exceeded
Check set point(s), sensors, pumping etc. Correct cause of high water temperature
ID01
First INI process data missing
Run the Z-INI; starting Initialization numbers must be tested and the saved for all connected
sensors in a number of conditions.
ID02
EMB EEPROM fault (2)
Reset the fault, cycle power on and off, if the fault reappears, the EMB–EEPROM is corrupted.
ID03
No valid data on microcontroller Flash memory
Reset the fault, cycle power on and off, if the fault reappears, the EMB–EEPROM is corrupted.
ID04
Internal fault (gv1)
Reset the fault, cycle power on and off, if the fault reappears, the EMB–EEPROM is corrupted.
ID05
Internal fault (gv2)
Reset the fault, cycle power on and off, if the fault reappears, the EMB–EEPROM is corrupted.
ID06
Internal fault (gv3)
Reset the fault, cycle power on and off, if the fault reappears, the EMB–EEPROM is corrupted.
ID09
Fan speed error
Cycle power off, check the four-wire fan connection; wires and each end at connectors. If all ok,
cycle power back on and if fan Speed error reappears, replace fan.
ID12
Flue thermostat open.
Check for open flue temperature switch, if parameter S24=1
ID89
Fan is not running
Either fan is not running (check wiring or replace), or factory programming has been altered
(consult factory).
ID96
Wrong EEPROM key connected
Install proper EMB EEPROM, if it cannot be found, contact the factory for assistance - be sure to
have model and serial number of the appliance in question.
ID99
BDB Reset action finished
There have been too many resets, a concerted effort must be made to find the cause of the fault
and correct it. This is a timed action, and the unit cannot be reset until the time has elapsed.
Contact the factory with further questions. This fault will require both a power reset and then an
on-screen fault reset via the HISTORY tab.
IG2/IG3
Too many restarts or relights after no-flame.
Appliance has been through multiple tests and checks including trying to ignite at different inputs
to avoid this shut down. Combustion related items must be checked, including air/gas ratio,
ignition cable and igniter. Check flow switch if installed.
IG4/IG5
Too many restarts or relights after no-flame.
Appliance has been through multiple tests and checks including trying to ignite at different inputs
to avoid this shut down. Combustion related items must be checked, including air/gas ratio,
ignition cable and igniter. Check flow switch if installed.
IG19
Too many attempts for ignition
Appliance has been through multiple tests and checks including trying to ignite at different inputs
to avoid this shut down. Combustion related items must be checked, including air/gas ratio,
ignition cable and igniter. Check flow switch if installed.
IG27
Too many attempts for ignition
Appliance has been through multiple tests and checks including trying to ignite at different inputs
to avoid this shut down. Combustion related items must be checked, including air/gas ratio,
ignition cable and igniter. Check flow switch if installed.
P04
Low or no water flow
Check for pump electrical issues i.e. no power to the pump, pump motor is seized, pump is
constantly powered and running.
S13
Additional safety circuit (terminals 20, 21) open
Check flow switch, burner door and heat exchanger rear wall high temperature limits
E. APPLIANCE HARD LOCKOUT CODES
Summary of Contents for XL800
Page 6: ...6 PART 1 GENERAL INFORMATION As a Stand Alone Appliance HOT CONTROL MENU NAVIGATION ...
Page 7: ...7 PART 1 GENERAL INFORMATION Appliance as Part of a Cascade HOT CONTROL MENU NAVIGATION ...
Page 19: ...19 PART 2 ELECTRICAL B INTERNAL WIRING CONNECTION continued XL BCB LAYOUT ...
Page 21: ...21 PART 2 ELECTRICAL XL CASCADE BOX ...
Page 31: ...31 PART 4 VENTING Direct Vent Terminal Clearances ...
Page 33: ...33 PART 4 VENTING Other Than Direct Vent Terminal Clearances continued ...
Page 69: ...69 PART 10 PARTS BREAKDOWN 1A 1B PART 10 PARTS BREAKDOWN 2 ...
Page 70: ...70 PART 10 PARTS BREAKDOWN 3 4 5 6 7 8 9A 9B 9C 10 4 ...